05000458/LER-2018-003, Condition Prohibited by Technical Specifications Due to Untimely Recognition of Failed Laboratory Analysis of Ventilation Charcoal Sample
| ML18170A346 | |
| Person / Time | |
|---|---|
| Site: | River Bend |
| Issue date: | 06/19/2018 |
| From: | Maguire W Entergy Operations |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| RBG-47874 LER 2018-003-00 | |
| Download: ML18170A346 (5) | |
| Event date: | |
|---|---|
| Report date: | |
| Reporting criterion: | 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor 10 CFR 50.73(a)(2)(v), Loss of Safety Function |
| 4582018003R00 - NRC Website | |
text
Entergx RBG-47874 June 19, 2018 Attn: Document Control Desk U.S. Nuclear Regulatory Commission 11555 Rockville Pike Rockville, MD 20852-2738
Subject:
Dear Sir or Madam:
Licensee Event Report 50-458 I 2018-003-00 River Bend Station, Unit 1 Docket No. 50-458 License No. NPF-47 Entergy Operations, Inc.
River Bend Station 5485 U.S. Highway 61 N St. Francisville, LA 70775 Tel 225-381-4374 William F. Maguire Site Vice President In accordance with 10 CFR 50.73, enclosed is the subject Licensee Event Report. This document contains no commitments. If you have any questions, please contact Mr. Tim Schenk at 225-381 -4177.
Sincerely, WFM/twf Enclosure cc:
(with Enclosure)
U.S. Nuclear Regulatory Commission Attn: Ms. Lisa M. Regner, Project Manager 09-D-14 One White Flint North 11555 Rockville Pike Rockville, MD 20852 U.S. Nuclear Regulatory Commission Region IV 1600 East Lamar Blvd.
Arli ngton, TX 76011-4511
RBG-47874 Page 2 of 2 NRC Senior Resident Inspector Attn: Mr. Jeff Sowa 5485 U.S. Highway 61, Suite 1 St. Francisville, LA 70775 Public Utility Commission of Texas Attn: PUC Filing Clerk 1701 N. Congress Avenue P. O. Box 13326 Austin, TX 78711-3326 INPO (via ICES reporting)
RBF1 0126
NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY OMB: NO. 3150~104 EXPIRES: 03/31/2020 (04-2018)
Esl,maled, the NRC may n01 conduct or sponsor. and a person Is nol required to respond to the Information coIection.
- 3. Page R iver Bend Station -
Unit 1 458 3
05000 1
OF
- 4. Title Condition Prohibited by Technical Specifications due to Untimely Recognition of Failed Laboratory Analysis of Ventilation Charcoal Sample
- 5. Event Date
- 6. LER Number
- 7. Report Date
- 8. Other Facilities Involved Month Day Year Vear I Sequential I Rev Facility Name Docket Number Number No.
Month Day Year NA 05000 NA Facility Name Docket Number 04 30 2018 2018 -
003 -
00 06 19 2018 NA NA 05000
- 9. Operating Mode
- 11. This Report is Submitted Pursuant to the Requirements of 10 CFR §: (Check all that apply) 0 20.2201(b) 0 20.2203(a)(3)(i) 0 50.73(a)(2)(1I)(A) 0 50.73(a)(2)(viil)(A) 0 20.2201(d) 0 20.2203(a)(3)(1I) 0 50.73(a)(2)(II)(B) 0 50.73(a)(2)(vlll)(B) 1 0 20.2203(a)(1 )
0 20.2203(a)(4 )
0 50.73(a)(2)(lIi) 0 50.73(a)(2)(lx)(A) 0 20.2203(a)(2)(i) 0 50.36(c)(1 )(I)(A) 0 50.73(a)(2)(lv)(A) 0 50.73(a)(2)(x)
- 10. Power Level 0 20.2203(a)(2)(II) 0 50.36(c)(1 )(II)(A) 0 50.73(a)(2)(v)(A) 0 73.71(a)(4) 0 20.2203(a)(2)(IiI) 0 50.36(c)(2) 0 50. 73(a )(2)(v)(B) 0 73.71(a)(5) 0 20.2203(a)(2)(lv) 0 50.46(a)(3)(II) 0 50.73(a)(2)(v)(C) 0 73.77(a)(1 )
100 0 20.2203(a)(2)(v) 0 50.73(a)(2)(I)(A) 0 50.73(a)(2)(v)(D) 0 73.77(a)(2)(1) 0 20.2203(a)(2)(vi)
[2] 50.73(a)(2)(I)(B) 0 50.73(a)(2)(vil) 0 73.77(a)(2)(1I) 0 50.73(a)(2)(I)(C) 0 Other (Specify in Abstract below or in PREVIOUS OCCURRENCE EVALUATION There have been no similar events reported by RBS in the last five years.
SAFETY SIGNIFICANCE
I YEAR 8 -1 SEQUENTIAL REV NUMBER NO.
003 1-0 The Division II CRFA system was considered to be Inoperable from the time the charcoal sample was obtained to the time the charcoal was replaced. However, the Division I CRFA system was Operable for the duration of this event.
Furthermore, the Division II CRFA system was returned to Operable status three days from the time of discovery. This event was of minimal significance to the health and safety of the public.
(NOTE: Energy Industry Identification System component function identifier and system name of each component or system referred to in the LER are annotated as (**XX**) and [XX], respectively.) Page 3
of 3