05000454/FIN-2013007-01
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Inadequate Identification of Fire Curtain Sprinkler Degradation for an Auxiliary Building Stairwell |
| Description | The inspectors identified a finding of very low safety significance and an associated NCV of Byron Operating License (OL) Condition 2.C.6 for Unit 1 and 2.E for Unit 2 when licensee personnel failed to identify that a fire sprinkler curtain on Elevation 346 had degraded. Specifically, a ball valve had a twisted stem, which had the effect of indicating that an isolation valve was fully open, when in fact it was significantly closed. As part of their immediate corrective actions, the licensee declared the auxiliary building Elevation 346 fire curtain inoperable and initiated compensatory measures that included fire watches until the isolation valve stem was replaced. The licensee entered this issue into their CAP as IR 1560667, Adverse Trend in Main Drain Results for 346 AB [Auxiliary Building] Sprinkler System. The performance deficiency was determined to be more than minor because it was associated with the External Factors attribute of the Initiating Events cornerstone and adversely affected the cornerstone objective of limiting the likelihood of those events that upset plant stability and challenge critical safety functions during shutdown as well as power operations. The inspectors determined that the finding could be evaluated using the SDP in accordance with IMC 0609, Appendix F, Fire Protection Significance Determination Process, because it was associated with fire protection defense-in-depth strategies involving fire confinement. The inspectors determined that while flow to the sprinkler heads was significantly degraded, because less than 10 percent of the heads were obstructed or fouled, and no adjacent heads were fouled, the water curtain had a low degradation rating in accordance with IMC 0609, Appendix F, Attachment 2. Therefore, in accordance with IMC 0609, Appendix F, Attachment 1, Step 1.3.1.B, the finding was determined to be of very low safety significance (Green). This finding had a cross-cutting aspect in the CAP component of the PI&R cross-cutting area (P.1.(a)), because licensee personnel twice failed to identify the degraded sprinkler curtain and when NRC personnel identified the issue and informed licensee personnel, the issue was not entered into the licensees CAP in a timely manner. |
| Site: | Byron |
|---|---|
| Report | IR 05000454/2013007 Section 4OA2 |
| Date counted | Sep 30, 2013 (2013Q3) |
| Type: | NCV: Green |
| cornerstone | Initiating Events |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71152 |
| Inspectors (proximate) | A Dahbur B Bartlett C Thompson E Duncan M Jones N Shah |
| Violation of: | License Condition - Fire Protection |
| CCA | P.1, Identification |
| INPO aspect | PI.1 |
| ' | |
Finding - Byron - IR 05000454/2013007 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Byron) @ 2013Q3
Self-Identified List (Byron)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||