Finding | |
---|---|
Title | Sprinkler System in Cable Spreading Room A Does Not Meet Licensee\'s Fire Protection Program Requirements |
Description | The team identified a non-cited violation of Shearon Harris Unit 1 operating license condition 2.F, for the licensees failure to install the sprinkler system in Cable Spreading Room A (CSRA) in accordance with the approved fire protection program (FPP). Specifically, the installed system would not have been able to deliver the sprinkler system design density of 0.3 gallons per minute/square foot in CSRA, as stated in the FPP in Updated Final Safety Analysis Report Section 9.5.1.2.3. The licensee entered this issue in the corrective action program and established a continuous fire watch in CSRA as a compensatory measure in accordance with the Shearon Harris FPP. The licensees failure to install the sprinkler system in CSRA in accordance with the approved FPP is a performance deficiency. This finding is more than minor because the installed sprinkler system degraded one of the fire protection defense in depth elements and it affected the reactor safety Mitigating Systems cornerstone objective. The team completed a Phase 2 screening of the finding in accordance with IMC 0609, Appendix F, Attachment 1, Part 2, Fire Protection SDP Phase 2 Worksheet, and concluded that the finding was of very low safety significance (Green), in accordance with Step 2.5, Task 2.5.5 of the Worksheet, because there was a safe shutdown path available which was independent of CSRA. The cause of this finding was not associated with a cross-cutting area because it is not reflective of current licensee performance. (Section 1R05.04 |
Site: | Harris ![]() |
---|---|
Report | IR 05000400/2008008 Section 1R05 |
Date counted | Dec 31, 2008 (2008Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.05 |
Inspectors (proximate) | N Merriweather N Staples B Melly M Thomas L Suggs K Miller O Lopez |
INPO aspect | |
' | |
Finding - Harris - IR 05000400/2008008 | ||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Harris) @ 2008Q4
Self-Identified List (Harris)
| ||||||||||||||||||||||||||||||||||||||||||