05000382/FIN-2009005-02
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Reactor Coolant Pump Vapor Seal Leakage |
| Description | A self-revealing Green noncited violation of 10 CFR Part 50, Appendix B, Criterion XVI, was identified for the licensees failure to promptly correct a condition adverse to quality. Specifically, the licensee did not promptly correct reactor coolant pump vapor seal leakage that resulted in boric acid accumulation on the component cooling water heat exchanger and cover areas of three reactor coolant pumps. Corrective actions for this condition were implemented during Refueling Outage 15, but these corrective actions failed to correct the condition and the vapor seal leakage continued through operating Cycle 16. This resulted in some additional boric acid corrosion and degradation to reactor coolant pump covers and carbon steel component cooling water flanges. The licensee implemented a design modification to correct the condition and documented the condition in Condition Report CR-WF3-2009-5501. The licensees failure to promptly correct a condition adverse to quality is more than minor because it is associated with the equipment performance attribute of the Initiating Events Cornerstone and affects the cornerstone objective to limit the likelihood of those events that upset plant stability. The finding has very low safety significance because, although the finding contributes to the likelihood of a reactor trip, mitigation equipment was still available. This finding had a crosscutting aspect in the area of human performance associated with work control in that the licensee did not effectively plan for the resources necessary to implement the postmaintenance testing associated with the corrective actions implemented during Refueling Outage 15, and therefore failed to discover that those corrective actions were inadequate to correct the condition H.3(a) (Section 4OA2) |
| Site: | Waterford |
|---|---|
| Report | IR 05000382/2009005 Section 4OA2 |
| Date counted | Dec 31, 2009 (2009Q4) |
| Type: | NCV: Green |
| cornerstone | Initiating Events |
| Identified by: | Self-revealing |
| Inspection Procedure: | IP 71152 |
| Inspectors (proximate) | L Ricketson P Elkmann J Clark R Azua D Overland M Bloodgood S Anderson T Buchanan N Greene |
| CCA | H.5, Work Management |
| INPO aspect | WP.1 |
| ' | |
Finding - Waterford - IR 05000382/2009005 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Waterford) @ 2009Q4
Self-Identified List (Waterford)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||