05000373/FIN-2011004-01
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Non-Conservative Voltage Input for Motor Starting Calculations |
| Description | The inspectors identified a finding of very low safety significance (Green) and associated NCV of Title 10 Code of Federal Regulations (CFR) Part 50, Appendix B, Criterion III, Design Control, involving the licenseei12s failure to perform adequate analysis to demonstrate that safety-related motors would start during a design basis event. The licensee entered this issue into the corrective action program (CAP) as Action Report (AR) 01139601 and conducted preliminary analysis to verify operability. The licenseei12s failure to perform adequate analysis to demonstrate that motors would start during block loading was determined to be more than minor because there was reasonable doubt as to whether motors which are required to start at the onset of an accident would have adequate voltage to start, pending reanalysis. The inspectors determined that this was a design deficiency that did not result in loss of operability or functionality; and therefore, the finding was of very low safety significance (Green). This finding was determined not to have a cross-cutting aspect |
| Site: | LaSalle |
|---|---|
| Report | IR 05000373/2011004 Section 1R21 |
| Date counted | Sep 30, 2011 (2011Q3) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.21 |
| Inspectors (proximate) | N Shah R Ruiz F Ramirez K Riemer S Sheldon M Mitchell B Kemker D Jones J Yesinowski P Smagacz J Corujo-Sandin P Cardona-Morales |
| INPO aspect | |
| ' | |
Finding - LaSalle - IR 05000373/2011004 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (LaSalle) @ 2011Q3
Self-Identified List (LaSalle)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||