05000362/LER-2005-001, Regarding Emergency Diesel Generator (EDG) 3G003 Declared Inoperable Due to Loose Wiring Connection on Emergency Supply Fan

From kanterella
(Redirected from 05000362/LER-2005-001)
Jump to navigation Jump to search
Regarding Emergency Diesel Generator (EDG) 3G003 Declared Inoperable Due to Loose Wiring Connection on Emergency Supply Fan
ML052380299
Person / Time
Site: San Onofre 
Issue date: 08/23/2005
From: Breig D
Southern California Edison Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
LER 05-001-00
Download: ML052380299 (6)


LER-2005-001, Regarding Emergency Diesel Generator (EDG) 3G003 Declared Inoperable Due to Loose Wiring Connection on Emergency Supply Fan
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition

10 CFR 50.73(a)(2)(ix)(A)

10 CFR 50.73(a)(2)(iii)

10 CFR 50.73(a)(2)(x)

10 CFR 50.73(a)(2)

10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor

10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat

10 CFR 50.73(a)(2)(v), Loss of Safety Function

10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications

10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)(viii)(A)

10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded

10 CFR 50.73(a)(2)(viii)(B)
3622005001R00 - NRC Website

text

SOUIHURN CALIEORNIA EDISON' An EDISON INIRV X7I/O,.

I Company Daniel P. Breig. P.E.

Station Manager San Onofre August 23, 2005 U.S. Nuclear Regulatory Commission Document Control Desk Washington, D.C. 20555-0001

Subject:

Docket No. 50-362 Licensee Event Report No. 2005-001 San Onofre Nuclear Generating Station, Unit 3

Dear Sir or Madam:

On June 26, 2005, Southern California Edison (SCE) made a phone report to the NRC for a condition affecting the emergency diesel generators (EDGs) at San Onofre Unit 3.

SCE subsequently determined that both Unit 3 EDGs remained operable and a report to the NRC was not required.

The original phone report (Event Log No. 41798) was retracted by phone on August 23, 2005. SCE is providing this voluntary LER to document this condition and inform the NRC of the corrective actions taken.

If you require any additional information, please contact me.

Unit 3 LER No. 2005-001 cc:

B. S. Mallett, NRC Regional Administrator, Region IV C. C. Osterholtz, NRC Senior Resident Inspector, San Onofre Units 2 & 3 P.O. Box 128 San Clemente. CA 92674-0128 949-368-9263/PAX 89263 Fax 949-368-6183 breigdp@songs.sce.com

NRC FORM 366 U.S. NUCLEAR REGULATORY APPROVED BY OMB: NO. 3150-010D4 EXPIRES: 06/30/2007 (7-2001)

COMMISSION

, the NRC may not conduct or sponsor, and a person Is not required to respond to, the Information collection.

3. PAGE San Onofre Nuclear Generating Station (SONGS) Unit 3 05000-362 l

1 OF5

4. TITLE Emergency Diesel Generator (EDG) 3G003 Declared Inoperable Due to Loose Wiring Connection on Emergency Supply Fan
5. EVENT DATE
6. LER NUMBER
7. REPORT DATE
8. OTHER FACILITIES INVOLVED T

FACIUTY NAME DOCKET NUMBER MO DAY YEAR YEAR MO DAY REVAM FACILITY NAME DOCKET NUMBER 06 26 2005 2005-001-00 08 23 2005

9. OPERATING
11. THIS REPORT IS SUBMIlTED PURSUANT TO THE REOUIREMENTS OF10 CFR 5: (Check all that apply)

MODE 20.2201 (b) 20.2203(a)(3)(ii) 50.73(a)(2)(ii)(B) 50.73(a)(2)(ix)(A)

10. POWER 20.2201(d) 20.2203(a)(4) 50.73(a)(2)(iii) 50.73(a)(2)(x)

LEVEL _ _

_20.2203(a)(1) 50.36(c)(1)(i)(A) 50.73(a)(2)(tv)(A) 73.71 (a)(4) 20.2203(a)(2)(i)

_ 50.36(c)(1)(ii)(A)

_ 50.73(a)(2)(v)(A) 73.71(a)(5) 20.2203(a)(2)(ii) 50.36(c)(2) 50.73(a)(2)(v)(B)

OTHER

,0.2203(a)(2)(ii)

,_SpecIfy In Abstract below or In NRC Form 20.2203(a)(2)(iv) 50.46(a)(3)(ii) 50.73(a)(2)(v)(D) 20.2203(a)(2)(v)

_ 50.73(a)(2)(i)(B)

_ 50.73(a)(2)(vii)

Voluntary 20.2203(a)(2)(vi) 50.73(a)(2)(iD(C) 50.73(a)(2)(viii)(A) 20.2203(a)(3)(i) 50.73(a)(2)(ii)(A) 50.73(a)(2)(viii)(B)

12. LICENSEE CONTACT FOR THIS LER NAME TELEPHONE NUMBER (Include Area Code)

D. P. Breig, Station Manager, Nuclear Generation 1949-368-9263CAS YTM COMONNT MANU-REPORTABLE CAS YTM CMOET MANU-REPORTABLE TO FACRMPONENT FACU TO EPIX CAUS E S C M E

FACTURER EPIX N

l

14. SUPPLEMENTAL REPORT EXPECTED
15. EXPECTED l

MONTH DAY YEAR SUBMISSION r

YES (If yes, complete EXPECTED SUBMISSION DATE)

I X fNO DATE l

1 b. ABSTRAL;T (Limit to 14UU spaces, i.e., approximately 1 b single-spaced typewritten lines)

On 06/25/2005, at about 1335 PDT, during a routine surveillance test of EDG 3G003, Emergency Supply Fan 3MA276 did not start. SCE operators declared 3G003 inoperable. SCE traced the fan failure to start to a loose electrical connection. SCE also found the same contact for 3G003 fan 3MA277 loose, but the fan still started. These connections were tightened; other connections were confirmed to be acceptable. EDG 3G003 was start tested and declared operable at 0406 PDT on 06/26/2005.

EDG 3G002 was inspected and other connections were found not completely tight. SCE could not conclusively determine if those connections would have caused 3G002 inoperability and conservatively declared 3G002 inoperable at 0459 PDT on 06/26/2005. This event was reported to the NRC on 06/26/2005 (Event Log No. 41798) in accordance with 10CFR50.72(b)(3)(v)(D).

It was subsequently determined that the connections found on 3G002 did not affect its operability and 3G002 remained operable and available to fulfill its design and safety function.

On 08/23/2005, SCE retracted its 06/26/2005 phone report (Event Log No. 41798) and is providing this LER to document this event and inform the NRC of the corrective actions taken.U.S. NUCLEAR REGULATORY COMMISSION (7-2001)

LICENSEE EVENT REPORT (LER)

TEXT CONTINUATION

1. FACILBTY NAME
2. DOCKET NUMBER I

S. LER NUMBER I PAGE p3 San Onofre Nuclear Generating Station (SONGS) Unit 3 2005

- 1
- 3 00 2 of 5 Plant:

San Onofre Nuclear Generating Station (SONGS) Unit 3 Event Date:

June 26, 2005 Reactor Vendor:

Combustion Engineering Mode:

Mode 1 - Power Operation Power:

100 percent

Background

San Onofre Unit 3 has two Emergency Diesel Generators (EDGs) [EK] to provide emergency AC power if normal AC power is unavailable. For EDG room cooling, each EDG has two emergency supply fans [FANS]. The fans are designed to keep EDG building air temperature below 122 degrees F when the EDG is running. The emergency supply fans are automatically placed in operation upon receipt of a corresponding EDG start signal.

Technical Specifications (TS) 3.8.1 requires two EDGs to be operable during Modes 1-4. If one EDG is inoperable, TS 3.8.1, Action B requires SCE to restore the EDG to operable status in 14 days and TS 3.8.1, Action B.3.1 requires SCE to investigate and determine if the remaining EDG is inoperable due to common cause issues. With two EDGs inoperable, SCE must restore one EDG to operable status within two hours (TS 3.8.1, Action E).

Description of Event

On June 25, 2005, at about 1335 PDT, during a routine monthly surveillance start test of Unit 3 EDG 3G003, Emergency Supply Fan 3MA276 did not start and plant operators declared 3G003 inoperable. SCE's investigation traced the 3MA276 fan failure to a loose wire connection on the motor-starter [MSTR] thermal overload (TOL) auxiliary contact (the "49" contact) in cubicle 3BH1 1. The screw securing the two ring-tongue lugs at this contact terminal was found to be loose. SCE personnel checked the wiring and confirmed the neutral circuit path lost continuity, which prevented fan 3MA276 from starting.

SCE inspected the remaining seven (there are eight total) safety-related cubicles for Unit 3 EDG 3G003 that contain motor-starter TOL auxiliary contacts. The wires were gently "wiggled" or moved to determine connection tightness. All connections were acceptable with the exception of the TOL contact for Emergency Supply Fan 3MA277. Fan 3MA277 had started successfully during the surveillance test but its TOL auxiliary contact (in cubicle 3BH1 2) was found to be loose. After tightening the TOL contacts for fan 3MA276 and 3MA277, plant operators successfully start-tested 3G003 (both fans started) and declared 3G003 operable at 0406 PDT on June 26, 2005.

SCE also inspected the safety related cubicles for EDG 3G002 for loose connections as required by TS 3.8.1, Action B.3.1 (common cause investigation). On June 26, 2005 at 0459 PDT, SCE found two connections for EDG 3G002 that were not completely tight (i.e.,

loose) and declared 3G002 inoperable. Components affected were a Radiator Fan and an Emergency Supply Fan.U.S. NUCLEAR REGULATORY COMMISSION (7-2001)

LICENSEE EVENT REPORT (LER)

TEXT CONTINUATION I

6. LER NUMBER PAGE 3)

San N a r S oiSEQUENTLA 3

San Onofre Nuclear Generating Station (SONGS) Unit 3 05000-362 I 2005 NUMBER I

E O3 of 5 When the loose connections on 3G002 were found, SCE could not conclusively determine if the loose connections would have caused 3G002 inoperability and conservatively declared 3G002 inoperable. Because EDGs 3G002 and 3G003 could have been inoperable at the same time, SCE reported this occurrence to the NRC on June 26, 2005 (Event Log No.

41798) in accordance with 10CFR50.72(b)(3)(v)(D) as an event or condition that could have prevented fulfillment of a safety function. Offsite power sources remained available throughout this event.

As part of the root cause evaluation, SCE determined that the conditions found on EDG 3G002 did not prevent its operability. The wires terminating at those connections could be wiggled but the ring-tongue lugs remained electrically connected and the circuit complete.

Bench-testing of the motor-starter confirmed that 3G002's electrical contact was maintained and the EDG remained operable throughout this event (3G002 was declared operable at 1340 PDT on June 26, 2005). Because at least one EDG remained operable, there was not a loss of safety function and this event was determined to be not reportable. On August 23, 2005, SCE retracted the original phone report (Event Log No. 41798) and is providing this LER to document this event and inform the NRC of the corrective actions taken.

To address possible common cause issues on Unit 2, SCE successfully start-tested EDGs 2G002 and 2G003, inspected the wire connections, and confirmed the connections were acceptable.

Cause of the event

EDG fan 3MA276 did not start during the June monthly surveillance test because of a poor electrical connection at the TOL terminal screw. The screw was tightened and the fan started when tested.

SCE's preliminary findings indicate that the neutral connection on the U49" contact in cubicle 3BH1 1 for fan 3MA276 was loose and also noted a thin non-conductive oxide layer (tarnish) was on the terminal screw at the time of the occurrence. It is most likely that both conditions (loose screw and non-conductive oxide layer) contributed to the loss of circuit continuity. The root cause evaluation is ongoing and when complete, may determine additional factors which lead to the failure of the fan to start.

Corrective Actions

Immediate actions were to inspect the safety-related electrical cubicles for the Unit 2 and 3 EDGs for acceptable wiring connections. Afterward, inspections of other selected motor-starters with TOL contacts, outside of the EDG rooms, were conducted to determine extent of condition.U.S. NUCLEAR REGULATORY COMMISSION 7-2001)

LICENSEE EVENT REPORT (LER)

TEXT CONTINUATION I

S. LER NUMBER I PAGE 3)

San yO N

SESUENTIAL gt llo I

San Onofre Nuclear Generating Station (SONGS) Unit 3 05000-362 E

00

- 001-R 00 N

4 of5 Completed and planned corrective actions for Unit 2 and 3 EDGs:

1. SCE traced the 3MA276 fan failure to a loose wire connection on the motor-starter TOL contact in cubicle 3BH1 1. SCE personnel checked the wiring and confirmed the neutral circuit path lost continuity, which prevented fan 3MA276 from starting. After the screw was tightened, fan 3MA276 started when tested.
2. SCE inspected the electrical connections of all 32 safety-related Motor Control Center (MCC) cubicles with motor starters for the 4 EDGs. Except for the two loose connections in cubicles 3BH11 and 3BH12, the other inspected wiring connections were acceptable.
3. On July 8, 2005, motor-starters in cubicles 3BH1 1 and 3BH12 were removed and replaced with in-kind parts. On July 11, 2005, laboratory analysis on the motor-starters removed from 3BH11 and 3BH12 determined that there was no unusual degradation of the loose terminal connections on the "49" device.
4. On July 12, 2005, SCE bench-tested the motor starters removed from 3BH11 and 3BH12 to duplicate the as-found condition of the loose connection on fan 3MA276.

However, a thin non-conductive oxide layer (tarnish) on the screw that was present during the event had been removed as a consequence of tightening the screw on June 26, 2005. Therefore, the as-found condition (i.e., a motor-starter remaining de-energized) could not be duplicated. The testing showed that circuit continuity could be maintained even with the connection screw loose, as seen on fan 3MA277.

5. SCE also inspected an additional 12 EDG cubicles (with and without motor starters) in Unit 2 EDG 2G003. The wiring connections were acceptable.
6. SCE completed a work history review for the 3BH1 1 and 3BH12 cubicles. This review concluded that the TOL auxiliary contact in 3BH1 1 and 3BH12 had not been replaced or modified and did not have previous occurrences of unacceptable connections.
7. SCE plans to inspect additional MCC cubicles for EDGs 3G003, 3G002 and 2G002 for loose connections.

SCE has completed or will complete additional inspections beyond the EDG systems to determine the possible extent of this condition (loose terminal connections) as follows:

1. Nine cubicles containing safety-related motor-starters located in the Control Building were inspected. The wiring connections were acceptable.
2. SCE developed a ranking of risk significant components containing motor-starters with TOL auxiliary contacts. Based on this ranking, 18 components (nine on eachU.S. NUCLEAR REGULATORY COMMISSION LICENSEE EVENT REPORT (LER)

TEXT CONTINUATION B. LER NUMBER PAGE 3)

SEQUENrIAL REV NO I San Onofre Nuclear Generating Station (SONGS) Unit 3 050032NUMBER 5 of 5 I2005 I

- 001 -

00 Units 2 and 3) will be inspected to ensure wiring connections are acceptable. To date, one "49" contact on an Unit 3 auxiliary feedwater discharge flow control valve was found loose. The valve was stroked and determined operable prior to the wiring inspection.

After completion of the root cause evaluation, SCE will determine if additional corrective actions are required.

Safety Significance

Throughout this event, San Onofre remained connected to the offsite power grid and offsite power was operable. Additionally, 3G002 was determined to be operable and available to fulfill its design and safety function. The safety significance of the loose connection affecting EDG 3G003 is, therefore, minimal.

As noted in the Corrective Action section SCE to date has inspected more than 40 cubicles containing motor-starters with TOL contacts (approximately 2000 connections). Of the population inspected, three connections (the original two on EDG 3G003, and one connection on an auxiliary feedwater discharge flow control valve) were found loose and are "49" contacts. Of these three contacts, one resulted in equipment (fan 3MA276) not functioning. The safety significance of this issue is, therefore, minimal.

Additional Information

SCE also performed an engineering analysis to determine the affect on EDG 3G003 with fan 3MA276 not functioning. The analysis demonstrated that with an outside ambient air temperature of 80 degrees F or less (as was the condition during this event), fan 3MA277 is capable of providing enough cooling to the EDG room with 3G003 running. Consistent with the guidance provided by Generic Letter 91-18, Revision 1, therefore, 3G003 was operable and capable of fulfilling its safety function.

In the past three years, SCE has not reported any other instances of a loss of safety function as a result of a loose connection or reportable instances of EDG inoperability.