| | | Reporting criterion |
|---|
| 05000361/LER-1987-001-02, :on 870205,reactor Manually Tripped by Operations Personnel Observing Closure of Main Feedwater Block Valve 2HV-4051.Caused by Const Personnel Erroneously Performing Work in Valve Control Cabinet |
- on 870205,reactor Manually Tripped by Operations Personnel Observing Closure of Main Feedwater Block Valve 2HV-4051.Caused by Const Personnel Erroneously Performing Work in Valve Control Cabinet
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(viii)(B) |
| 05000206/LER-1987-001-01, :on 870117,ground Indication Received on Dc Bus 1 Required Entry Into Tech Spec 3.0.3.Caused by Terminal Box Conduit Locking Ring Vibrating Loose.Ground Eliminated |
- on 870117,ground Indication Received on Dc Bus 1 Required Entry Into Tech Spec 3.0.3.Caused by Terminal Box Conduit Locking Ring Vibrating Loose.Ground Eliminated
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.73(a)(2)(viii) 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(1) 10 CFR 50.73(a)(2)(6) |
| 05000362/LER-1987-001, :on 870109,discovered That 18-month Surveillance of Instrument Line Snubbers Not Performed. Caused by Clerical Error.Review of All Snubber Documents Included in Snubber Svc Life Program |
- on 870109,discovered That 18-month Surveillance of Instrument Line Snubbers Not Performed. Caused by Clerical Error.Review of All Snubber Documents Included in Snubber Svc Life Program
| 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(iii) 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(viii)(B) 10 CFR 50.73(a)(2)(1) |
| 05000206/LER-1987-002, :on 870228,turbine Bldg Yard Sump Effluent Monitor RIT-2101,found to Be Isolated & Compensatory 12 H Sample Had Not Been Obtained Since 870226.Caused by Control Room Operator Error.Operator Will Be Counseled |
- on 870228,turbine Bldg Yard Sump Effluent Monitor RIT-2101,found to Be Isolated & Compensatory 12 H Sample Had Not Been Obtained Since 870226.Caused by Control Room Operator Error.Operator Will Be Counseled
| 10 CFR 50.73(a)(2)(iii) 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(1) |
| 05000361/LER-1987-002-01, :on 870219,sump Effluent Monitor 2RE-7821 Found Partially Plugged W/Debris After Monitor Removed from Svc to Implement Sample Line Mods.On 870303,monitor 3RE-7821 Found Partially Plugged.Design Mods Implemented |
- on 870219,sump Effluent Monitor 2RE-7821 Found Partially Plugged W/Debris After Monitor Removed from Svc to Implement Sample Line Mods.On 870303,monitor 3RE-7821 Found Partially Plugged.Design Mods Implemented
| 10 CFR 50.73(a)(2)(1) |
| 05000206/LER-1987-003-02, :on 870310,reactor Trip Occurred Due to Loss of Generator Field.Caused by Electrical Short Due to Brush Dropped Into Main Exciter Commutator Assembly.Temporary Improvements to Available Lighting Made |
- on 870310,reactor Trip Occurred Due to Loss of Generator Field.Caused by Electrical Short Due to Brush Dropped Into Main Exciter Commutator Assembly.Temporary Improvements to Available Lighting Made
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) |
| 05000206/LER-1987-003-01, :on 870310,turbine & Reactor Trips Occurred as Result of Trip Signal in Response to Generator Field Loss. Caused by Electrical Short Resulting from Brush Being Dropped in Main Exciter Commutator Assembly |
- on 870310,turbine & Reactor Trips Occurred as Result of Trip Signal in Response to Generator Field Loss. Caused by Electrical Short Resulting from Brush Being Dropped in Main Exciter Commutator Assembly
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) |
| 05000206/LER-1987-004, :on 870313,east Main Feedwater Pump Removed from Svc While Loose Deflector Ring Repositioned & Set Screw Tightened,Constituting Entry Into Tech Spec 3.0.3.Request to Operate One Train for 72 H Submitted |
- on 870313,east Main Feedwater Pump Removed from Svc While Loose Deflector Ring Repositioned & Set Screw Tightened,Constituting Entry Into Tech Spec 3.0.3.Request to Operate One Train for 72 H Submitted
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(viii)(A) |
| 05000206/LER-1987-005-02, On 870324,Nuclear Instrumentation Sys Power Channel 1207 Declared Inoperable Due to Low Output Resulting in Entry Into Limiting Condition for Operation 3.0.3.Caused by Inadequate Procedure.Procedure Revised | On 870324,Nuclear Instrumentation Sys Power Channel 1207 Declared Inoperable Due to Low Output Resulting in Entry Into Limiting Condition for Operation 3.0.3.Caused by Inadequate Procedure.Procedure Revised | 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) |
| 05000206/LER-1987-005, :on 870324,nuclear Instrumentation Sys Power Range Channel 1207 Declared Inoperable.Channel Placed in Trip Condition.On 870428 & 29,Channel 1207 Automatically Reset from Trip to Inoperable Condition |
- on 870324,nuclear Instrumentation Sys Power Range Channel 1207 Declared Inoperable.Channel Placed in Trip Condition.On 870428 & 29,Channel 1207 Automatically Reset from Trip to Inoperable Condition
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) |
| 05000206/LER-1987-006-01, :on 870513,during Insp of Environ Qualified Butt Spliced Connections Per IE Info Notice 86-104,one Level Switch Found Missing Raychem Heat Shrink Sleeving.Caused by Requirement Being Deleted During Drawing Rev |
- on 870513,during Insp of Environ Qualified Butt Spliced Connections Per IE Info Notice 86-104,one Level Switch Found Missing Raychem Heat Shrink Sleeving.Caused by Requirement Being Deleted During Drawing Rev
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) |
| 05000206/LER-1987-006, :on 870513,insp Per IE Info Notice 86-104 Found wide-range Containment Water Level Instrumentation in non-environ Qualification Configuration.Caused by Personnel Error.Training Program Initiated |
- on 870513,insp Per IE Info Notice 86-104 Found wide-range Containment Water Level Instrumentation in non-environ Qualification Configuration.Caused by Personnel Error.Training Program Initiated
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) |
| 05000206/LER-1987-007-02, :on 870713,discovered Boric Acid Storage Tank Level Instrumentation Monthly Functional Test Performed Delinquently.Caused by Failure of Planner to Include Test in Tracking Sys.Planner Counseled |
- on 870713,discovered Boric Acid Storage Tank Level Instrumentation Monthly Functional Test Performed Delinquently.Caused by Failure of Planner to Include Test in Tracking Sys.Planner Counseled
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) |
| 05000361/LER-1987-008, :on 870219,operating Records Identified Several ESF Actuations.Operating Instructions for Performing Power Transfer Evolutions Will Be Modified to Note That Such Actuations Will Occur & Considered Part of Preplanned Plan |
- on 870219,operating Records Identified Several ESF Actuations.Operating Instructions for Performing Power Transfer Evolutions Will Be Modified to Note That Such Actuations Will Occur & Considered Part of Preplanned Plan
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) |
| 05000206/LER-1987-008-01, :on 870602,while in Mode 5,meggering of CRD Mechanism Coil Circuits Revealed Low Insulation Resistance in 22 Circuits.Cause of Damage Occurred During Penetration Installations.Cable Tray Covers to Be Provided |
- on 870602,while in Mode 5,meggering of CRD Mechanism Coil Circuits Revealed Low Insulation Resistance in 22 Circuits.Cause of Damage Occurred During Penetration Installations.Cable Tray Covers to Be Provided
| 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) |
| 05000206/LER-1987-009-01, :on 870610,during Performance of Procedural Steps in Preparation of Engine Air Roll,Diesel Generator 1 Inadvertently Started.Caused by Operator Failure to Identify Control push-button.Operator Counseled |
- on 870610,during Performance of Procedural Steps in Preparation of Engine Air Roll,Diesel Generator 1 Inadvertently Started.Caused by Operator Failure to Identify Control push-button.Operator Counseled
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) |
| 05000361/LER-1987-009, :on 870104,Train B of Containment Purge Isolation Sys Spuriously Actuated by Containment Area Radiation Monitor 3RT-7856.Caused by Movement of Connecting Cable on Panel Door.Personnel Cautioned on Door Usage |
- on 870104,Train B of Containment Purge Isolation Sys Spuriously Actuated by Containment Area Radiation Monitor 3RT-7856.Caused by Movement of Connecting Cable on Panel Door.Personnel Cautioned on Door Usage
| 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) |
| 05000206/LER-1987-010-01, :on 870620,containment Isolation Sys Actuated Due to Momentary Loss of Power to Three Train 4 Detector Channels.Caused by Loose Connection at Common Power Supply to Transmitters.Nest Receptacle Repaired |
- on 870620,containment Isolation Sys Actuated Due to Momentary Loss of Power to Three Train 4 Detector Channels.Caused by Loose Connection at Common Power Supply to Transmitters.Nest Receptacle Repaired
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) |
| 05000206/LER-1987-011-01, :on 880728,spurious Actuation of Containment Isolation Train a Occurred W/Isolation Valves Verified Properly Closed.Caused by Broken Instrument Electrical Solder Connection.Procedures Modified |
- on 880728,spurious Actuation of Containment Isolation Train a Occurred W/Isolation Valves Verified Properly Closed.Caused by Broken Instrument Electrical Solder Connection.Procedures Modified
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) |
| 05000206/LER-1987-012-02, :on 870825,containment Air Luck Hatch Did Not Fully Close Due to Hatch Drive Failure,Resulting in Brief Breach of Containment Integrity.Caused by Broken Master Link.Broken Master Link Replaced |
- on 870825,containment Air Luck Hatch Did Not Fully Close Due to Hatch Drive Failure,Resulting in Brief Breach of Containment Integrity.Caused by Broken Master Link.Broken Master Link Replaced
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) |
| 05000206/LER-1987-013-01, :on 870902,redundant Pump G-002B Not Tested Prior to Disabling of auto-start Capability of Pump G-002A During Calibr of Hydrazine Storage Tank Level Transmitter. Caused by Personnel Error.Personnel Counseled |
- on 870902,redundant Pump G-002B Not Tested Prior to Disabling of auto-start Capability of Pump G-002A During Calibr of Hydrazine Storage Tank Level Transmitter. Caused by Personnel Error.Personnel Counseled
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) |
| 05000362/LER-1987-013, :on 870624,HPSI Pump Bypass Valve Found Not Fully Closed.Caused by Lack of Limit Switch Actuating Assembly Collar Retaining Device.Limit Switch Returned to Original Configuration W/Locking Mechanism |
- on 870624,HPSI Pump Bypass Valve Found Not Fully Closed.Caused by Lack of Limit Switch Actuating Assembly Collar Retaining Device.Limit Switch Returned to Original Configuration W/Locking Mechanism
| 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(1) |
| 05000206/LER-1987-014-02, :on 870626,determined That Battery Weekly Surveillance Not Performed Prior to Mode Change,Contrary to Tech Spec 4.0.4.Caused by Personnel Error.Individual Involved Reinstructed |
- on 870626,determined That Battery Weekly Surveillance Not Performed Prior to Mode Change,Contrary to Tech Spec 4.0.4.Caused by Personnel Error.Individual Involved Reinstructed
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) |
| 05000206/LER-1987-015, :on 871007,determined That ESF Designs Failed to Meet Single Failure Criteria.Cause Re motor-operated Valve MOV-883 Due to Failure to Review Affect of Revised Single Failure Regulatory Guidance |
- on 871007,determined That ESF Designs Failed to Meet Single Failure Criteria.Cause Re motor-operated Valve MOV-883 Due to Failure to Review Affect of Revised Single Failure Regulatory Guidance
| 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(B) |
| 05000206/LER-1987-015-02, :on 871007,determined That Engineered Safety Sys Design Failed to Meet Single Criteria.Caused by Newly Identified time-dependent Single Failure Susceptibilty. Special Operator Training Provided |
- on 871007,determined That Engineered Safety Sys Design Failed to Meet Single Criteria.Caused by Newly Identified time-dependent Single Failure Susceptibilty. Special Operator Training Provided
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) |
| 05000206/LER-1987-016-02, :on 871110,Automatic Switch Co Solenoid Valve Failures Occurred.Caused by Thin Hard Film Between Top of Slug & Housing.Root Cause Evaluation Continuing.Further Testing Performed |
- on 871110,Automatic Switch Co Solenoid Valve Failures Occurred.Caused by Thin Hard Film Between Top of Slug & Housing.Root Cause Evaluation Continuing.Further Testing Performed
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) |
| 05000206/LER-1987-016, :on 871110,engineering Evaluation Concluded That Presence of Film Was Cause for Solenoid Valve Failures Which Rendered Independent Trains in Multiple Sys Inoperable.Lubricant Removed from Valves |
- on 871110,engineering Evaluation Concluded That Presence of Film Was Cause for Solenoid Valve Failures Which Rendered Independent Trains in Multiple Sys Inoperable.Lubricant Removed from Valves
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) |
| 05000206/LER-1987-017, :on 871201,remotely Operated,Normally Closed, Containment Isolation Valves in Vent Line Did Not Close Upon Demand Upon Completion of Venting of Loop B Header.Seats of Valves Found Worn & Warped.Valves Replaced |
- on 871201,remotely Operated,Normally Closed, Containment Isolation Valves in Vent Line Did Not Close Upon Demand Upon Completion of Venting of Loop B Header.Seats of Valves Found Worn & Warped.Valves Replaced
| 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) |
| 05000206/LER-1987-017-02, :on 870910 & 1201,containment Isolation Valves Loop B Header Would Not Fully Close Upon Demand.Cause Undetermined.Administrative Controls Implemented to Prevent Inadvertent Opening of Valves |
- on 870910 & 1201,containment Isolation Valves Loop B Header Would Not Fully Close Upon Demand.Cause Undetermined.Administrative Controls Implemented to Prevent Inadvertent Opening of Valves
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)() 10 CFR 50.73(a)(2) 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) |
| 05000206/LER-1987-018-01, :on 871216,Tech Spec 3.0.3 Voluntarily Entered During Dc Ground Troubleshooting.Caused by Presence of Water Inside Housing of Solenoid.Ground Eliminated by Drying Electrical Connections |
- on 871216,Tech Spec 3.0.3 Voluntarily Entered During Dc Ground Troubleshooting.Caused by Presence of Water Inside Housing of Solenoid.Ground Eliminated by Drying Electrical Connections
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(iv), System Actuation 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) |