05000354/FIN-2016001-01
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Untimely correction of a Condition Adverse to Quality Associated with High Vibrations on the C Emergency Diesel Generator |
| Description | A self-revealing finding of very low safety significance (Green) and associated NCV of Title 10 of the Code of Federal Regulations (10 CFR) Part 50, Appendix B, Criterion XVI, Corrective Action, were identified when PSEG did not correct a condition adverse to quality (CAQ). Specifically, despite identifying a potential CAQ on November 3, 2014, associated with high vibrations on the C emergency diesel generator (EDG) jacket water (JW) braided flexible hose during a system walkdown, no notification (NOTF) was generated, no evaluation of the high vibration condition was conducted, and the CAQ was not promptly corrected as required by the corrective action program (CAP). Subsequently, during a monthly surveillance run conducted on January 4, 2016, the C EDG was declared inoperable when a large JW leak developed in the aforementioned braided flexible hose. PSEGs corrective actions included replacing the failed flexible hose and performing extent of condition walkdowns on the other EDGs JW piping structural supports. PSEG also conducted simple troubleshooting on the piping and support structures of all the EDGs, and plans to initiate a vibration monitoring program of the EDGs and EDG support systems. The inspectors determined that the finding was more than minor because it was associated with the Equipment Performance attribute of the Mitigating Systems cornerstone and adversely affected the cornerstone objective of ensuring the reliability of systems that respond to initiating events to prevent undesirable consequences. Specifically, not correcting the high vibrations on the JW piping resulted in an unplanned shutdown of the diesel, inoperability and unavailability when the leak worsened to a point where PSEG determined that the EDG could not meet its 24-hour mission time. In accordance with IMC 0609.04, Initial Characterization of Findings, dated June 19, 2012, and Exhibit 2 of IMC 0609, Appendix A, The SDP for Findings At-Power, dated June 19, 2012, the inspectors determined that this finding is of very low safety significance (Green) because the performance deficiency was not a design or qualification deficiency, did not involve an actual loss of safety function, did not represent the actual loss of a safety function of a single train for greater than its technical specification (TS) allowed outage time, and did not represent an actual loss of function of one or more non-TS trains of equipment designated as high safety-significant in PSEGs maintenance rule program for greater than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. This finding had a cross-cutting aspect in the area of Problem Identification and Resolution, Identification, because PSEG did not implement the CAP with a low threshold for identifying issues and did not identify issues completely, accurately and in a timely manner in accordance with the CAP. Specifically, the issue of high vibrations on the C EDG JW braided flexible hose was identified by PSEG, but was not placed into CAP, leading to the issue not being properly documented or evaluated to ensure the cause of the high vibrations was addressed in a timely manner. |
| Site: | Hope Creek |
|---|---|
| Report | IR 05000354/2016001 Section 4OA2 |
| Date counted | Mar 31, 2016 (2016Q1) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | Self-revealing |
| Inspection Procedure: | IP 71152 |
| Inspectors (proximate) | F Bower J Hawkins J Schoppy S Haney G Dipaolo |
| Violation of: | 10 CFR 50 Appendix B Criterion XVI Technical Specification |
| CCA | P.1, Identification |
| INPO aspect | PI.1 |
| ' | |