05000346/FIN-2015008-01
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Vulnerability of EDG Crosstie to a Non-Essential Bus |
Description | The inspectors identified a finding of very-low safety significance (Green), and an associated NCV of Title 10, Code of Federal Regulations (CFR) Part 50, Appendix B, Criterion III, Design Control, for the failure to assure that applicable regulatory requirements, and the design basis were correctly translated into specifications, drawings, procedures, and instructions, and verifying the adequacy of design. Specifically, the licensee failed to verify the adequacy of procedures controlling alignment of non-essential busses to the emergency diesel generators during a design basis event. The procedures guidance could put the plant in an unanalyzed alignment with the potential to result in the failure of safety-related equipment. The licensee entered this finding into their Corrective Action Program (CAP), and initiated a Standing Order to preclude the unanalyzed alignment. The finding was determined to be more than minor because the finding was associated with the Mitigating Systems cornerstone attribute of Procedure Quality, and affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The finding screened as very low-safety significance (Green) because the inspectors were able t
answer Yes to screening question A1 because the finding represents a design deficiency confirmed not to result in loss of operability. The inspectors did not identify a cross-cutting aspect associated with this finding as it did not reflect current performance. |
Site: | Davis Besse |
---|---|
Report | IR 05000346/2015008 Section 1R21 |
Date counted | Mar 31, 2015 (2015Q1) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.21 |
Inspectors (proximate) | A Dunlop C Baron C Lipa G O'Dwyer N Valos S Kobylarz S Sheldon |
Violation of: | 10 CFR 50 Appendix B Criterion III, Design Control |
INPO aspect | |
' | |
Finding - Davis Besse - IR 05000346/2015008 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Davis Besse) @ 2015Q1
Self-Identified List (Davis Besse)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||