05000346/FIN-2009004-04
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Licensee-Identified Violation |
| Description | A Severity Level IV violation of 10 CFR 50.9, Completeness and Accuracy of Information, was identified for providing inaccurate information to the NRC. Specifically the licensee provided inaccurate information and non-conservative TS values for minimum emergency diesel generator (EDG) steady state voltages in TS SR 3.8.1.2 and SR 3.8.1.8. The licensee entered this condition into their corrective action program (CR 09-63730). The finding was assessed using the traditional enforcement process because the issue potentially affected the NRCs ability to perform its regulatory function. The finding is of very low safety 27 Enclosure significance, because the submittal of inaccurate information was not identified as willful and licensees procedures required leaving the EDG voltage regulators set at a voltage sufficiently high to meet license requirements under analyzed accident transient loading conditions |
| Site: | Davis Besse |
|---|---|
| Report | IR 05000346/2009004 Section 4OA7 |
| Date counted | Sep 30, 2009 (2009Q3) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | Licensee-identified |
| Inspection Procedure: | |
| Inspectors (proximate) | J Rutkowski T Go A Wilson J Bozga J Cameron |
| INPO aspect | |
| ' | |