Finding | |
|---|---|
| Title | Inadequate Control Air Compressor Capacity Test Program |
| Description | A finding of very low safety significance and an associated NCV of 10 CFR Part 50, Appendix B, Criterion XI, Test Control, was identified by the inspectors for the failure to perform adequate testing for both the Division 1 and 2 CACs. Specifically, the licensee failed to incorporate appropriate acceptance criteria and failed to include appropriate test methodology in the test procedures for the safety-related CACs. Corrective actions planned included revising and/or re-performing the test procedures as necessary. The finding was more than minor because the finding was associated with the Mitigating Systems Cornerstone attribute of Procedure Quality and affected the cornerstone objective of ensuring the reliability and capability of systems that respond to initiating events to prevent undesirable consequences. The finding was of very low safety significance because the finding was confirmed not to result in a loss of operability or functionality. No cross-cutting aspect was assigned because this issue is not indicative of current plant performance. (Section 1R22.1(1) |
| Site: | Fermi |
|---|---|
| Report | IR 05000341/2008005 Section 1R22 |
| Date counted | Dec 31, 2008 (2008Q4) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.22 |
| Inspectors (proximate) | R Jickling R Winter T Steadham J Rutkowski M Bielby R Morris A Wilson M Jones |
| INPO aspect | |
| ' | |
Finding - Fermi - IR 05000341/2008005 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Fermi) @ 2008Q4
Self-Identified List (Fermi)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||