05000336/FIN-2013007-01
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Verify 480VAC MCC Starters Had Adequate Control Voltage to Operate Under All Design Conditions |
Description | The team identified a finding of very low safety significance involving a non-cited violation (NCV) of Title 10 of the Code of Federal Regulations (10 CFR) Part 50, Appendix B, Criterion III, Design Control, in that Dominion did not verify that Unit 3 safety-related motor control center (MCC) starters had adequate control voltage to operate under all design conditions. Specifically, Dominion did not use the minimum voltage that would be available at Unit 3 MCCs during the most limiting block starting of large electrical loads during a Unit 3 loss of coolant accident (LOCA) as the design input for the minimum voltage under which an MCC starter was required to operate, to ensure that the starter\'s contactor would close when Unit 2 off-site power is cross-tied to Unit 3. In response, Dominion entered the issue into their corrective action program and issued an Operations Standing Order to ensure that the off-site electrical distribution system would not be placed in a configuration that would allow a lower minimum voltage than what was previously analyzed for the MCC starters until the issue was resolved. The finding was more than minor because it was similar to Example 3.j of NRC Inspection Manual Chapter (IMC) 0612, Appendix E, Examples of Minor Issues, because without verification that the components would operate at the lowest potential voltage possible, the team had reasonable doubt with the operability of the associated components. In addition, the finding was associated with the Design Control attribute of the Mitigating Systems cornerstone and affected the objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences (i.e., core damage). Using IMC 0609, Appendix A, The Significance Determination Process for Findings At-Power, Exhibit 2, Mitigating Systems Screening Questions, a Region I Senior Reactor Analyst (SRA) conducted a detailed risk evaluation. Since the ability of the MCC starters to function under the worst case conditions could not be verified during the inspection period, a detailed risk evaluation was determined to be appropriate. Results of the evaluation demonstrated that the initiating event frequency was substantially below 1E-6, and therefore, the SRA concluded the finding to be of very low safety significance (Green). This finding had a cross-cutting aspect in the area of Human Performance, Decision Making, because, in the design of a Unit 3 480 volts alternating current (VAC) MCC starter modification, Dominion did not use a conservative or bounding value as a design input for the minimum voltage under which a component might be required to operate. [IMC 0310, Aspect H.1(b) |
Site: | Millstone ![]() |
---|---|
Report | IR 05000336/2013007 Section 1R17 |
Date counted | Mar 31, 2013 (2013Q1) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.17 |
Inspectors (proximate) | A Bolger J Richmond S Pindale F Arner P Krohn M Orr |
Violation of: | 10 CFR 50 Appendix B Criterion III, Design Control |
CCA | H.14, Conservative Bias |
INPO aspect | DM.2 |
' | |
Finding - Millstone - IR 05000336/2013007 | |||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Millstone) @ 2013Q1
| |||||||||||||||||||||||||||||||||||||||||||||||||||||