Finding | |
|---|---|
| Title | Sprinklers too far below Ceiling in Cable Spreading Room |
| Description | A green NCV of Unit 1 License Condition 16 and Unit 2 License Condition 13, Fire Protection, was identified for failure to install the automatic suppression system (sprinkler system) in the cable spreading room according to the applicable National Fire Protection Association standard with regard to the ceiling to sprinkler head dimension. As a result, the fusible link type sprinkler heads may be significantly slower than originally intended after fire ignition. The licensee entered this problem into their corrective action program. This finding is a performance deficiency because the licensee did not locate the sprinkler heads according to the applicable industry code of record for the facility. The finding is more than minor because it is associated with the reactor safety, mitigating systems, cornerstone attribute of protection against external factors, i.e. fire, and it substantially affects the objective of ensuring reliability and capability of systems that respond to initiating events. The finding was determined to be of very low safety significance when the likelihood of fires, the transients that could be initiated by fires and the probability of failure of mitigating systems for those transients were evaluated |
| Site: | Sequoyah |
|---|---|
| Report | IR 05000327/2008006 Section 4OA5 |
| Date counted | Jun 30, 2008 (2008Q2) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | |
| Inspectors (proximate) | F Mccreesh J Montgomery N Staples P Fillion R Nease R Rodriguez |
| INPO aspect | |
| ' | |
Finding - Sequoyah - IR 05000327/2008006 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Sequoyah) @ 2008Q2
Self-Identified List (Sequoyah)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||