Finding | |
|---|---|
| Title | Sprinkler System in Room 690.0-A1 of the Auxiliary Building has NFPA Code Deviation |
| Description | The team observed a number of water suppression sprinkler heads in the eastern portion of the Auxiliary Building Elev. 690 (Room 690.0-A1, Fire Area FAA-029) that were located approximately six feet below the ceiling. These sprinkler heads are part of an NFPA 13 preaction sprinkler system which requires that the sprinkler heads in this area be no more than 12 inches below the ceiling. The sprinkler system in this area would not be effective in a response to a fire since the time delay to fuse any particular sprinkler head could be significant due to the location of the sprinkler heads. This portion of the sprinkler system does not meet the requirements of NFPA 13 and the licensee could not produce an evaluation or analysis that demonstrated the capability of this system to adequately control a potential fire in this area. However, the licensee claimed that the installation had been previously approved by the NRC; therefore, considered the system non-degraded. They did, however, initiate a Problem Evaluation Report (PER) to evaluate the condition. In order to determine all the facts concerning the licensing basis of the system and to review the potential acceptability of the as-built system with its code deviation an URI was established: URI 05000327, 328/2008006-02, Sprinkler System in Room 690.0-A1 of the Auxiliary Building has NFPA Code Deviation |
| Site: | Sequoyah |
|---|---|
| Report | IR 05000327/2008006 Section 4OA5 |
| Date counted | Jun 30, 2008 (2008Q2) |
| Type: | URI: Green |
| cornerstone | Other |
| Identified by: | NRC identified |
| Inspection Procedure: | |
| Inspectors (proximate) | N Merriweather M Thomas R Fanner R Nease L Suggs J Dymekf Mccreeshj Montgomery N Staples P Fillion R Nease R Rodriguez |
| INPO aspect | |
| ' | |
Finding - Sequoyah - IR 05000327/2008006 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Sequoyah) @ 2008Q2
Self-Identified List (Sequoyah)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||