Finding | |
|---|---|
| Title | Untimely Corrective Actions for Installing Appendix R Emergency Lights |
| Description | The team identified a non-cited violation of Hatch Unit 1 License Condition 2.C.3 and Unit 2 License Condition 2.C.3 (a) for the failure to take timely corrective actions to restore emergency lighting to be in compliance with 10 CFR Part 50, Appendix R,Section III.J. Specifically, during a 2006 triennial fire protection inspection, a total of ten Unit 1 and Unit 2 indicating instruments, credited for alternative post-fire safe shutdown, were identified in condition reports written in 2006, as not having dedicated emergency lighting units installed to illuminate the instruments. The licensee subsequently closed the 2006 condition reports to design change packages and, at the time of this inspection, had not implemented the modifications to restore compliance. The licensee entered the current non-compliance into their corrective action program as condition report CR 2010115127. The licensees failure to take timely corrective actions to address non-compliances with 10 CFR Part 50, Appendix R,Section III.J, as required by the licensees fire protection program, is a performance deficiency. The finding is more than minor because it affects the human performance attribute of the Mitigating Systems cornerstone and the objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences (i.e. core damage). Specifically, the finding affected the ability of operators to shutdown the reactor from outside the control room in the event of a fire. The team evaluated this finding using Inspection Manual Chapter 0609, Appendix F, Fire Protection Significance Determination Process, Phase 1 Qualitative Screening Approach. The finding affects post-fire safe shutdown and was assigned a low degradation rating because operators had a high likelihood of completing tasks requiring use of the affected indicators using hand-held portable lights. The finding is characterized as Green, a finding of very low safety significance. The finding has a cross-cutting aspect in the Human Performance Area, Resources component, because the licensee failed to ensure that equipment was available and adequate to assure nuclear safety. Specifically, the licensee did not ensure that emergency lighting units were adequate to support post-fire safe shutdown actions. |
| Site: | Hatch |
|---|---|
| Report | IR 05000321/2010009 Section 1R05 |
| Date counted | Dec 31, 2010 (2010Q4) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.05 |
| Inspectors (proximate) | F Ehrhardt M Thomas P Fillion G Wiseman R Nease P Braxton J Dymek |
| CCA | H.1, Resources |
| INPO aspect | LA.1 |
| ' | |
Finding - Hatch - IR 05000321/2010009 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Hatch) @ 2010Q4
Self-Identified List (Hatch)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||