05000318/LER-2025-001-01, Loss of Site Transformer U-4000-12

From kanterella
Jump to navigation Jump to search
Loss of Site Transformer U-4000-12
ML25303A285
Person / Time
Site: Calvert Cliffs 
Issue date: 10/30/2025
From:
Constellation Energy Generation
To:
Office of Nuclear Reactor Regulation
Shared Package
ML25303A283 List:
References
LER 2025-001-01
Download: ML25303A285 (1)


LER-2025-001, Loss of Site Transformer U-4000-12
Event date:
Report date:
3182025001R01 - NRC Website

text

Abstract

At 0842 7/2/25 with Unit 2 in Mode 1 at 100% power, an actuation of the Engineered Safety Feature Actuation System (ESFAS) Undervoltage (UV) occurred on Safety Related 4 kV Bus #21 during steady state conditions. The cause of the UV actuation was the loss of 13/4 kV transformer U-4000-12 due to its feeder breaker 252-1103 tripping open. The 2A Emergency Diesel Generator (EDG) automatically started as designed when the UV signal was received and re-powered 4 kV Bus #21. Non-Safety Related 4 kV Bus #22 automatically fast transferred to its alternate power supply. The cause of 1BKR252-1103 (U-4000-12 Feeder Breaker) tripping open due to the actuation of Differential Protection Relay 1RY287/T-12 was determined to be water intrusion into the switch enclosure 1H1103XSW.

(See Page 2 for required number of digits/characters for each block)

(See NUREG-1022, R.3 for instruction and guidance for completing this form http://www.nrc.gov/reading-rm/doc-collections/nuregs/staff/sr1022/r3/)

30Page 4 of 4 Water intrusion was also identified during an inspection of the U-25000-11 isophase on 02/18/2024 (04751071)

H. COMPONENT FAILURE DATA

Component IEEE 803 IEEE805 FUNCTION ID SYSTEM ID Breaker RG EB