05000282/LER-2014-001, Cancellation of Licensee Event Report (LER) 50-282/2014-001-00 Associated with D1/D2 Emergency Diesel Generators (Edgs) Inoperable Due to Outside Air Temperature Greater than 97 Degrees Fahrenheit

From kanterella
(Redirected from 05000282/LER-2014-001)
Jump to navigation Jump to search
Cancellation of Licensee Event Report (LER) 50-282/2014-001-00 Associated with D1/D2 Emergency Diesel Generators (Edgs) Inoperable Due to Outside Air Temperature Greater than 97 Degrees Fahrenheit
ML14302A451
Person / Time
Site: Prairie Island 
Issue date: 10/27/2014
From: Davison K
Northern States Power Co, Xcel Energy
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
L-PI-14-109 LER 14-001-00
Download: ML14302A451 (2)


LER-2014-001, Cancellation of Licensee Event Report (LER) 50-282/2014-001-00 Associated with D1/D2 Emergency Diesel Generators (Edgs) Inoperable Due to Outside Air Temperature Greater than 97 Degrees Fahrenheit
Event date:
Report date:
2822014001R00 - NRC Website

text

(l Xcel Energy OCT 2 7 2014 U S Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Prairie Island Nuclear Generating Plant Unit 1 Docket 50-282 Renewed License No. DPR-42 L-PI-14-109 10 CFR 50.73 Cancellation of Licensee Event Report (LER) 50-282/2014-001-00 Associated with D1/D2 Emergency Diesel Generators (EDG's) Inoperable Due to Outside Air Temperature Greater Than 97 Degrees Fahrenheit Reference: 1. Northern States Power Company, a Minnesota corporation, doing business as Xcel Energy (hereafter "NSPM") letter to NRC, "LER 50-282/2014-001-00, D1/D2 Emergency Diesel Generators (EDG's)

Inoperable Due to Outside Air Temperature Greater Than 97 Degrees Fahrenheit." June 27, 2014. (ADAMS Accession ML14178B278)

This letter constitutes notification to the NRC of the cancellation of Prairie Island Nuclear Generating Plant (PINGP) LER 50-282/2014-001-00 (Reference 1). The cancellation is consistent with the guidance in NUREG-1022, Rev 3, "Event Reporting Guidelines 10 CFR 50.72 and 50.73."

Based on further analysis of the D1/D2 EDG's inoperability due to the outside air temperature greater than 97 degrees Fahrenheit, thorough engineering evaluation of the test report and the test results of the affected components, it was concluded that the test report is acceptable for NSPM use which ensures that the installed Foxboro Electronic Control Temperature Indicating Transmitter, Model 632-2AS and Foxboro Temperature Controller, Model 62HB-4E-OH, would perform their intended safety functions as expected if exposed to an abnormal temperature environment of 130 degrees Fahrenheit in the diesel generator rooms.

Components required for D1 and D2 to be operable will function as expected at an increased room temperature of 125 degrees Fahrenheit or an outside air temperature of 103 degrees Fahrenheit. In the past three (3) years, the outside air temperature did not exceed 103 degrees Fahrenheit. Therefore, there was no reportable condition.

Based on this determination, no safety system functional failure or common cause inoperability of independent trains or channels existed and NSPM is cancelling LER 50-282/2014-001-00.

1717 Wakonade Drive East

  • Welch, Minnesota 55089-9642 Telephone: 651.388.1121

Document Control Desk Page 2 Summary of Commitments This letter contains no new commitments and no changes to existing commitments.

P~y~

~;,~.,.,

Kevin Davison Site Vice President, Prairie Island Nuclear Generating Plant Northern States Power Company - Minnesota Enclosure cc:

Administrator, Region Ill, USNRC Project Manager, PINGP, USNRC Resident Inspector, PINGP, USNRC Department of Commerce, State of Minnesota