05000282/FIN-2013002-01
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Failure to Properly Secure Materials Near Critical Drainage Path |
| Description | The inspectors identified a finding of very low safety significance and an non-cited violation of 10 CFR Part 50, Appendix B, Criterion V, Instructions, Procedures, and Drawings, on February 4, 2013, due to the licensees failure to follow procedures for material storage near a Unit 2 Turbine Building critical drainage path. Specifically, ten drums were not secured in accordance with Section 6.2.11 of Procedure 5AWI 8.9.0, Internal Flooding Drainage Control. Corrective actions for this issue included removing the material and providing training to personnel on internal flooding drainage control requirements. The inspectors determined that this finding was more than minor because if left uncorrected the unsecured material could become buoyant, impede water drainage, and impact the function of safety-related equipment following an internal flood. This finding was of very low safety significance because each question listed in IMC 0609, Appendix A, Exhibit 2, Mitigating Systems Screening Questions, was answered no. This finding was cross-cutting in the Human Performance, Work Control area because the licensee failed to keep personnel appraised of the operational impact of work activities and plant conditions that may affect work activities |
| Site: | Prairie Island |
|---|---|
| Report | IR 05000282/2013002 Section 1R06 |
| Date counted | Mar 31, 2013 (2013Q1) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.06 |
| Inspectors (proximate) | A Dunlop C Moore D Passehl J Bozga K Riemer K Stoedter M Holmberg M Learn M Phalen P Zurawski T Bilik |
| Violation of: | 10 CFR 50 Appendix B Criterion V |
| CCA | H.5, Work Management |
| INPO aspect | WP.1 |
| ' | |
Finding - Prairie Island - IR 05000282/2013002 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Prairie Island) @ 2013Q1