05000254/FIN-2010003-02
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | PCIS Relay Common Neutral Broken |
| Description | A self-revealed finding of very low safety significance and a NCV of Technical Specification (TS) 5.4.1 was identified on April 8, 2010, when a Unit 2 Group III containment isolation signal was received during replacement of a primary containment isolation system (PCIS) relay as a result of a disconnected common neutral wire. Immediate corrective actions for this event included restoration of the reactor water cleanup system and rewiring for the PCIS relay to the proper configuration. The inspectors determined that the licensees failure to identify and provide instructions to mitigate the common neutral during the work planning process was a performance deficiency. The inspectors determined that this finding was cross-cutting in the area of Human Performance, Work Control, because the licensee failed to assess the impact of changes to the work scope during the maintenance activity when plant operating conditions had changed (H.3(b))
The inspectors determined the finding was more than minor because the performance deficiency impacted the Mitigating Systems Cornerstone attribute of Configuration Control for Operating Equipment Lineup to ensure the availability, reliability and capability of safety systems to respond to initiating events to prevent undesirable consequences. The inspectors performed a Phase 1 SDP evaluation. Using IMC 0609, Attachment 4, Table 4a, Mitigating Systems Cornerstone, all questions were answered No, and this finding screened as Green, or having a very low safety significance. |
| Site: | Quad Cities |
|---|---|
| Report | IR 05000254/2010003 Section 4OA2 |
| Date counted | Jun 30, 2010 (2010Q2) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | Self-revealing |
| Inspection Procedure: | IP 71152 |
| Inspectors (proximate) | W Slawinski M Ring J Mcghee E Coffman B Cushman D Sand C Mathews |
| CCA | H.5, Work Management |
| INPO aspect | WP.1 |
| ' | |
Finding - Quad Cities - IR 05000254/2010003 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Quad Cities) @ 2010Q2
Self-Identified List (Quad Cities)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||