ENS 46936
ENS Event | |
---|---|
15:26 Jun 8, 2011 | |
Title | Notification Of Unusual Event Due To Flooding That Potentially Affected Safety Related Equipment |
Event Description | Flushing activities were in progress on the 2A Auxiliary Feedwater (AF) Pump suction line from the Essential Service Water System (SX). At 1011 [CDT], during this flushing activity, the flushing hose ruptured and caused flooding in the Auxiliary Building that had the potential to affect safety related equipment needed for the current operating mode. This was due to the flood waters contacting the motors of the 1A and 2A AF Pumps.
At 1026, an Unusual Event was declared by the Shift Emergency Director because the conditions for EAL entry were met for EAL HU5. Specifically the EAL conditions were 'Flooding in the Auxiliary Building that has the potential to affect safety related equipment needed for the current operating mode.' Auxiliary Feedwater is required to be operable in Mode 1 for each unit. The leak was immediately isolated (within 45 seconds of hose rupture) and remains isolated. Maintenance personnel are in the process of testing the 1A and 2A AF Pump motor to determine operability. The appropriate Tech Spec Action Statements have been entered on each Unit for the AF Pumps. The leak also caused the wetting of MCC [Motor Control Center] 132X1, which feeds the 1B AF Pump control power. The Unit 0 [Common] Component Cooling Pump feed breaker cubicle was also wetted. Investigation into these components are also in progress. The licensee has entered Technical Specification LCO 3.7.5 Condition A which requires restoration of the one of the AF pumps within 72 hrs. There were no personnel injuries. The licensee has notified the NRC Resident Inspector.
At 1122 [CDT] on 6/8/11, the Unusual Event was terminated due to the flooding conditions no longer existing. Evaluation of wetted components are still in progress. The NRC Resident Inspector has been notified of event. Notified IRD (Gott), R3DO (Lara), NRR EO (Thorp), FEMA (Blankenship), and DHS (Flinter). |
Where | |
---|---|
Braidwood Illinois (NRC Region 3) | |
Reporting | |
Emergency class: | Unusual Event |
10 CFR 50.72(a) (1) (i), Emergency Class Declaration | |
Time - Person (Reporting Time:+-3.3 h-0.138 days <br />-0.0196 weeks <br />-0.00452 months <br />) | |
Opened: | Scott Butler 12:08 Jun 8, 2011 |
NRC Officer: | Howie Crouch |
Last Updated: | Jun 8, 2011 |
46936 - NRC Website
Loading map... {"minzoom":false,"maxzoom":false,"mappingservice":"leaflet","width":"350px","height":"250px","centre":false,"title":"","label":"","icon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"zoom":6,"defzoom":14,"layers":["OpenStreetMap"],"image layers":[],"overlays":[],"resizable":false,"fullscreen":false,"scrollwheelzoom":true,"cluster":false,"clustermaxzoom":20,"clusterzoomonclick":true,"clustermaxradius":80,"clusterspiderfy":true,"geojson":"","clicktarget":"","imageLayers":[],"locations":[{"text":"\u003Cb\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca class=\"mw-selflink selflink\"\u003EENS 46936\u003C/a\u003E - \u003Ca href=\"/Braidwood\" title=\"Braidwood\"\u003EBraidwood\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E\u003C/b\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003ENotification of Unusual Event Due to Flooding That Potentially Affected Safety Related Equipment\n\u003C/p\u003E\u003C/div\u003E","title":"ENS 46936 - Braidwood\n","link":"","lat":41.24283055555556,"lon":-88.2290111111111,"icon":"/w/images/b/be/Constellation_icon.png"}],"imageoverlays":null} | |
Unit 1 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (100 %) |
After | Power Operation (100 %) |
Unit 2 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (99 %) |
After | Power Operation (99 %) |
WEEKMONTHYEARENS 503012014-07-24T00:30:00024 July 2014 00:30:00
[Table view]10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Based on Shots Fired in the Owner Controlled Area ENS 469362011-06-08T15:26:0008 June 2011 15:26:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Due to Flooding That Potentially Affected Safety Related Equipment ENS 466942011-03-24T15:18:00024 March 2011 15:18:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unexpected Loss of Annuciators During Planned Maintenance ENS 456182010-01-10T01:51:00010 January 2010 01:51:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Declared Due to a Fire in the Auxiliary Building Lasting Greater than 15 Minutes ENS 452382009-07-31T02:08:00031 July 2009 02:08:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Declared Due to a Loss of Offsite Power for Greater than 15 Minutes ENS 415342005-03-28T19:59:00028 March 2005 19:59:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Hydrogen Leak 2014-07-24T00:30:00 | |