ML16343A761

From kanterella
Revision as of 03:43, 8 July 2018 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Donald C. Cook Nuclear Plant, Units 1 & 2, Revision 27 to Updated Final Safety Analysis Report, Chapter 14, Table 14.3.9-14, Debris Quantities for Mftl Head Loss Tests
ML16343A761
Person / Time
Site: Cook  American Electric Power icon.png
Issue date: 10/24/2016
From:
Indiana Michigan Power Co
To:
Office of Nuclear Reactor Regulation
Shared Package
ML16336A263 List: ... further results
References
AEP-NRC-2016-42
Download: ML16343A761 (1)


Text

I I N N D D I I A A N N A A A A N N D D M M I I C C H H I I G G A A N N P P O O W W E E R R D D.. C C.. C C O O O O K K N N U U C C L L E E A A R R P P L L A A N N T T U U P P D D A A T T E E D D F F I I N N A A L L S S A A F F E E T T Y Y A A N N A A L L Y Y S S I I S S R R E E P P O O R R T T Revision: 22Table: 14.3.9-14 Page: 1 of 1 UNIT 1 DEBRIS QUANTITIES FOR MFTL HEAD LOSS TESTS Debris Type Units Mass Test 1 (DEGB)

Mass Test 2 (DGBS)

Fibrous Debris Nukon kg 0.447 0.447 Particulate Debris RMI kg 17.590 9.466 Cal-Sil kg 3.402 0.855 Marinite I kg 0.002 0.000 Wollastonite kg 0.006 0.004 Min-K kg 0.016 0.000 Unqualified Non-OEM Epoxy kg 0.196 0.083 Unqualified Non-OEM Alkyd kg 0.049 0.249 Stone Flour kg 17.766 14.564