06:04 May 12, 2015 | |
| Title | |
| Event Description | On May 12, 2015, at 0104 CDT, during performance of 3-SR-3.3.6.1.2(3B), High Pressure Coolant Injection (HPCI) System Steam Supply Pressure Low Functional Test, an inadvertent PCIS Group 4 (HPCI) isolation occurred. All automatic actions occurred as designed. HPCI was declared inoperable and Technical Specification LCO 3.5.1.C was entered with required action to verify immediately that RCIC is operable administratively and to restore HPCI to operable within 14 days. HPCI was returned to service at 0125 CDT, declared operable and TS LCO 3.5.1.C was exited. The cause of the isolation is unknown with an investigation in progress.
This condition is reportable as an 8-hour ENS notification under 10CFR 50.72(b)(3)(v)(D) due to the failure of a single train system affecting accident mitigation. This condition also requires a 60 day written report. The NRC Resident Inspector has been notified. |
| Where | |
|---|---|
| Browns Ferry Alabama (NRC Region 2) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
| Time - Person (Reporting Time:+3.07 h0.128 days <br />0.0183 weeks <br />0.00421 months <br />) | |
| Opened: | Andrew Mitchell 09:08 May 12, 2015 |
| NRC Officer: | Dong Park |
| Last Updated: | May 12, 2015 |
| 51066 - NRC Website
Loading map... {"minzoom":false,"maxzoom":false,"mappingservice":"leaflet","width":"350px","height":"250px","centre":false,"title":"","label":"","icon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"zoom":6,"defzoom":14,"layers":["OpenStreetMap"],"image layers":[],"overlays":[],"resizable":false,"fullscreen":false,"scrollwheelzoom":true,"cluster":false,"clustermaxzoom":20,"clusterzoomonclick":true,"clustermaxradius":80,"clusterspiderfy":true,"geojson":"","clicktarget":"","imageLayers":[],"locations":[{"text":"\u003Cb\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca class=\"mw-selflink selflink\"\u003EENS 51066\u003C/a\u003E - \u003Ca href=\"/Browns_Ferry\" title=\"Browns Ferry\"\u003EBrowns Ferry\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E\u003C/b\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003EHigh Pressure Coolant Injection Declared Inoperable\n\u003C/p\u003E\u003C/div\u003E","title":"ENS 51066 - Browns Ferry\n","link":"","lat":34.70418333333333,"lon":-87.11844722222222,"icon":"/w/images/c/ce/Tennessee_Valley_Authority_icon.png"}],"imageoverlays":null} | |
Unit 3 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |