ENS 43518
From kanterella
Jump to navigation
Jump to search
ENS Event | |
---|---|
21:45 Jul 24, 2007 | |
Title | High Pressure Coolant Injection Inoperable Due to Failed Power Supply |
Event Description | At 1645 on 7/24/07 during the transfer to the Normal Power Supply of the 3A 250 RMQV Board upon completion of scheduled maintenance. Unit 3 High Pressure Coolant Injection system received a 120 VAC Power Failure and was declared inoperable. 120VAC HPCI power is supplied by the Unit 3 ECCS Div 2 Analog Trip Unit Inverter. The Inverter lost power during the 250vdc board transfer and was not able to be restored to service.
Investigation is still continuing on the failure of the Div 2 ECCS Inverter. This event is reportable as an 8-hour Non-Emergency Notification in accordance with 10 CFR 50.72 (b)(3)(v)(B) as; 'Any event or condition that at the time of discovery could have prevented the fulfillment of the Safety Function of structures or systems that are needed to: Remove Residual Heat' ; and 10 CFR 50.72 (b)(3)(v)(D), 'any event or condition that at the time of discovery could have prevented the fulfillment of the Safety Function of structures or systems that are needed to; mitigate the consequences of an accident.' This event also requires a 60 day written report in accordance with 10 CFR 50.73 (a)(2)(v)(B) and 10 CFR 50.73 (a)(2)(v)(D). NRC EVENT # 43518 was reported to Mr. Kozal and the NRC Resident (C. Stancil) was notified at 1925 CDST on 07/24/07. |
Where | |
---|---|
Browns Ferry Alabama (NRC Region 2) | |
Reporting | |
10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
Time - Person (Reporting Time:+0.33 h0.0138 days <br />0.00196 weeks <br />4.52034e-4 months <br />) | |
Opened: | Tim A Golden 22:05 Jul 24, 2007 |
NRC Officer: | Jason Kozal |
Last Updated: | Jul 24, 2007 |
43518 - NRC Website
Loading map... {"minzoom":false,"maxzoom":false,"mappingservice":"leaflet","width":"350px","height":"250px","centre":false,"title":"","label":"","icon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"zoom":6,"defzoom":14,"layers":["OpenStreetMap"],"image layers":[],"overlays":[],"resizable":false,"fullscreen":false,"scrollwheelzoom":true,"cluster":false,"clustermaxzoom":20,"clusterzoomonclick":true,"clustermaxradius":80,"clusterspiderfy":true,"geojson":"","clicktarget":"","imageLayers":[],"locations":[{"text":"\u003Cb\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca class=\"mw-selflink selflink\"\u003EENS 43518\u003C/a\u003E - \u003Ca href=\"/Browns_Ferry\" title=\"Browns Ferry\"\u003EBrowns Ferry\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E\u003C/b\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003EHigh Pressure Coolant Injection Inoperable Due to Failed Power Supply\n\u003C/p\u003E\u003C/div\u003E","title":"ENS 43518 - Browns Ferry\n","link":"","lat":34.70418333333333,"lon":-87.11844722222222,"icon":"/w/images/c/ce/Tennessee_Valley_Authority_icon.png"}],"imageoverlays":null} | |
Unit 3 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (100 %) |
After | Power Operation (100 %) |
Retrieved from "https://kanterella.com/w/index.php?title=ENS_43518&oldid=426848"