OPERATING DATA REPORT I)OCKET NO.
50-219 DATE 10/12/78-COMPLETED BY C. M. McClain TELEPilONE 201-4 %-8200 OPERATING STATUS N"I'5
- 1. Unit Name:
Ovster Creek #1
- 2. Reporting Period:
September i978
- 3. Licensed Thennal Power (MWt):
1930-
. ;., $5p
.,.a r-
- 4. Nameplate Rating (Gross MWe).
650
. - nd --
- 5. Design Electrical Rating (Net MWe):
650
- 6. Maximum Dependable Capacity (Gross MWe):
650 620
- 7. Maximum Dependable Capacity (Net MWe):
- 8. If Changes Occur m Capacity Ratings (Items Number 3 Through 7) Since Last Report. Gise Reasons:
t
- 9. Power Lesel To Which Restricted.lf Any (Net MWe):
- 10. Reasons For Restrictions. lf Any:
This Month Yr. to.Date...
Cumulatise l1. Hcurs in Reporting Period 720.0 6,551.0 76,895.0
- 12. Number Of Hours Reactor Was Critical 343.7 6,105.4 60,510.0
- 13. Reactor Resene Shutdown Hours 0.0 0.0 468.2
- 14. Hours Generator On.Line 331.6 6,069.0 59,340.3
- 15. Unit Reserve Shutdown Hours 0;0 0.0 0.0
- 16. Gross Thermal Energy Generated (MWH1 430,036.0 10,277,193.4 99,267,730.7 i
17 Gross Electrical Energy Generated (MWH1 141,470.0 3,522,180.0 33,879,515 T
- 18. Net Electrical Energy Generated (MWH) 133,258.0 3,396,123.0 32,668,231.0 7
- 19. Unit Service Factnr 46.1 92.6 77.2' j
- 20. Unit Availability Factor 46.1 92.6 77.2
- 21. Unit Capacity Factor'(Using MDC Neti 29.9 83.6 70.4 -
- 22. Unit Capacity Factor (U>ing DER Net) 28.5 79.8 _
65.4
- 23. Unit Fnrced Ontage Rate 7.9 2.t) 5.2 -
- 24. Simidowns Scheduled User Next 6 Months (Type. Date.and Duration of Eacht:
Refueling.* maintenance outage began on September 16, 1978.
- 25. If Shut Down At End Of Report Period, theimated I> ate'of Startup:
November. l'1, 1978
- 26. Units in Test Status Irrior to Commercial Operationi:
Forceast Achiesed INITI A L CRITICA Lil Y INITIA1. ELECTRICITY j
COMM LRCIA L OPER A IlON h h M O eN/
k
(" '" l i
. _ _ _ - - _ _ _. - = _
~ _ _ - - -.
AVI It At.1: D All Y llNil POWI It I l.Yl.l.
o nocxEl No. 50-219 UNil -Oyster Creek #1 DATE.10/12/78 COMPLETED BY C. M. McClain TELEPHONE 201-455-8200 Ext. Plaza 244 MONTH September 1978 DAY AVERAGE DAILY POWER LEVEL DAY AVER AGE DAILY POWER LEVEL (MWe Net)
(MWe Net) i NI9 0
17 i
2
-4I7 18 0
3 41 4 19 0
140 20 0
5 163 0
6 431 22 0
~
7 197 23 0
8 409 24 0
i 9
413 l
25 0
10 410 0
26 11 407 0
27 l
404 0
23 13 405 0
29 y
408 0
/
39 i
is 388 3,
16 0
INSTRUCTIONS On this format. list the arcrage daily unit power lesel ni \\tWe Net for cach day in the reiinstmp month. Compute io the nearest whole megawatt.
I (Ol771 L
m 50-219 DOCKET NO.
UNIT SilUIDOWNS AND POWER REDUCTIONS UNIT NAME _0yster Creek fl DATE 10/12/78 COMPLETED BY' C. H. McClain REPORT MON Til' SeDtember 1978 TELEPHONE 201-455-8200 Ex6. Plaza 244 n.
E E
.3E 3
.$ Y 5' Licensee
,E -r,
'f~,,
Cause & Cr: retine Date BE i
iE5 Evens s?
a2 Aci;on to Report N0
!0 Prevent Recurrense 3 d =!
]8 c
I 7
780904 F
28.4 A
.3 N/A CH INSTRU Mal function of feedwater control system.
Feedwater master controller failed due to a ground in the level recorder.
The necessary repairs were made and plant operations was resumed.
8 780915 s
360.1 S
1 N/A ZZ ZZZZZZ Refueling / maintenance outage.
I 2
3 4
F: Forced Reason:
Method:
Exhibit G-Instructions S. Scheduled A Equipment Failure (Explain) 1 Manual for Preparation of Data B-Maintenance of Test 2-Manual Scram.
Entr> Sheets for Licensee C Refueling 3 Automatic Scram.
Event Report iLt.Rl Fde eNt: REG-D Regulatory Restriction 4-Other I Explain) 0161)
E-Operator Training & License Examination F Administrative 5
G Operational Eiror IExplam)
Exhibit I - Same Sourse l's/77)
Il-Other IE xplain)
Oyster Creek Station #1 Docket No. 50-219 i
GPERATIONS
SUMMARY
- SEPTEMBER 1978 At the beginning of the report period, the unit was operating at approximately 69% power in an end of cycle reactivity coastdown with control rod withdrawal i
limited by the' Technical Specifications.
On September 4,1978, a turbine trip and reactor scram occurred when the feedwater master controller failed due to a ground in the level recorder.
The unit was returned to service on September 5 following repairs to the feedwater controls.
l i
On September 15, 1978, the unit was shut down to commence refueling operations.
Refueling continues at the end of this report period.
i 1
Six (6) Reportable Occurrences were identified during the report period:
d R0 #78-15 occurred during the post scram period on September 4 when both isolation condensers isolated by actuation of their line break sensors.
R0 #78-16 was identified on September 14 and involves failure to inspect two (2) hydraulic shock and sway arrestors as required.
R0 #78-17 occurred on September 14 when the closed position torque switch on isolation condenser valve V-14-37. failed, tr,ipping.the. motor overloads.
R0 #78-18 occurred on September 16 when three (3) main steam isolation
(
valves failed to meet the maximum allowable leakage rate.
l RO #78-19 occurred on September 15 when two (2) reactor building to torus vacuum breaker valves malfunctioned during operability testing.
l
(
I R0 #78-20 occurred on September 17 when two (2) intermediate range flux monitors became inoperable in the refuel mode.
-l
[
l e
f i
I i
I t
?
I
7 Oyster Creek Station #1
^
~
i Docket No. 50-219 INSTRLNENT CORRECTIVE MARTIDWCE OF GASL ITDiS FOR THE MONril OF SEPTDiBER,1978 Item #
I.
Fguignent Malfunction Corrective Action 1
Waste Concentrator level Recorder will not Repaired broken wire in Ievel Recorder advance in chart drive motor 2
Isolation Condenser Inoperative Replaced defective notor Shell. Side 'Ibnp. Recorder assembly
> Repaired nonitor as per i
3 Main Steam Line Monitor reading low bbnitor i1-4 procedure 721.3.001 1
4 Beactor Invel Recorder responsible for Replaced with calibrated recorder 1D-14 Rx scram on 9/5/78 recorder 5
IBM Channel 14 Surveillance discrepancy Calibrated nean square analog l
noter reading not within unit as per instruction tech l
40% + 1%
manual No. GEK857, readjusted I
the (125%-40%) reading to meet tech specs 6
IRM Channel 16 Detector inoperative Installed new detector as per procedure 720.3.002 7
SRM Surveillance No lights on 4P i Changed defective dual trip t
step 6:10 unit (17.
Readjusted and tested as per procedure 721.3.001 4
Fuel Pool Recorder String on recorder broken Replaced string and calibrated 8
I l
f 8
s S. %
v w --i e--r-w--.--u--=,.
,,--c--o w
v-n----
- - - - - + -
-r----
ee r,
m
-y--m w
-- r + = - - - =-e y-
-,erv vw,n.--,,
r--*
,,r,-
m2v,--g--- - --. -,-
y
Oyster Creek Station #1
^
i Docket No. 50-219 MBCilANICAL CORRECTIVE MAINIDWKE OF OASL ITEMS FOR 'IIIE MONTil OF SEPTEFBER,1978 Item #
ELIniprent Malfunction Corrective Action 1
Fuel Fool Bridge Fuel grapple sticking Inspt M. grapple and tightened guide shces 2
1-2 Fire Ptmp Icak on cooling water Replaced 5' of pipe,1 1/2" inlet line schedule 80 3
V-ll-17, makeup valve Valve not closing Installed new valve stem, to fuel pool off properly diaphragm, and bushing 4
CRD Mxlule 34-31 V-107 Ilandwheel missing Installed new stem and handle 5
Fire Diesel 1-2 Oil terrperature and coolant Installed ncw thermostat and terrperature did not achieve tested OK mininun specifications as I
per procedure 645.4.001 6
Fuel Pool Filter Filter elments suspected Installed new filter elements of failing 7
Radwaste centrifuge East bearing leaking oil Repaired oiler on both bearings 8
CRD 34-19 V-lll valve leaking Replaced V-lll valve with rebuiit v1 9
Snubbers -
Accmulator levels on Checked accuuulator levels and Beactor Bldg.
w rtain snubbers did not added or drained oil as necessary conform to procedure on last inspection I
't. %
Oyster Creek Station il
-w Docket tio. 50-219 ELECTRICAL CORRECP1VE 1%INTE2mNCE OF QN3L-ITOG mR 'nE MOtml OF SEPI124BER,1973 1
Item i Equignent Malfunction Corrective Action 1
Belay 6K59 Pelay appears to be buzzing Feplac M faulty relay with same type 2
Dnergency Condenser, Screw on torque switch was Adjusted switch and tightened Isolation Valve V-14-37, loose causing "close" screws "Close" limit switch torque switch to move s
failed to drop out contactor tripping r
overload i
3 6Kl7 Belay, Control Relay buzzing Changed out relay Ibom Panel llF 4
- 2 Diesel Generator Did not trip at 500 IM, Idjusted rack switch in l
tripped at 50 KW governor actuator and tested satisfactorily i
e i
e
?
k r
4 i
's I
Oyster Creek Station #1 Docket No. 50-219 REFUELING INFORMATION - SEPTEMBER 1978 Name of facility:
Oyster Creek Station #1 Scheduled date for next refueling shutdown:
Began September 16, 1978 Scheduled date for restart following refueling:
November 11, 1978 Will refueling or resumption of operation thereaf ter require a Technical Specification change or other license amendment?
No. Technical Specification change relative to the refueling is s
anticipated.
It has been determined that no unreviewed safety questions are associated with the reload core.
Sche' uled date(s) for submitting proposed licensing action and supporting d
information:
No submittal is scheduled.
I Important licensing considerations associated with refueling, e.g., new or different fuel design or supplier, unreviewed design or performance analysis methods, significant changes in fuel design, new' operating. procedures:
No major changes have been made, nor are there any anticipated.
The number of fuel assemblies (a) in the core
- 560 (b) in the spent fuel storage pool - 452 The present licensed spent fuei pool storage capacity and the size of any i
increase in licensed storage capacity that has been requested or is planned, l
In number of fuel ~ assemblies:
"~ ls 1,800 The projected date of the last refueling that can be discharged to the spent fuel pool assuming the present licensed capacity:
l
^
s The Fall 1986 Outage.
~
h i
f 9
l l
'