MONTHYEARML20217K4451999-09-30030 September 1999 Monthly Operating Rept for Sept 1999 for Oyster Creek Nuclear Generating Station.With ML20211P6731999-08-31031 August 1999 Monthly Operating Rept for Aug 1999 for Oyster Creek Nuclear Generating Station.With ML20211A7051999-07-31031 July 1999 Monthly Operating Rept for July 1999 for Oyster Creek Nuclear Station.With ML20209G0631999-06-30030 June 1999 Monthly Operating Rept for June 1999 for Oyster Creek Nuclear Generating Station.With ML20195E7961999-05-31031 May 1999 Monthly Operating Rept for May 1999 for Oyster Creek Nuclear Generating Station.With ML20206N7431999-04-30030 April 1999 Monthly Operating Rept for Apr 1999 for Oyster Creek Nuclear Generating Station.With ML20205P5401999-03-31031 March 1999 Monthly Operating Rept for Mar 1999 for Oyster Creek Nuclear Generating Station.With ML20204C8201999-02-28028 February 1999 Monthly Operating Rept for Feb 1999 for Oyster Creek Nuclear Generating Station.With ML20199E4671998-12-31031 December 1998 Monthly Operating Rept for Dec 1998 for Oyster Creek Nuclear Generating Station.With ML20198D2091998-11-30030 November 1998 Monthly Operating Rept for Nov 1998 for Oyster Creek Nuclear Generating Station.With ML20155J3021998-10-31031 October 1998 Monthly Operating Rept for Oct 1998 for Oyster Creek Nuclear Generating Station.With ML20154L5571998-09-30030 September 1998 Monthly Operating Rept for Sept 1998 for Oyster Creek Nuclear Generating Station.With ML20151V6311998-08-31031 August 1998 Monthly Operating Rept for Aug 1998 for Oyster Creek Nuclear Generating Station.With ML20237B0131998-07-31031 July 1998 Monthly Operating Rept for July 1998 for Oyster Creek Nuclear Generating Station ML20236R0511998-06-30030 June 1998 Monthly Operating Rept for June 1998 for Oyster Creek Nuclear Generating Station ML20249B2981998-05-31031 May 1998 Monthly Operating Rept for May 1998 for Oyster Creek Nuclear Station ML20247G0581998-04-30030 April 1998 Monthly Operating Rept for Apr 1998 for Oyster Creek Nuclear Generating Station ML20216K0341998-03-31031 March 1998 Monthly Operating Rept for Mar 1998 for Oyster Creek Nuclear Generating Station ML20216J0841998-02-28028 February 1998 Monthly Operating Rept for Feb 1998 for Oyster Creek Nuclear Generating Station ML20203A3801998-01-31031 January 1998 Monthly Operating Rept for Jan 1998 for Oyster Creek Nuclear Generation Station ML20198P1791997-12-31031 December 1997 Monthly Operating Rept for Dec 1997 for Oyster Creek Nuclear Station ML20197E9131997-11-30030 November 1997 Monthly Operating Rept for Nov 1997 for Oyster Creek Nuclear Station ML20199D4381997-10-31031 October 1997 Monthly Operating Rept for Oct 1997 for Oyster Creek Nuclear Station ML20198J7361997-09-30030 September 1997 Monthly Operating Rept for Sept 1997 for Oyster Creek Nuclear Generating Station ML20210V0181997-08-31031 August 1997 Monthly Operating Rept for Aug 1997 for Oyster Creek Nuclear Generating Station ML20210L2961997-07-31031 July 1997 Monthly Operating Rept for Jul 1997 for Oyster Creek Nuclear Station ML20141H2051997-06-30030 June 1997 Monthly Operating Rept for June 1997 for Oyster Creek Nuclear Station ML20210L3081997-06-30030 June 1997 Corrected Page to MOR for June 1997 for Oyster Creek Nuclear Generating Station ML20141A5021997-05-31031 May 1997 Monthly Operating Rept for May 1997 for Oyster Creek Nuclear Generating Station ML20141H7441997-04-30030 April 1997 Monthly Operating Rept for Apr 1997 for Oyster Creek Nuclear Generating Station ML20137X8231997-03-31031 March 1997 Monthly Operating Rept for Mar 1997 for Oyster Creek Nuclear Generating Station ML20137C3771997-02-28028 February 1997 Monthly Operating Rept for Feb 1997 for Ocnpp ML20134P6151997-01-31031 January 1997 Monthly Operating Rept for Jan 1997 for Oyster Creek Nuclear Generating Station ML20133M1751996-12-31031 December 1996 Monthly Operating Rept for Dec 1996 for Oyster Creek Nuclear Generating Station ML20132D1011996-11-30030 November 1996 Monthly Operating Rept for Nov 1996 for Oyster Creek Nuclear Generating Station ML20134M9761996-10-31031 October 1996 Monthly Operating Rept for Oct 1996 for Oyster Creek Nuclear Generating Station ML20129B1631996-09-30030 September 1996 Monthly Operating Rept for Sept 1996 for Oyster Creek Nuclear Generating Station ML20117M7561996-08-31031 August 1996 Monthly Operating Rept for Aug 1996 for Oyster Creek Nuclear Generating Station ML20116M6761996-07-31031 July 1996 Monthly Operating Rept for Jul 1996 for Oyster Creek Nuclear Generating Station ML20115F8561996-06-30030 June 1996 Monthly Operating Rept for June 1996 for Oyster Creek Nuclear Generating Station ML20112J7431996-05-31031 May 1996 Monthly Operating Rept for May 1996 for Oyster Creek Nuclear Generating Station ML20112A6891996-04-30030 April 1996 Monthly Operating Rept for Apr 1996 for Oyster Creek Nuclear Generating Station ML20101R0401996-03-31031 March 1996 Monthly Operating Rept for Mar 1996 for Oyster Creek Station ML20101D7701996-02-29029 February 1996 Monthly Operating Rept for Feb 1996 for Ocnpp ML20100G5101996-01-31031 January 1996 Monthly Operating Rept for Jan 1996 for Oyster Creek Nuclear Generating Station ML20096E8071995-12-31031 December 1995 Monthly Operating Rept for Dec 1995 for Oyster Creek Nuclear Generating Station ML20099L7571995-11-30030 November 1995 Monthly Operating Rept for Nov 1995 for Oyster Creek Nuclear Generating Station ML20094P8431995-10-31031 October 1995 Monthly Operating Rept for Oct 1995 for Oyster Creek Nuclear Generating Station ML20093H3571995-09-30030 September 1995 Monthly Operating Rept for Sept 1995 for Oyster Creek Nuclear Generating Station ML20092H7741995-08-31031 August 1995 Monthly Operating Rept for Aug 1995 for Oyster Creek Nuclear Generating Station 1999-09-30
[Table view] Category:TEXT-SAFETY REPORT
MONTHYEARML20217K4451999-09-30030 September 1999 Monthly Operating Rept for Sept 1999 for Oyster Creek Nuclear Generating Station.With ML20211P6731999-08-31031 August 1999 Monthly Operating Rept for Aug 1999 for Oyster Creek Nuclear Generating Station.With ML20211A7051999-07-31031 July 1999 Monthly Operating Rept for July 1999 for Oyster Creek Nuclear Station.With ML20209G0631999-06-30030 June 1999 Monthly Operating Rept for June 1999 for Oyster Creek Nuclear Generating Station.With ML20212H5491999-06-18018 June 1999 Non-proprietary Rev 4 to HI-981983, Licensing Rept for Storage Capacity Expansion of Oyster Creek Spent Fuel Pool ML20195E7961999-05-31031 May 1999 Monthly Operating Rept for May 1999 for Oyster Creek Nuclear Generating Station.With ML20206N7431999-04-30030 April 1999 Monthly Operating Rept for Apr 1999 for Oyster Creek Nuclear Generating Station.With ML20205P5401999-03-31031 March 1999 Monthly Operating Rept for Mar 1999 for Oyster Creek Nuclear Generating Station.With ML20204C8201999-02-28028 February 1999 Monthly Operating Rept for Feb 1999 for Oyster Creek Nuclear Generating Station.With ML20199E4671998-12-31031 December 1998 Monthly Operating Rept for Dec 1998 for Oyster Creek Nuclear Generating Station.With ML20195E8321998-12-31031 December 1998 10CFR50.59(b) Rept of Changes to Oyster Creek Sys & Procedures, for Period of June 1997 to Dec 1998.With ML20198D2091998-11-30030 November 1998 Monthly Operating Rept for Nov 1998 for Oyster Creek Nuclear Generating Station.With ML20195J8591998-11-12012 November 1998 Rev 11 to 1000-PLN-7200.01, Gpu Nuclear Operational QA Plan ML20195C4271998-11-0606 November 1998 Safety Evaluation Supporting Proposed Ocnpp Mod to Install Core Support Plate Wedges to Structurally Replace Lateral Resistance Provided by Rim Hold Down Bolts for One Operating Cycle ML20155J3021998-10-31031 October 1998 Monthly Operating Rept for Oct 1998 for Oyster Creek Nuclear Generating Station.With ML20154R4981998-10-20020 October 1998 Core Spray Sys Insp Program - 17R ML20154L3051998-10-14014 October 1998 Safety Evaluation Accepting Licensee Request to Defer Insp of 79 Welds from One Fuel Cycle at 17R Outage ML20154Q3371998-09-30030 September 1998 Rev 8 to Oyster Creek Cycle 17,COLR ML20154L5571998-09-30030 September 1998 Monthly Operating Rept for Sept 1998 for Oyster Creek Nuclear Generating Station.With ML20151V6311998-08-31031 August 1998 Monthly Operating Rept for Aug 1998 for Oyster Creek Nuclear Generating Station.With ML20237D5691998-08-31031 August 1998 Rev 0 to MPR-1957, Design Submittal for Oyster Creek Core Plate Wedge Modification ML20237D5711998-08-18018 August 1998 Rev 0 to SE-000222-002, Core Plate Wedge Installation ML20237B0131998-07-31031 July 1998 Monthly Operating Rept for July 1998 for Oyster Creek Nuclear Generating Station ML20236R0511998-06-30030 June 1998 Monthly Operating Rept for June 1998 for Oyster Creek Nuclear Generating Station ML20249B2981998-05-31031 May 1998 Monthly Operating Rept for May 1998 for Oyster Creek Nuclear Station ML20248F3531998-05-21021 May 1998 Part 21 Rept Re Electronic Equipment Repaired or Reworked by Integrated Resources,Inc from Approx 930101-980501.Caused by 1 Capacitor in Each Unit Being Installed W/Reverse Polarity. Policy of Second Checking All Capacitors Is Being Adopted ML20247F1891998-05-0505 May 1998 Risk Evaluation of Post-LOCA Containment Overpressure Request ML20247G0581998-04-30030 April 1998 Monthly Operating Rept for Apr 1998 for Oyster Creek Nuclear Generating Station ML20216K0341998-03-31031 March 1998 Monthly Operating Rept for Mar 1998 for Oyster Creek Nuclear Generating Station ML20151Y4651998-03-31031 March 1998 Non-proprietary Version of Rev 1 to GENE-E21-00143, ECCS Suction Strainer Hydraulic Sizing Rept ML20217A4631998-03-23023 March 1998 Safety Evaluation Accepting Use of Three Heats/Lots of Hot Rolled XM-19 Matl in Core Shroud Repair Assemblies Re Licenses DPR-16 & DPR-59,respectively ML20212E2291998-03-0404 March 1998 Rev 11 to 1000-PLN-7200,01, Gpu Nuclear Operational QAP, Consisting of Revised Pages & Pages for Which Pagination Affected ML20216J0841998-02-28028 February 1998 Monthly Operating Rept for Feb 1998 for Oyster Creek Nuclear Generating Station ML20203B2781998-02-16016 February 1998 10CFR50.59(b) Rept of Changes to Oyster Creek Systems & Procedures ML20203A3801998-01-31031 January 1998 Monthly Operating Rept for Jan 1998 for Oyster Creek Nuclear Generation Station ML20198P1791997-12-31031 December 1997 Monthly Operating Rept for Dec 1997 for Oyster Creek Nuclear Station ML20217C7591997-12-31031 December 1997 1997 Annual Environmental Operating Rept for Oyster Creek Nuclear Generating Station ML20197E9131997-11-30030 November 1997 Monthly Operating Rept for Nov 1997 for Oyster Creek Nuclear Station ML20199E4561997-11-13013 November 1997 Safety Evaluation Accepting Ampacity Derating Analysis in Response to NRC RAI Re GL-92-08, Thermo-Lag 330-1 Fire Barriers, for Plant ML20199D4381997-10-31031 October 1997 Monthly Operating Rept for Oct 1997 for Oyster Creek Nuclear Station ML20202E8511997-10-21021 October 1997 Rev 0 to Scenario 47, Gpu Nuclear Oyster Creek Nuclear Generating Station Emergency Preparedness (Nrc/Fema Evaluated) 1997 Biennial Exercise. Pages 49 & 59 of Incoming Submittal Were Not Included ML20211M9481997-10-0303 October 1997 Supplemental Part 21 Rept Re Condition Effected Emergency Svc Water Pumps Supplied by Bw/Ip Intl Inc to Gpu Nuclear, Oyster Creek Nuclear Generation Station.No Other Nuclear Generating Stations Effected by Notification ML20198J7361997-09-30030 September 1997 Monthly Operating Rept for Sept 1997 for Oyster Creek Nuclear Generating Station ML20211B7461997-09-24024 September 1997 Part 21 Rept Re Failure of Emergency Service Water Pump Due to Threaded Flange Attaching Column to Top Series Case Failure.Caused by Dissimilar Metals.Pumps in High Ion Svc Will Be Upgraded to 316 Stainless Steel Matl ML20210V0181997-08-31031 August 1997 Monthly Operating Rept for Aug 1997 for Oyster Creek Nuclear Generating Station ML20210L2961997-07-31031 July 1997 Monthly Operating Rept for Jul 1997 for Oyster Creek Nuclear Station ML20149F9961997-07-18018 July 1997 Safety Evaluation Re Gpu Nuclear Operational Quality Assurance Plan,Rev 10 for Three Mile Island Nuclear Generating Station,Unit 1 & Oyster Creek Nuclear Generating Station ML20196H0111997-07-11011 July 1997 Special Rept 97-001:on 970620,removed High Range Radioactive Noble Gas Effluent Monitor (Stack Ragems) from Service to Allow Secondary Calibr IAW Master Surveillance Schedule. Completed Calibr on 970628 & Returned Stack Ragems to Svc ML20210L3081997-06-30030 June 1997 Corrected Page to MOR for June 1997 for Oyster Creek Nuclear Generating Station ML20141H2051997-06-30030 June 1997 Monthly Operating Rept for June 1997 for Oyster Creek Nuclear Station 1999-09-30
[Table view] |
Text
.
OPERATING DATA REPORT I)OCKET NO. 50-219
- DATE 10/12/78-COMPLETED BY C. M. McClain TELEPilONE 201-4 %-8200 -
OPERATING STATUS Ovster Creek #1 N"I'5
- 1. Unit Name:
- 2. Reporting Period: September i978 -
- 3. Licensed Thennal Power (MWt): 1930- .. . ;., $5p . ,.a r-
- 4. Nameplate Rating (Gross MWe).
650 . - nd --
- 5. Design Electrical Rating (Net MWe): 650
- 6. Maximum Dependable Capacity (Gross MWe): 650 -
- 7. Maximum Dependable Capacity (Net MWe): 620
- 8. If Changes Occur m Capacity Ratings (Items Number 3 Through 7) Since Last Report. Gise Reasons:
t
- 9. Power Lesel To Which Restricted.lf Any (Net MWe):
- 10. Reasons For Restrictions. lf Any:
This Month ..
Yr. to.Date . . . Cumulatise >
l1. Hcurs in Reporting Period 720.0 6,551.0 76,895.0
- 12. Number Of Hours Reactor Was Critical ._ 343.7 6,105.4 60,510.0
- 13. Reactor Resene Shutdown Hours 0.0 0.0 468.2
- 14. Hours Generator On.Line 331.6 6,069.0 59,340.3
- 15. Unit Reserve Shutdown Hours 0;0 0.0 0.0
- 16. Gross Thermal Energy Generated (MWH1 430,036.0 10,277,193.4 99,267,730.7 -
i 17 Gross Electrical Energy Generated (MWH1 141,470.0 3,522,180.0 33,879,515 T
- 18. Net Electrical Energy Generated (MWH) 133,258.0 3,396,123.0 32,668,231.0 7
- 19. Unit Service Factnr 46.1 92.6 77.2' j
- 20. Unit Availability Factor 46.1 92.6 77.2
- 21. Unit Capacity Factor'(Using MDC Neti 29.9 83.6 70.4 -
- 22. Unit Capacity Factor (U>ing DER Net) 28.5 79.8 _ 65.4
- 23. Unit Fnrced Ontage Rate 7.9 2.t) 5.2 -
- 24. Simidowns Scheduled User Next 6 Months (Type. Date.and Duration of Eacht:
Refueling.* maintenance outage began on September 16, 1978.
- 25. If Shut Down At End Of Report Period, theimated I> ate'of Startup: November. l'1, 1978
- 26. Units in Test Status Irrior to Commercial Operationi: Forceast Achiesed INITI A L CRITICA Lil Y INITIA1. ELECTRICITY j COMM LRCIA L OPER A IlON
- l h h M O eN/ k -
(" '" l i
. _ - _ ___ ___ _ _ - __ _ - - _ _- . _ _ _ - - _ _ _ . - = _ _ , . . _ _ _ . . ~ _ _ - - - .
o
- AVI It At.1: D All Y llNil POWI It I l.Yl.l.
nocxEl No. 50-219 UNil -Oyster Creek #1 DATE .10/12/78 COMPLETED BY C. M. McClain TELEPHONE 201-455-8200 Ext. Plaza 244 MONTH September 1978 DAY AVERAGE DAILY POWER LEVEL DAY AVER AGE DAILY POWER LEVEL (MWe Net) (MWe Net) i NI9 17 0 i 2 -4I7 18 0 3 41 4 19 0
.: 140 20 0 5 163 0
~
6 431 22 0 7 197 23 0 i 8 409 24 0 9 413 25 0 l
10 410 26 0 11 407 27 0 l
- 404 23 0 13 405 0 29 y 408 0 /
39 i is 388 3, 16 0 INSTRUCTIONS On this format. list the arcrage daily unit power lesel ni \tWe Net for cach day in the reiinstmp month. Compute io the nearest whole megawatt.
I (Ol771 L -
m -
DOCKET NO. 50-219 UNIT SilUIDOWNS AND POWER REDUCTIONS UNIT NAME _0yster Creek fl DATE 10/12/78 .
COMPLETED BY' C. H. McClain REPORT MON Til' SeDtember 1978 TELEPHONE 201-455-8200 Ex6. Plaza 244 n.
- E E
-, .3E 3 .$ Y 5' Licensee ,E -r, 'f~,,
a2 Cause & Cr: retine
%. Date
- - BE i iE5 Evens N0 s?
Aci;on to
]8 $ Report !0 Prevent Recurrense
, 3 dc=!
I 7 780904 F 28.4 A .3 N/A CH INSTRU Mal function of feedwater control system. Feedwater master controller failed due to a ground in the level recorder. The necessary repairs were made and plant operations was resumed. -
8 780915 s 360.1 S 1 N/A ZZ ZZZZZZ Refueling / maintenance outage.
I 2 3 4 F: Forced Reason: Method: Exhibit G-Instructions S. Scheduled A Equipment Failure (Explain) 1 Manual for Preparation of Data '
B-Maintenance of Test 2-Manual Scram. Entr> Sheets for Licensee C Refueling . 3 Automatic Scram. Event Report iLt.Rl Fde eNt: REG-D Regulatory Restriction 4-Other I Explain) 0161)
E-Operator Training & License Examination F Administrative 5 G Operational Eiror IExplam) Exhibit I - Same Sourse l's/77) Il-Other IE xplain)
Oyster Creek Station #1 Docket No. 50-219 i
GPERATIONS
SUMMARY
- SEPTEMBER 1978 (
At the beginning of the report period, the unit was operating at approximately
- 69% power in an end of cycle reactivity coastdown with control rod withdrawal i limited by the' Technical Specifications. On September 4,1978, a turbine trip and reactor scram occurred when the feedwater master controller failed -
due to a ground in the level recorder. The unit was returned to service on ,
September 5 following repairs to the feedwater controls. l i
On September 15, 1978, the unit was shut down to commence refueling operations. '
Refueling continues at the end of this report period. , i 1
Six (6) Reportable Occurrences were identified during the report period:
d R0 #78-15 occurred during the post scram period on September 4 when both isolation condensers isolated by actuation of their line break sensors. .
R0 #78-16 was identified on September 14 and involves failure to ,
inspect two (2) hydraulic shock and sway arrestors as required.
R0 #78-17 occurred on September 14 when the closed position torque switch on isolation condenser valve V-14-37. failed, tr,ipping.the. motor .
overloads.
R0 #78-18 occurred on September 16 when three (3) main steam isolation (
valves failed to meet the maximum allowable leakage rate. l RO #78-19 occurred on September 15 when two (2) reactor building to ;
torus vacuum breaker valves malfunctioned during operability testing. l
( R0 #78-20 occurred on September 17 when two (2) intermediate range I
flux monitors became inoperable in the refuel mode. -l
[
_ l
,, e f
i I
i ,
I t
?
I
7
^ ~ Oyster Creek Station #1 i Docket No. 50-219 , .
INSTRLNENT CORRECTIVE MARTIDWCE OF GASL ITDiS FOR THE MONril OF SEPTDiBER,1978
.; Item # I. Fguignent Malfunction Corrective Action -
1 Waste Concentrator level Recorder will not Repaired broken wire in Ievel Recorder advance in chart drive motor -
2 Isolation Condenser Inoperative Replaced defective notor Shell. Side 'Ibnp. Recorder assembly 3 Main Steam Line Monitor reading low - < > Repaired nonitor as per
- bbnitor i1-4 procedure 721.3.001 4 Beactor Invel Recorder responsible for Replaced with calibrated recorder 1D-14 Rx scram on 9/5/78 recorder 5 IBM Channel 14 Surveillance discrepancy Calibrated nean square analog noter reading not within unit as per instruction tech 40% + 1% manual No. GEK857, readjusted I the (125%-40%) reading to !
, meet tech specs 6 IRM Channel 16 Detector inoperative Installed new detector as per
. procedure 720.3.002 7 SRM Surveillance No lights on 4P i Changed defective dual trip t step 6:10 unit (17. Readjusted and .
tested as per procedure 721.3.001 8 .
Fuel Pool Recorder String on recorder broken Replaced string and calibrated 4
I l
f 8
s S. %
,..,_-%. - . v - - - - w --i e--r-w--.--u--=,. ,,--c--o w v-n---- - - - - - + - -r---- ----ee r, m -y--m -
_w -- r + = - - - =-e y- -,erv vw,n.--,, * --- - - - r--* ,,r,- , m2v,--g--- - --. -,- -----y
^ i Oyster Creek Station #1 Docket No. 50-219 , ,
MBCilANICAL CORRECTIVE MAINIDWKE OF OASL ITEMS FOR 'IIIE MONTil OF SEPTEFBER,1978 ,
Item # ELIniprent Malfunction Corrective Action 1 Fuel Fool Bridge Fuel grapple sticking Inspt M. grapple and tightened guide shces 2 1-2 Fire Ptmp Icak on cooling water Replaced 5' of pipe,1 1/2" inlet line schedule 80 3 V-ll-17, makeup valve Valve not closing Installed new valve stem, to fuel pool off properly diaphragm, and bushing 4 CRD Mxlule 34-31 V-107 Ilandwheel missing Installed new stem and handle 5 Fire Diesel 1-2 Oil terrperature and coolant Installed ncw thermostat and terrperature did not achieve tested OK mininun specifications as I per procedure 645.4.001 6 Fuel Pool Filter Filter elments suspected Installed new filter elements of failing Repaired oiler on both bearings 7 Radwaste centrifuge East bearing leaking oil 8 CRD 34-19 V-lll valve leaking Replaced V-lll valve with rebuiit v1 9 Snubbers - Accmulator levels on Checked accuuulator levels and Beactor Bldg. w rtain snubbers did not added or drained oil as necessary conform to procedure on last inspection I
't. %
-w - .
Oyster Creek Station il .
Docket tio. 50-219 ELECTRICAL CORRECP1VE 1%INTE2mNCE OF QN3L-ITOG mR 'nE MOtml OF SEPI124BER,1973 1
Item i Equignent Malfunction Corrective Action -
1 Belay 6K59 Pelay appears to be buzzing Feplac M faulty relay with
2 Dnergency Condenser, Screw on torque switch was Adjusted switch and tightened <
Isolation Valve V-14-37, loose causing "close" screws "Close" limit switch torque switch to move s failed to drop out contactor tripping r
overload i 3 6Kl7 Belay, Control .
Relay buzzing Changed out relay Ibom Panel llF ,
4 #2 Diesel Generator Did not trip at 500 IM, Idjusted rack switch in l tripped at 50 KW governor actuator and tested satisfactorily i
e e
i
?
r 4
i
. 's I
Oyster Creek Station #1 .
Docket No. 50-219 REFUELING INFORMATION - SEPTEMBER 1978 Name of facility: Oyster Creek Station #1 Scheduled date for next refueling shutdown: Began September 16, 1978 Scheduled date for restart following refueling: November 11, 1978 Will refueling or resumption of operation thereaf ter require a Technical Specification change or other license amendment?
No . Technical s Specification change relative to the refueling is anticipated. It has been determined that no unreviewed safety
. questions are associated with the reload core.
Sche' d uled date(s) for submitting proposed licensing action and supporting information:
No submittal is scheduled. -
I Important licensing considerations associated with refueling, e.g. , new or '
different fuel design or supplier, unreviewed design or performance analysis methods, significant changes in fuel design, new' operating . procedures: '
No major changes have been made, nor are there any anticipated. -
The number of fuel assemblies (a) in the core -
- 560 (b) in the spent fuel storage pool - 452
< The present licensed spent fuei pool storage capacity and the size of any i increase in licensed storage capacity that has been requested or is planned, l In number of fuel ~ assemblies: ,
"~ ls :
1,800 The projected date of the last refueling that can be discharged to the spent fuel pool assuming the present licensed capacity: *
^
l s The Fall 1986 Outage.
~ .
h i
f 9
l l