ENS 41072
ENS Event | |
---|---|
03:56 Sep 26, 2004 | |
Title | Unusual Event Declared Due to a Loss of Offsite Power |
Event Description | At 2356 [EDT], September 25, 2004, off-site power was lost for both units. At the time of the event both units were in mode 4 and cooling down to meet shutdown entry conditions. The shutdown of both units was due to hurricane conditions from hurricane Jeanne. All four emergency diesels (2 per unit) started and properly loaded. Both units are stable in natural circulation cooling. Efforts continue to place both units on shutdown cooling. All systems operated as expected. The plant was already in a Notification of Unusual Event due to the Hurricane. Shutdown Cooling was established on Unit 1 at approximately 0020 EDT on 9/26/04.
The licensee informed both state and local agencies and the NRC Resident Inspector. A conference call was held at approximately 0005 EDT with R2 Response Manager (Len Wert), NRR EO (Stu Richards) and IRD (Susan Frant) to discuss the loss of offsite power. The participants concluded that the NRC Monitoring Mode entered at 1515 EDT on 9/25 for the Hurricane was appropriate.
At 2356, September 25, 2004, St. Lucie Station, Units 1 and 2, experienced a loss of off -site power (LOOP). At the time of the LOOP all four emergency diesel generators started and loaded the safety related buses. In it's initial notification of the LOOP (0035 09/26/04, EN# 41067), FPL reported that all systems had performed as expected. However, during it's post LOOP walkdowns of the control room boards the control room operators determined that the 1 B Intake Cooling Water (ICW) pump had not automatically started as expected. The pump was subsequently started from the control room using the manual control switch. The cause for the failure to automatically start will be investigated and corrected prior to returning the unit to service. Notified R2 Response Manager (Len Wert)
At 1050 EDT both units recovered offsite power exiting the criteria for the UE based on LOOP. The licensee informed state and local agencies and the NRC Resident Inspector. HOO Note: See related ENs # 41067, 41071 and 41073. |
Where | |
---|---|
Saint Lucie Florida (NRC Region 2) | |
Reporting | |
Emergency class: | Unusual Event |
10 CFR 50.72(a) (1) (i), Emergency Class Declaration 10 CFR 50.72(b)(3)(iv)(A), System Actuation | |
Time - Person (Reporting Time:+-3.35 h-0.14 days <br />-0.0199 weeks <br />-0.00459 months <br />) | |
Opened: | Tom Coste 00:35 Sep 26, 2004 |
NRC Officer: | Steve Sandin |
Last Updated: | Sep 26, 2004 |
41072 - NRC Website
Loading map... {"minzoom":false,"maxzoom":false,"mappingservice":"leaflet","width":"350px","height":"250px","centre":false,"title":"","label":"","icon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"zoom":6,"defzoom":14,"layers":["OpenStreetMap"],"image layers":[],"overlays":[],"resizable":false,"fullscreen":false,"scrollwheelzoom":true,"cluster":false,"clustermaxzoom":20,"clusterzoomonclick":true,"clustermaxradius":80,"clusterspiderfy":true,"geojson":"","clicktarget":"","imageLayers":[],"locations":[{"text":"\u003Cb\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca class=\"mw-selflink selflink\"\u003EENS 41072\u003C/a\u003E - \u003Ca href=\"/Saint_Lucie\" title=\"Saint Lucie\"\u003ESaint Lucie\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E\u003C/b\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003EUnusual Event Declared Due to a Loss of Offsite Power\n\u003C/p\u003E\u003C/div\u003E","title":"ENS 41072 - Saint Lucie\n","link":"","lat":27.348672222222223,"lon":-80.24639722222223,"icon":"/w/images/9/9b/NextEra_Energy_icon.png"}],"imageoverlays":null} | |
Unit 1 | |
---|---|
Reactor critical | Not Critical |
Scram | No |
Before | Hot Shutdown (0 %) |
After | Hot Shutdown (0 %) |
Unit 2 | |
---|---|
Reactor critical | Not Critical |
Scram | No |
Before | Hot Shutdown (0 %) |
After | Hot Shutdown (0 %) |
Saint Lucie with 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation | |
WEEKMONTHYEARENS 572492024-07-28T22:37:00028 July 2024 22:37:00
[Table view]10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip ENS 560872022-09-03T02:48:0003 September 2022 02:48:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to Loss of Feed Pump ENS 550782021-01-20T23:22:00020 January 2021 23:22:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Trip of Motor Control Center ENS 548082020-07-31T21:00:00031 July 2020 21:00:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notice of Unusual Event Due to Hurricane Warning Posted for Area ENS 543622019-10-30T04:26:00030 October 2019 04:26:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Due to Release of Flammable Gas ENS 542532019-09-01T21:17:0001 September 2019 21:17:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration En Revision Imported Date 9/4/2019 ENS 531112017-12-11T04:50:00011 December 2017 04:50:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Due to a Smoke Detector Alarm Received Inside Containment ENS 530852017-11-22T14:37:00022 November 2017 14:37:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration St. Lucie Unit 2 Unusual Event Due to a Smoke Detector Alarm Received Inside Containment ENS 530362017-10-26T06:12:00026 October 2017 06:12:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Following a Loss of Load ENS 529562017-09-08T21:14:0008 September 2017 21:14:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event - Hurricane Warning ENS 527572017-05-15T22:00:00015 May 2017 22:00:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Valid Emergency Diesel Generator Signal Generated Upon Loss of 4160V Power ENS 522802016-10-05T02:53:0005 October 2016 02:53:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Due to a Hurricane Warning ENS 521912016-08-21T23:37:00021 August 2016 23:37:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event - Loss of Offsite Power ENS 514232015-09-17T16:22:00017 September 2015 16:22:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Valid Actuation of Uv Relays Following Loss of Unit 2 Startup Transformer ENS 513022015-08-10T02:15:00010 August 2015 02:15:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip During Testing ENS 506072014-11-12T20:48:00012 November 2014 20:48:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to Lowering Steam Generator Water Level ENS 497072014-01-09T23:03:0009 January 2014 23:03:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Severe Rain Storm ENS 495362013-11-14T17:18:00014 November 2013 17:18:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to Low Level in the 2B Steam Generator ENS 483882012-10-08T01:40:0008 October 2012 01:40:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Essential Bus Deenergized While Defueled ENS 483692012-10-03T12:43:0003 October 2012 12:43:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Failure of Startup Transformer Caused Undervoltage Condition on Essential Bus ENS 479152012-05-11T07:55:00011 May 2012 07:55:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to Feedwater Control Valve Failure ENS 476572012-02-10T06:34:00010 February 2012 06:34:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Maintenance Activities Cause an Inadvertent Emergency Diesel Generator Start ENS 469282011-06-06T07:29:0006 June 2011 07:29:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Error During Reactor Protection System Surveillance Leads to Reactor Trip ENS 458432010-04-15T19:39:00015 April 2010 19:39:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unplanned Manual Reactor Trip ENS 453742009-09-21T17:34:00021 September 2009 17:34:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unplanned Manual Reactor Trip During Reactor Startup ENS 449522009-04-01T22:05:0001 April 2009 22:05:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unplanned Manual Reactor Trip ENS 442762008-06-07T12:18:0007 June 2008 12:18:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Following the Trip of a Condensate Pump ENS 439292008-01-24T03:15:00024 January 2008 03:15:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event - Uncontrolled Hydrogen Leak ENS 438742007-12-29T06:31:00029 December 2007 06:31:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip When Five Control Rods Unexpectedly Dropped 20 Inches ENS 420682005-10-23T09:05:00023 October 2005 09:05:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Hurricane Warning ENS 419442005-08-25T03:02:00025 August 2005 03:02:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Hurricane Warning ENS 419112005-08-11T14:48:00011 August 2005 14:48:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip on a Condensate Pump Bus Lockout ENS 417152005-05-19T00:59:00019 May 2005 00:59:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Inadvertent De-Energization of 4160 V Safety Related A.C. Bus with Edg Auto Start ENS 412932004-12-25T11:52:00025 December 2004 11:52:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unit 2 Manually Tripped to Remove Failing Condensate Pump from Service ENS 410722004-09-26T03:56:00026 September 2004 03:56:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Declared Due to a Loss of Offsite Power ENS 410672004-09-24T21:00:00024 September 2004 21:00:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Entered Unusual Event Classification Due to Hurricane Warning in Effect ENS 410062004-09-02T14:43:0002 September 2004 14:43:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notice of Unusual Event Declared ENS 406312004-03-31T23:56:00031 March 2004 23:56:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Reactor Coolant System Leakage Greater than 10 Gpm ENS 404032003-12-20T14:49:00020 December 2003 14:49:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Rps Actuation Due to Loss of Turbine Generator Excitation 2024-07-28T22:37:00 | |