Notice of Violation from Insp on 890717-20.Violation Noted: Failure to Conspicuously Post High Radiation Area,Per Tech Spec Requirement
ML20246D291
Person / Time
Site: Humboldt Bay
Issue date: 08/08/1989
From: Yuhas G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
To:
Shared Package
ML20246D285 List:
References
50-133-89-02, 50-133-89-2, NUDOCS 8908250315
Download: ML20246D291 (2)


Text

_ _ _ - _ _ _

7

'e s l Appendix A Notice of Violation Pacific Gas and Electric Company Docket No. 50-133 Humboldt Bay Power Plant Unit 3 License No. DPR-7

, Dufing an NRC inspection conducted during the period of July 17-20, 1989, one violation of NRC requirements was identified. In'accordance with the " General Statement of Policy and Procedure for NRC Enforcement Actions," 10 CFR Part 2 Appendix C (1988), as modified by Fed. Reg.- 40019 (October 13, 1988), the t violation is: listed below:

A. Technibal Specifications.VII.K.1 states- in part that: " ...eachhihh radiation area as defined in 10 CFR Part 20, in which the intensity of

~

radiation is equal to or less than-1000 mr/hr at 45 cm (18 in.) from the radiation source or from any surface that radiation penetrates, shall be

. . barricaded and conspicuously posted as a high radiation area, and entrance therleto shall be controlled by issuance of special work

/ -

permits...."

. 10 CFR 20.202(b)(2) defines a high radiation area as any area, accessible y to personnel, in which there exists radiation originating.in whole or in

J part within licensed material at such levels that a major portion of the whole body could receive in any one hour a dose of 100 mrem.

Contrary .to'the above, a high radiation area within the number three

, outside storage vault, which contained three drcms of radioactive waste with radiation levels of at least 300 mr/hr at eighteen inches from the surface, was not conspicuously posted.

This is a Severity Level IV Violation (Supplement IV).

Pursuant to the provisions of 10 CFR 2.201, Pacific Gas and Electric Company is hereby required to submit a written statement or explanation to the U.S.

Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington, D.C.

20555, with a copy to the Regional Administrator, Region V, within 30 days of the date of the letter transmitting this Notice. This reply should be clearly marked as a " Reply to a Notice of Violation" and should include for each violation: (1) the reason for the violation, if admitted, (2) the corrective steps that have been taken and the results achieved, (3) the corrective steps that will be taken to avoid further violations, and (4) the date when full

. compliance will be achieved. If an adequate reply is not received within the time specified in this Notice, an order may be issued to show cause why the license should not be. modified, suspended or revcked or why such other action as may be proper should not be taken. Consideration may be given to extending

.the response time for good cause shown.