Technical Specifications for Monticello Generating Plant Regarding Primary Coolant Sources Outside Containment
ML031700542
Person / Time
Site: Monticello Xcel Energy icon.png
Issue date: 06/17/2003
From: Padovan L
NRC/NRR/DLPM/LPD3
To: Denise Wilson
Nuclear Management Co
References
TAC MB8063
Download: ML031700542 (1)


Text

'1 I

B. Primary_lant Sources gutde Coainment This program provides controls to minimize leakage from those portions of systems outside contalnment that could contaln highly radlonctive flulds during a serious transient or accident to levels as low as practicable. The systems Include Core Spray, Hlgh Pressure Coolant Inlection, Residual Heat Removal, Reactor Core Isolatlon Cooling, Combustible Gas Control, process sampling, and Standby Gas Treatment. The program shall Include the following:

1. Preventive maintenance and periodic visual Inspection requirements; and
2. ntegrated leak test requirements for each system at refuellng cyde Intervals or less.

The provislons of Specification 4.O.B are appflcable.

A program acceptable to the Commission was described Ina letter dated December 31, 1979, from L 0 Mayer, NSP, to Director of Nuclear Reactor Regulation, Lessons Leamed Implementation."

C. (Deleted) I 6.8 254 Amendment No. 420,136