05000278/LER-2012-001

From kanterella
Revision as of 11:09, 27 November 2017 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
LER-2012-001,
Peach Bottom Atomic Power Station (Pbaps) Unit 3
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications

10 CFR 50.73(a)(2)(vii), Common Cause Inoperability
2782012001R00 - NRC Website

Unit Conditions Prior to the Event Unit 3 was in Mode 1, operating at 100`/)0 of rated thermal power when this event was discovered. There were no other structures, systems or components out of service that contributed to this event.

Description of the Event

On 4/18/12, Instrument and Controls (I&C) personnel were performing a calibration surveillance test for the 'A' Core Spray Pump (EIIS:P) discharge flow logic switches. During the procedure, the differential pressure indicating switch (DPIS)(EIIS:PDS) 3-14-081A was found to be out of calibration. This switch indicates the difference in pressure between the suction line and the discharge line of the 'A' Core Spray Pump. The difference in pressure is used by the control logic to determine if the minimum flow bypass valve (EIIS:ISV), MO-3-14-005A, should be opened or closed. The switch has two trip setpoints. The high side trip setpoint determines when the bypass valve should open and has a test acceptable range of 341 psi to 349 psi. The low side trip setpoint determines when the bypass valve should close and has a test acceptable range of 321 psi to 329 psi. Technical Specification (TS) allowable range is 319 psi to 351 psi. The surveillance test determined the high side trip setpoint to be 351 psi and the low side trip setpoint to be 317 psi, which is 2 psi below the TS allowable value. The switch was recalibrated in accordance with the procedure and retested to demonstrate that the setpoints were within the acceptable range.

On 4/19/12, the same test was performed on DPIS 3-14-081D, which is the corresponding switch for the `D' Core Spray Pump. The test found the high side trip setpoint to be within tolerance at 346 psi. The low side trip setpoint was found to be out of tolerance low at 266 psi, or approximately 53 psi below the TS allowable value. The switch was successfully recalibrated in accordance with procedure and returned to service.

Both incidents occurred during scheduled surveillance tests and had no significant impact on train outage time. Following recalibration, both switches were returned to an operable status on the day of B' and 'C' Core Spray pumps on 4/18/12 and 4/19/12 and for all four of the Unit 2 Core Spray pumps on 5/1/12 and 5/2/12.

Technical Specification Requirements Technical Specification (TS) Table 3.3.5.1-1, "Emergency Core Cooling System Instrumentation", Function 1.d, provides requirements for the Core Spray Pump bypass valve instrumentation. With one channel inoperable, TS 3.3.5.1 Condition E requires that the channel be restored to operable within 7 days, and, if the redundant ECCS initiation capability is inoperable, the supported feature must be declared inoperable within one hour.

Reportabilitv This report is being submitted pursuant to:

10CFR 50.73(a)(2)(i)(B) — Any operation or condition which was prohibited by the plant's TS, and 10CFR 50.73(a)(2)(vii) — Any event where a single cause or condition caused at least one independent train or channel to become inoperable in multiple systems or two independent trains or channels to become inoperable in a single system.

Based on the amount that DPIS 3-14-081D was out of calibration (53 psi) on 4/19/12, it is likely that it was inoperable on 4/18/12 when DPIS 3-14-081A was out of calibration and inoperable. In addition, a single cause resulted in more than one instrument channel in one system being inoperable.

Analysis of the Event

The Core Spray System consists of two independent trains (subsystems), each with two 50% capacity pumps (four pumps total). Each pump has a minimum flow bypass valve that provides a safety related function for both its opening and closing operations. In the event that less than minimum flow exists through the pump discharge line, the valve opens to prevent overheating and pump damage. This condition could occur in response to a loss of coolant accident (LOCA), when an initiation signal starts the pumps prior to the injection signal. Once an injection signal is received, the bypass valve is required to close to ensure the full design flow to the core is provided.

To detect flow through the pump, a pressure switch detects the differential pressure between the suction and discharge lines of the pump. The switches are Barton Model 580A differential pressure indicating switches (DPIS), currently manufactured by Cameron Measurement Systems. Each DPIS contains two internal switches which actuate at the high and low setpoints. A series of gears, cams and pivots transmit movement from the bellows to the internal switches. Accurate operation of the DPIS requires correct alignment of the internal mechanical components and wear and corrosion can affect reliability of the switches.

The preferred method for corrective maintenance is replacement of the entire pressure switch instead of replacement of worn components or recalibration of the internal switches. Replacement of the entire switch and obtaining replacement parts became increasingly difficult following a change in ownership in 2007 and production of qualified Barton replacement switches was discontinued until 2010. As a result, PBAPS began to place more emphasis on adjustments to the internal components of the switch instead of replacement.

In January 2012, two Barton pressure switches on the Unit 3 Core Spray system were found out of calibration (one 4.6% high and the other 10.6% low). A cause evaluation was performed and a degrading trend in component performance was identified that started in 2008. Several corrective actions were initiated, including switch replacement and improvements in training. Cameron established an environmental qualification program in 2010 and has begun supplying qualified Barton pressure switches. PBAPS has established an expedited procurement and replacement schedule for the Core Spray system. A training and qualification program was established to develop site subject matter experts for Barton pressure switches. The training included a Barton training lab, with a technical representative from Cameron to provide guidance on design and adjustments to the switches.

The out of calibration events described above occurred during normal scheduled surveillance testing.

There were no actual safety consequences associated with this event. In the event of a valid signal, it has been determined that the Core Spray system would still have been able to perform its safety function.

Cause of the Event

The declining trend in performance of Barton pressure switches at PBAPS since 2008 was due to insufficient knowledge and skill by maintenance personnel to effectively troubleshoot and maintain the instruments. Prior to 2008, maintenance personnel would typically have replaced the entire switch.

During the period of time when qualified Barton pressure switches were no longer being manufactured, additional emphasis was placed on adjustments to the internal components of the switch.

In addition, during lab training with a Cameron technical representative, it was determined that the high and low trip setpoints for the switches in the Core Spray system are sufficiently close together such that it can cause setpoint interferences and create additional drag on the cam assemblies. This makes the switches sensitive to wear, increases the potential for setpoint drift and increases the level of knowledge and skill needed to maintain them. It was also identified during the lab training that maintenance procedures did not provide adequate guidance for detecting component failures and to differentiate them from instrument drift.

Corrective Actions

Replacement of the eight Barton pressure switches for the Core Spray pump bypass valves in the Units 2 and 3 Core Spray systems has begun and is being tracked within the corrective action program.

A site training and qualification program has been developed to establish a group of subject matter experts for Barton pressure switches. Also, procedure enhancements have been made to provide improved guidance for troubleshooting.

The site corrective action program is tracking these corrective actions and has evaluated the extent of condition.

Previous Similar Occurrences As stated above, there has been a declining trend in Barton pressure switches for the Core Spray system being out of calibration or failing since 2008. From 1998 to 2007 there were approximately 6 occurrences. From 2008 to present, there have been approximately 8 occurrences. Setpoint drift issues for Barton pressure switches have also been identified as an industry issue (reference NRC Information Notice 86-065).