05000269/FIN-2008003-01
From kanterella
Revision as of 20:38, 28 October 2017 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Finding | |
---|---|
Title | Required Pressure Tests Not Performed |
Description | The inspectors identified a Green non-cited violation (NCV) of 10 CFR 50.55a(g)(4) for the failure to perform periodic leakage testing of Class 1 portions of low pressure injection system during the third inspection interval of the Unit 1 Inservice Inspection Program as required by Section XI of the American Society of Mechanical Engineers (ASME) Code for the third 10-year Inservice Inspection interval. The licensee entered this issue into their Corrective Action Program (CAP) for resolution. This finding is more than minor because it affected the Equipment Performance attribute of the Mitigating Systems Cornerstone objective, in that there were no additional measures taken to perform the required pressure testing (or obtain regulatory relief within the time limits of the regulation) to ensure the availability, reliability, and capability of a system that responds to initiating events to prevent undesirable consequences. This finding is of very low safety significance because it was not a design issue resulting in a loss of operability, did not represent an actual loss of a systems safety function, did not result in exceeding a Technical Specification (TS) allowed outage time, and did not affect external event mitigation. This finding has a cross-cutting aspect of Work Control in the area of Human Performance, as identified in NRC Manual Chapter 0305, Section 06.07 [H.3.(b)]. (Section 1R08.1 |
Site: | Oconee ![]() |
---|---|
Report | IR 05000269/2008003 Section 1R08 |
Date counted | Jun 30, 2008 (2008Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.08 |
Inspectors (proximate) | A Hutto B Collins E Riggs L Lake R Chou R Mackowski S Rose |
CCA | H.5, Work Management |
INPO aspect | WP.1 |
' | |
Finding - Oconee - IR 05000269/2008003 | |||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Oconee) @ 2008Q2
Self-Identified List (Oconee)
| |||||||||||||||||||||||||||||||||||||||||||