Semantic search

Jump to navigation Jump to search
Condition
Printout selection
Options
Parameters [
limit:

The maximum number of results to return
offset:

The offset of the first result
link:

Show values as links
headers:

Display the headers/property names
mainlabel:

The label to give to the main page name
intro:

The text to display before the query results, if there are any
outro:

The text to display after the query results, if there are any
searchlabel:

Text for continuing the search
default:

The text to display if there are no query results
class:

An additional CSS class to set for the table
transpose:

Display table headers vertically and results horizontally
sep:

The separator between results
prefix:

Control display of namespace in printouts
Sort options
Delete
Add sorting condition
 Issue dateTitleTopic
ML19351A4527 December 1989NPDES Noncompliance Notification:On 891201,water Overflowed Through Vented Manhole Upstream of Normal Final Discharge Point Into Possum Hollow Creek Approx 100 Yards Upstream from Schuylkill River.Caused by Procedural Deficiency
ML20005E54321 December 1989NPDES Noncompliance Notification:On 891101 & 17,zinc Samples for Discharge Point 001 Exceeded Permit Limit.Caused by Random Error Such as Sample Contamination or Limitations in Daily Zinc Testing Probably Due to Cold Water Temps
ML20005G98415 January 1990NPDES Noncompliance Notification:On 891227,permit Limit for Zinc Exceeded.Caused by Sampling Inadequacies Rather than Excessive Chemical Discharges.Routine Daily Flushing of Sample Line 001 Performed & Lower Range Control Used
ML20006F54520 February 1990NPDES Noncompliance Notification:On 900129 & 0202,samples Taken Above Permit Limit of 1 Mg/L.Caused by Excessive Amount of Suspended Solids in Makeup Water Due to Extensive Rainfall.Sampling Program Being Explored
ML20024H84419 August 1993NPDES Noncompliance Notification Re Perkiomen Storage Tank Overflow to Possum Hollow Run.Application for Amend to Permit PA0051926 Submitted
ML20044C40516 March 1993NPDES Noncompliance Notification:On 930222,discovered That Contractor Personnel Discharged Treated Water from Fire Hydrant Supplied by Unit 1 Cooling Tower Into Storm Water Drain E-3.2.Caused by Personnel Error.Label Applied
ML20044G76421 May 1993NPDES Noncompliance Notification:From 930417-18,equipment Problems Occurred Which Rendered Dissolved Oxygen & Ph Monitoring Instrumentation Inoperable.Caused by Debris in Sample Line.Methods for Filtering Flow Under InvestigationGrab sample
ML20046B80529 July 1993NPDES Noncompliance Notification:On 930618,20 & 27,water Processing Facility Temp Exceeded Permitted Max Limitation of 74 Degrees F.Caused by Lack of Training & Written Instructions.Training Provided & Addl Instruction IssuedGrab sample
ML20056G39227 August 1993NPDES Noncompliance Notification:On 930710,13,14 & 25, Water Processing Facility (Wpf) Discharge Temp Exceeded Max Limitation of 74 Degrees F.Rev to NPDES Permit,Removing Temp Limits Approved & Wpf Chillers Removed from Svc
ML20058H28726 October 1990NPDES Noncompliance Notification:On 900905,routine Weekly Sample Collected from Holding Pond Exceeded Limits.Caused by Release of Oil from Pond Surface Prior to Discharge Termination
ML20059C49426 October 1993NPDES Noncompliance Notification:On 930907,cooling Tower Blowdown Water Discharged Into Possum Hollow Creek Due to Loss of Two of Four Operating Circulating Water Pumps. Procedures for Performing Excavations Revised
ML20059G45521 August 1990NPDES Noncompliance Notification:On 900715 & 17,five of Seven Samples from Discharge Point 001 Exceeded Limit. Acid Injection Sys Adjusted Immediately & Mod Designed to Automate Acid Feed Sys on Both Units
ML20059M43724 September 1990NPDES Noncompliance Notification:On 900806 & 10,samples of Fecal Coliform from Discharge 001 Exceeded Permit Limit. Caused by Water Processing Facility Not Sufficient to Reduce Number of Colonies
ML20059M43924 September 1990NPDES Noncompliance Notification:On 900822,sample Collected from Discharge Point 001 Exceeded Permit Limit for Zinc. Sample Not Representative of Actual Discharge
ML20064A44121 August 1990NPDES Noncompliance Notification:On 900629,ambient Water Temps Caused Bradshaw Reservoir Pump Trips Due to Equipment Overheating.Similar Temp Transients Caused by Equipment Trips & Power Loss Occurred on 900702,04,05,06,09 & 10Grab sample
ML20064C77025 February 1994NPDES Noncompliance Notification:On 940116 & 17 Manual Reactor Scram Occurred.Caused by Failure to Adequately Throttle Cooling Tower Bypass Valves.Procedure Revised
ML20065B92225 March 1994NPDES Noncompliances Notification:On 940204,discharge 001 Maximum Daily Limit of 1.0 mg/1 Total Zinc Was Exceeded. Caused by Low Ph Transient in Unit 2 Cooling Tower Water Sys.Isolated Acid Injection Sys
ML20065M68129 November 1990NPDES Noncompliance Notification:On 901003,routine Weekly Discharge 001 Sample Exceeded Max Permit Limits for Grease & Oil.Sample Contained 43.7 Mg Per Liter of Oil & Grease. Abnormal Reading Believed to Be Caused by Oily Silt
ML20070S30722 March 1991NPDES Noncompliance Notification:On 910204,discovered That Misalignment of Diverter Valve to Outfall 003 May Have Allowed Mixture of Storm Water & Steam Condensate to Be Released from Outfall.Valve Repositioned
ML20071L17627 July 1994NPDES Noncompliance Notification:On 940609,zinc Analyses Indicated That Discharge 001 Total Zinc Levels in Excess of Max Daily Limitations in Both Cooling Towers.Daily Zinc Control Limits Will Be Administratively Maintained Lower
ML20072R46031 August 1994NPDES Noncompliance Notification:On 940708 & 0815,Discharge 001 Total Zinc Concentrations Exceeded Max Daily Limitations.Daily Zinc Trending Analysis Will Be Upgraded & Chemistry Technician Involved in 940815 Event CounselledGrab sample
ML20077D87017 May 1991NPDES Noncompliance Notification:On 910512,cooling Tower Experienced Failure,Causing Large Vol of Cooling Tower Water to Bypass Normal Blowdown Discharge Pathway.Cooling Tower Will Be Inspected During mid-yr Outage
ML20077G57720 June 1991NPDES Noncompliance Notification:On 910528,chiller C at Bedminster Water Processing Facility Tripped Due to High Vibration & Temp at Discharge 001 Exceeding Permitted Instantaneous Temp.Discharge Temp Setpoint Lowered
ML20082L98728 August 1991NPDES Noncompliance Notification:On 910707 & 19,electrical Storm Caused Loss of Power to Bedminster Water Processing Facility & Tripped Chillers.On 910721,discharge Temp Exceeded Permitted Limits.Permit Limits Changed
ML20086E49822 November 1991NPDES Noncompliance Notification:On 911016 Underground Fire Water Pipeline Inadvertently Punctured by Contractor Backhoe Ram During Excavation of Trench.Caused by Inadequate Review of Required Prints.Backhoe Ram Operator Terminated
ML20091Q43023 January 1992NPDES Noncompliance Notification:On 911218 Cooling Tower Blowdown Water Discharged to Possum Hollow Creek Resulting in Unpermitted Discharge Due to Failure to Identify & Revise All Appropriate Procedures.Procedure GP-3 to Be Revised
ML20095J12023 April 1992NPDES Noncompliance Notification:On 920322,cooling Tower Blowdown Water Discharged Into Possum Hollow Creek.Caused by Procedure Deficiency.Sys Operating Procedure S09.4.A Expected to Be Revised by 920501
ML20100P63128 February 1996NPDES Noncompliance Notification:On 951108,discharge 001 Net TSS in Excess of Maximum Daily Limit.Caused by Flaw in Methodology to Calculate Net TSS concentration.Follow-up Composite Samples TakenGrab sample
ML20101H53226 June 1992NPDES Noncompliance Notification:On 920504,crack Discovered on Above Ground Cleanout for Sewage Line Leading from Plant Training Ctr to Plant Sewage Sys Holding Tanks.Caused by Expansion of Sewage Spill Line.Clamps Installed
ML20101K46628 March 1996NPDES Noncompliance Notification:On 960218,discovered That No Records Existed for Bradshae Reservoir Discharge Water Temp for Listed Time Periods.Caused by Temporary Reassigment of Personnel.Review of Staffing in Progress
ML20108A36728 April 1996NPDES Noncompliance Notification:On 960314,personnel Observed Sewage Overflowing from MH-07 & Into Storm Drain W-4.Caused by Blockage of Pipe Section Between MH-07 & MH-08.Sewer Contract Svc Pressure Cleaned
ML20108A38028 April 1996NPDES Noncompliance Notification:On 960223,identified Seven Issues of Administrative non-compliance/ambiguity W/Permits. Caused by Inadequate Administration.Individuals Gained Better Understanding W/Guidance
ML20113C44524 June 1996NPDES Noncompliance Notification:On 960318,flow Integrator Used to Measure Spray Pond Effluent Flow Declared Inoperable.Caused by Faulty Flow Integrator.Frequency of Use of Instrument Changed to Daily as Stated in Issue Number
ML20115G11512 July 1996NPDES Noncompliance Notification:On 960619,resulting Net TSS Value 82.8 mg/1,exceeded Max Daily Limit of 60 Mg/L.Caused by Excessive Storm Water Runoff.Net TSS RevisedGrab sample
ML20116B38524 July 1996NPDES Noncompliance Notification:On 960602 Identified Ph Levels Exceeded NPDES Permit Limitations.Caused by Natural Biological activity.CO2 Injection Established,Maintained & Monitored Until 960612
ML20117A57623 November 1992NPDES Noncompliance Notification:On 921013 & 14,four of Five Samples Collected from Discharge Point 001 Exceeded Daily Max Permit Limit of 1.0 Mg/L.Caused by Heavy Rains Across Southeastern PA on 921009.Injection Rates Decreased
ML20117G70723 August 1996NPDES Noncompliance Notification:On 960715,geometric Mean of Fecal Coliform Concentration Exceeded NPDES Permit Limit. Caused by Leaking Seals on Ozone Diffusers.Temporary Adjustments Made to Ozone Gas Flow BalanceGrab sample
ML20126G99924 December 1992NPDES Noncompliance Notification:On 921104,dissolved Oxygen Monitoring Equipment at Bradshaw Reservoir Discharge & Water Processing Facility Became Fouled by Organic Concentrations. Caused by Heavy Rainfall.Manual Samples Will Be Obtained
ML20126J07629 May 1985NPDES Noncompliance Notification:On 850522,approx 300 Gallons Water W/Ph Between 9.0 & 9.5 Discharged from Point 004.Caused by Sulfuric Acid Cleanup.Personnel Counseled & Pollution Incident Protection Procedure Being DevelopedGrab sample
ML20128A50725 January 1993NPDES Noncompliance Notification:On 921117 & 25,analytical Results for inductively-coupled Plasma Analyzer at Discharge Point 001 Exceeded Zinc Concentration.Total Zinc Concentration Analysis Will Be Performed Onsite
ML20128N12517 February 1993NPDES Noncompliance Notification:On 930103,cooling Tower Blowdown Water Overflowed from Discharge 001 Pipeline & Flowed Into Possum Hollow Creek.Caused by Failure to Throttle Unit 2 Bypass Valves.Procedure Changed
ML20129E54126 September 1996NPDES Noncompliance Notification:On 960812,discharge Observed from Unit 2 Cooling Tower Overflow to Outfall 021. Caused by Personnel Error in Performing Required Analysis of Cooling Tower Overflow Sample.Individual Counseled
ML20129E56827 September 1996NPDES Noncompliance Notification:On 960805,geometric Mean of Fecal Coliform Concentration Calculated to Be 641 Colonies Per 100 Ml.Cause Suspected to Be Due to Malfunctioning Ozone Disinfection Sys.Adjustments to Sys Have Been MadeGrab sample
ML20134E06428 October 1996NPDES Noncompliance Notification:During Month of Sept 1996, NPDES Limit for Fecal Coliform Concentration at Discharge of Bradshaw Reservoir Pumps Was Not Met.Caused by Leaking Gaskets on Ozone Gas Diffusers.New Gaskets,InstalledGrab sample
ML20134G32431 January 1997NPDES Noncompliance Notification:On 970108,util Informed NRC That PA Dept of Environ Protection Granted Approval for Temporary Discharge at Lgs,Per 961219
ML20134K4431 August 1985NPDES Noncompliance Notification:On 850707,fecal Coliform Colony Count of Sample from Discharge Point 101 (Sewage Treatment Plant) Exceeded Limits.Caused by Pump Losing Suction Due to Tubing Floating to Surface
ML20135A58527 November 1996NPDES Noncompliance Notification:On July-Sept 1996 Re NPDES Limit for Fecal Coloform Concentration Not Met.Caused by Inadequate Gasket Installation.Ozonators Overhauled to Ensure Peak PerformanceGrab sample
ML20137M55127 March 1997NPDES Noncompliance Notification:On 970228,flow Integrator Used to Measure Spray Pond Effluent Flow Was Identified to Be Malfunctioning & Declared Inoperable Due to Lodged Debris.Revised Procedure for Spray Pond Effluent Flow
ML20137Y13426 November 1985NPDES Noncompliance Notification:On 851031,fecal Coliform Colony Count of Monthly Sample from Discharge Point 101 Exceeded Monthly Average Permit Limit.Caused by Failure of Hypochlorite Pump to Maintain Adequate Flow to Contact Tank
ML20138G96524 December 1996NPDES Noncompliance Notification:On 960428,calibration of Flowmeter Used to Measure Spray Pond Flow Was Not Checked on Routine Basis Because Person Required to Develop Maint Was Unaware of Requirements.Installed New Meter