Semantic search

Jump to navigation Jump to search
Condition
Printout selection
Options
Parameters [
limit:

The maximum number of results to return
offset:

The offset of the first result
link:

Show values as links
headers:

Display the headers/property names
mainlabel:

The label to give to the main page name
intro:

The text to display before the query results, if there are any
outro:

The text to display after the query results, if there are any
searchlabel:

Text for continuing the search
default:

The text to display if there are no query results
class:

An additional CSS class to set for the table
transpose:

Display table headers vertically and results horizontally
sep:

The separator between results
prefix:

Control display of namespace in printouts
Sort options
Delete
Add sorting condition
 Issue dateTitleTopic
ML18004B98730 August 1979Ro:On 790829,svc Water Booster Pump a Tripped When Svc Water Booster Pump B Was Stopped,In Violation of Tech Specs 3.3.4.1.a.Power Reduction Initiated & Svc Water Booster Pumps Returned to Svc
ML19317D4681 May 1973Ro:On 730423,water Spill from Refueling Water Storage Tank to Storm Drainage Sys.Caused by Inadequate Procedures & Personnel Error.Plant Mgt Will Review Methods & Have Cautioned Operators to Exercise Extreme Caution
ML19341B27415 January 1981Ro:On 810114,both Channels of Heat Trace for Both Boric Acid Transfer Pumps Determined Inoperable in Violation of Tech Spec 3.2.3.C.Caused by Misleading Step in Procedure for Taking Pump Out of SvcBoric Acid
ML20009H57722 July 1981Ro:On 810608,fire Barrier Penetration Fire Seals Found in Nonconformance W/Approved Configuration Requirements. Deficiencies Occurred During Mod 445-N Implementation.Seals Will Be Repaired During Refueling OutageSafe Shutdown
Fire Barrier
ML20009H68930 July 1981Nonroutine 30-day Rept:On 810623,fire Door 5 Opened to Relieve Excessive Heat from Auxiliary Feedwater Pump Room. Heat Caused by Backleakage Combined W/Hot Temp & Lack of Ventilation.Repairs Scheduled for Fall Refueling OutageFire Barrier
ML20028F39319 January 1983Ro:On 821220,reactor Trip Circuit Breaker a Failed to Trip When Trip Signal Initiated.Caused by Sticking Undervoltage Relay.Relay Replaced.Contacts Cleaned
ML20038B5003 December 1981Ro:On 811201,pressurizer Block Valves Found to Not Meet Design Specs of Closing Against Design Pressure.Caused by Undersized Motor Operator Which Will Not Develop Sufficient Torque to Shut Block Valve
ML20038C7962 December 1981Ro:On 811201,discovered Pressurizer Block Valves Did Not Meet Design Spec in That They May Not Close Against Design Pressure.Caused by Undersized Limitorque Operator Model SMB-000-5
ML20039F60828 December 1981Ro:On 811228,review of Info Re Reactor Vessel Matl Surveillance Program Revealed Calculational Error in Analyses Used to Update Heatup & Cooldown Curves.Unrevised Tech Spec Figures 3.1-1 & 3.1-2 Remain Conservative