Responds to NRC 961223 Ltr Re Violations Noted in Insp Rept 50-335/96-17.Corrective Actions:Fpl Has Adopted Policy of Verbatim Compliance with Procedural Instructions at St Lucie Plant
ML17229A211
Person / Time
Site: Saint Lucie NextEra Energy icon.png
Issue date: 01/28/1997
From: PLUNKETT T F
FLORIDA POWER & LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
L-97-016, L-97-16, NUDOCS 9702030207
Download: ML17229A211 (13)


See also: IR 05000335/1996017

Text

CATEGORY1REGULATORYINFORMATIONDISTRIBUTIONSYSTEM(RIDS)ACCESSIONNBR:9702030207DOC.DATE:97/01/28NOTARIZED:NOACIL:50-335St.LuciePlant,Unit1,FloridaPower&LightCo.AUTEUR.NAMEAUTHORAFFILIATIONLUNKETT,T.F.FloridaPower6LightCo.RECIP.NAMERECIPIENTAFFILIATIONDocumentControlBranch(DocumentControlDesk)SUBJECT:RespondstoNRC961223ltrreviolationsnotedininsprept50-335/96-17.Correctiveactions:FPLhasadoptedpolicyofverbatimcompliancewithproceduralinstructionsatStLucieplant.DISTRIBUTIONCODE:ZEOZDCOPIESRECEIVED:LTRiENCLtSIZE:l0TITLE:General(50Dkt)-InspRept/NoticeofViolationResponseNOTES:DOCKETI05000335ERECIPIENTIDCODE/NAMEPD2-3PDINTERNAL:ACRSNRR/DRPM/PERBOEDIRRGN2FILE01TERNAL:LITCOBRYCEPJHNRCPDRCOPIESLTTRENCL11221111111111111111RECIPIENTIDCODE/NAMEWIENS,L.AEOD/SPD/RABDEDRONRR/DISP/PIPBNRR/DRPM/PECBNUDOCS-ABSTRACTOGC/HDS3NOACCOPIESLTTRENCL1111111111111111DNNOTETOALL"RIDS"RECIPIENTS:PLEASEHELPUSTOREDUCEWASTE!CONTACTTHEDOCUMENTCONTROLDESK,ROOMOWFNSD-5(EXT.4l5-2083)TOELIMINATEYOURNAMEFROMDISTRIBUTIONLISTSFORDOCUMENTSYOUDON'TNEED!TOTALNUMBEROFCOPIESREQUIRED:LTTR19ENCL19

r.<

FloridaPowersLightCompany,i.u.Box128,FortPierce.FL34954-0120@PLJanuary28,1997L-971610CFR2.201U.S.NuclearRegulatoryCommissionAttn:DocumentControlDeskWashington,D.C.20555Re:St.LucieUnit1DocketNo.50-335ReplytoaNoticeofViolationFloridaPowerandLightCompanyhasreviewedthesubjectNoticeofViolationand,pursuantto10CFR2.201,theresponsestotheviolationsareattached.ThesubjectinspectionreportwasdatedDecember23,1996,witharesponsetotheNoticeofViolationrequiredwithin30daysofthatdate,i.e.,byJanuary22,1997.FPLreceivedIntegratedInspectionReportNo.96-17onDecember30,1996.ThesevendaydelayinthereceiptoftheinspectionreportandNoticeofViolationbyFPLwasdiscussedwithCaudleA.Julian(USNRC/RegionIQandEdwardWeinkam(FPL)onJanuary9,1997.InaccordancewiththeresponsereliefdiscussedintheNoticeofViolation,Mr.Juliangrantedanextensiontotherequiredresponsedate.Verytrulyyours,T.F.PlunkettPresidentNuclearDivisionTFP/JAS/EJWAttachmentcc:RegionalAdministrator,USNRC,RegionIISeniorResidentInspector,USNRC,St.LuciePlant9702030207970%28PDRADOCK050003358PDRanFPLGroupcompany

L-97416AttachmentTechnicalSpecification6.8.1.a,requiresthatwrittenproceduresshallbeestablished,implementedandmaintainedcoveringtheactivitiesrecommendedinappendixAofRegulatoryGuide1.33,Revision2,February1978.AppendixA,paragraph7ofRG1.33requiresproceduresforcalibrationofarea,process,portableandairborneradiationmonitors.I&CProcedureNo1-1220053,"CalibrationoftheControlRoomOutsideAirIntakeMonitors,"Rev2,datedSeptember15,1994,providesinstructionsforcalibratingthecontrolroomoutsideairintakeradiationmonitors.Step7.1ofI&CProcedureno1-1220053,statesacompletedcopyofthisprocedureshallbemaintainedintheplantfilesinaccordancewithQI17-PR/PSL-1,"QualityAssuranceRecords."Step7.2statesacopyoftheassayreportfortheradiationchecksourcesanddatasheetsassociatedwiththisprocedureshouldberetainedandincludedasacalibrationpackageuponcompletion.Step9.3.10,ofI&CProcedureNo1-1220053,required,inpart,thatifthehighvoltageisadjustedmorethan50volts,oranewdetectorisinstalledorifmonitorcannotbeadjustedtowithinJ10%tolerancegotostep9.4NewCalibration.Step9.4,ofI&CProcedureNo1-1220053,describedtheprocessforperformingaprimarycalibrationandrequired,inpart,theperformanceofahighvoltageplateaufordeterminingoperatingvoltageforthedetector.TheprocedurealsorequiredtheintroductionofknownradioactivegasinvariousactivitylevelstodevelopanefficiencycurveinpCi/ccvscpmforthenewdetector.Atleast4pointswererequiredonthegraph.Contrarytotheabove,onApril11,1995,thelicenseereplacedthedetectorfortheUnit1RE-26-47ControlRoomOutsideAirIntakeMonitorandfailedtoadequatelyperformtheprimarycalibrationinaccordancewithI&CProcedureNo1-1220053,inthat;thelicenseefailedtodevelopanefficiencycurvewithatleastfourcalibrationpointsofknownquantitiesofradioactivematerialasrequiredbystep9.4oftheprocedure;andthelicenseefailedtomaintaincalibrationdocumentationasrequiredbysteps7.1and7.2ofprocedure.

'-97-016turb~snt>nlv"ak~tirpn'En(ntinnThisisaSeverityLevelIVviolation(SupplementIV)applicabletoUnit1only.1.FPLconcurswiththeviolation.2.ThecauseoftheviolationwaspersonnelerroronthepartofautilityInstrumentandControl(1&C)Technicianwhofailedtostrictlyadheretoanapprovedplantprocedure(1-1220053)requiringtheperformanceanddocumentationofaprimarycalibrationoftheControlRoomOutsideAirIntakeRadiationMonitor(RE-26-47).Thetechniciandidnotdemonstrateathoroughawarenessoftheimportanceandthespecificrequirementsrelatedtotheimplementationofthecalibrationprocedure.A.Sincethetimeofthisviolation(April1995)FPLhasadoptedapolicyofverbatimcompliancewithproceduralinstructionsatSt.LuciePlant.ThepolicyappliestoallplantpersonnelandiscurrentlyincorporatedintheSt.LuciePlantQualityInstructions.B.TheControlRoomOutsideAirIntakeMonitor(RE-26-47)wasremovedfromserviceonJanuary6,1997,pendingtheperformanceofaprimarycalibrationoftheinstrument,andaredundantchannel(RE-26-46)wasselectedforuse.C.AprimarycalibrationwasperformedusingrevisedI&CProcedure1-1220053,andafunctionaltestwascompletedforControlRoomOutsideAirIntakeMonitorRE-26-47.ThemonitorwasreturnedtoserviceonJanuary21,1997.4.A.ThecurrentsitephilosophyregardingverbatimcomplianceandproceduraladherencewasreinforcedtotheI&Cpersonnelinvolvedinthisevent,whichactuallyoccurredinApril1995.B.Sincethetimeofthisviolation(April1995)FPLhasimplementedseveralkeyactionstoimprovepersonnelperformance,includingprocedureadherence,atSt.LuciePlant.Theseactionshaveincludedincreasedmanagementoversight,

L-97-016Attachmentreinforcementofmanagementexpectationsatthesupervisorylevel,anddevelopmentofguidelinesforassessingandimprovingemployeeperformance.FPLiscontinuingtoreinforcehighstandardsofpersonalaccountability,includingproceduraladherence,toplantpersonnelatSt.Lucie.C.ThisviolationwillbeincorporatedintotheeventstrainingprogrammaterialsforSt.Luciemaintenancepersonneltoreinforcetheexpectationforverbatimprocedurecomplianceandtheimportanceofmaintainingdocumentationasrequiredbyprocedures.ThisactionwillbecompletedbyMarch31,1997.5.FullCompliancewasachievedonJanuary21,1997,withthecompletionofItem3C,above.TechnicalSpecification6.8.1.a,requiresthatwrittenproceduresshallbeestablished,implementedandmaintainedcoveringtheactivitiesrecommendedinappendixAofRegulatoryGuide1.33,Revision2,February1978.AppendixA,paragraph7ofRG1.33requiresproceduresforcalibrationofarea,process,portableandairborneradiationmonitors.ISAACProcedureNo1-1220053,"CalibrationoftheControlRoomOutsideAirIntakeMonitors,"Rev2,datedSeptember15,1994,providesinstructionsforcalibratingthecontrolroomoutsideairintakeradiationmonitors.Contrarytotheabove,theprocedureforcalibratingthecontrolroomoutsideairintakeradiationmonitorswasinadequate,inthat,onApril11,1995,theproceduredidnotprovidesufficientguidanceforthedocumentationofinstrumentcalibration.Thecalibrationrecordsnecessarytoprovidesufficientdocumentationtodemonstratethataprimarycalibrationhadbeenperformedwerenotclearlyspecifiedbytheprocedure.ThisisaSeverityLevelIVviolation(SupplementIV)applicabletoUnit1only.1~FPLconcurswiththeviolation.

I97-016Attachment2.Thecauseoftheviolationwaspersonnelerror,inthatsufficientguidanceregardingrequireddocumentationrecordswasnotincorporatedduringtheoriginaldevelopmentofProuxiure1-1220053,"CalibrationoftheControlRoomOutsideAirIntakeMonitors,"whichwaswrittenin1989.Specifically,highvoltageandprimarycurveplotswerenotproperlyidentifiedasrecordswhichwererequiredtobemaintainedfollowingtheperformanceofaprimarycalibrationonthisinstrumentation.3.A.I&CProcedure1-1220053,"CalibrationoftheControlRoomOutsideAirIntakeMonitor's"wasrevisedtomoreclearlyspecifytherequirementsformaintainingsufficientdocumentationasarecordwhenaprimarycalibrationhasbeenperformed.TheprocedurechangewasapprovedonJanuary10,1997.B.TheControlRoomOutsideAirIntakeMonitor(RE-26-47)wasremovedfromserviceonJanuary6,1997,andaredundantchannel(RE-26-46)wasselectedforuse.AprimarycalibrationwassubsequentlyperformedusingrevisedI&Cprocedure1-1220053andthemonitorwasreturnedtoserviceJanuary21,1997.4.A.FPLhasidentifiedseveraladditionalproceduresforreviewwhicharecurrentlybeingusedbyI&Ctocalibrateandfunctionallytestradiationmonitoringinstrumentation.Theseprocedureswillbereviewedtoensurethatproperguidanceisincludedtodescribethedocumentationrequiredtobemaintainedasaqualityrecord.ThisactionwillbecompletedbyFebruary28,1997.B.RecentselfassessmentactivitiesperformedbyFPLhaveidentifiedthatproceduralimprovementsarenecessarytoimprovethelevelofdetailprovidedinplantprocedures.FPLhasinitiatedactionstoaddresstheweaknesseswhichwereidentifiedbytheaboveselfassessmentandtoensurethatcurrentprocedureupgradeinitiativesareadequatelysupported,staffedanddirected.5.FullcompliancewasachievedJanuary10,1997,withthecompletionofItem3A,above.

L-97-016Attachment5lialatioiijTechnicalSpecification6.3.1stateseachmemberoftheunitstaffshallmeetorexceedtheminimumqualificationsofANSI/ANS-3.1-1978.TechnicalSpecification6.4.1statesaretrainingandreplacementtrainingprogramfortheunitstaffshallbemaintainedunderthedirectionoftheTrainingManagerandshallmeetorexceedtherequirementsandrecommendationsofSection5.5ofANSUANS-3.11978and10CFRPart55andthesupplementalrequirementspecifiedinSectionsAandCofEnclosure1oftheMarch28,1980NRClettertoalllicensees,andshallincludefamiliarizationwithrelevantindustryoperationalexperience.LicenseeprocedureQI2-PR/PSL-2,"IndoctrinationandTrainingofStLuciePlantPersonnel,"revision23,datedOctober23,1996,statestheinstructionshallapplybutnotbelimitedtotraininginseveralgeneralareas,including6.0JobSpecificTechnicalTraining.Section4.1,statestheTrainingManagershallberesponsibletothePlantGeneralManagerfortheestablishmentandcoordinationoftrainingactivitiesasrequiredbySt.LuciePlantTechnicalSpecifications,Section6.4andasrequiredtomeetregulatory'equirements.Section4.3.2statesthatdepartmentheadsshallberesponsibleforapprovingdepartmentpersonnelqualificationstandards,appropriateforthedutiestobeperformed.Section4.3.3statesthatDepartmentHeadsshallensurethatpersonnelperformingactivitiesaffectingqualityreceivedepartmentaltrainingcommensuratewiththeworkperformedpriortoperformingthoseactivitiesorareperformingthoseactivitiesunderthesupervisionofatrainedindividualuntiltherequiredtrainingiscomplete.Contrarytotheabove,onJuly1,1996,licenseepersonnelassignedI&CpersonneltheresponsibilitiestocalibrateUnit1plantradiationmonitoringinstrumentationutilizedtoperformcertainplantprocesscontrols,radiologicalmonitoringandcontinuouseffluentmonitoringfunctionsthatwerenotfullytrainedandqualifiedtoperformthosefunctionsinaccordancewiththelicenseestrainingprogram.ThisisaSeverityLevelIVviolation(SupplementIV)applicabletoUnit1only,

L-97-016Attachment1.FPLconcurswiththeviolation.2.ThecauseofthisviolationwastheineffectivetransferofaccountabilityfortheUnit1radiationmonitoringinstrumentationfromChemistryandHealthPhysicsDepartmentstotheI&CDepartmentpriortoensuringthattheaffectedI&Cpersonnelhadcompletedallappropriatetrainingqualifications.TrainingforthesubjectI&CpersonnelhadbeenscheduledtobeimplementedandwaspostponedbytheI&Csystemsupervisorduetoworkpriorities.AsubsequentverificationwasnotmadebyI&Csupervisiontoverifythatpersonnelhadbeenfullytrainedpriortoreceivingresponsibilityfortheaboveinstrumentation.A.ArevisedschedulewasimplementedforthecompletionofthespecifictrainingandqualificationrequiredforI&Cpersonnelresponsibleforperformingradiationmonitorcalibrationandtesting.TheabovetrainingforthesepersonnelwillbecompletedbyMarch31,1997,followingareviewoftheassociatedI&Cprocedures.B.Asupervisor'smeetingwasheldbytheI&CDepartmentheadtoaddressandemphasizetherequirementsforobtainingpriordepartmentheadapprovalofchangestoscheduledtrainingandensuringthatallpersonnelareproperlyandcurrentlytrainedtoperformthetaskswhichtheyareassigned.I&Cpersonnelperformingradiationmonitoringcalibrations,andfunctionalcheckswererequiredtoworkunderadditionalsupervisoryoversightpendingthecompletionoftheappropriatequalificationtraining.C.AppropriateTrainingpersonnelwerecounseledontheimportanceofinformingmanagementwhentrainingorqualificationrequirementsarenotbeingadequatelymet.4.A.TherequiredtrainingandqualificationofI&Cpersonnelresponsibleforperformingcalibrationandtestingofradiationmonitoringinstrumentationwill

L-97-016AttachmentbecompletedbyMarch31,1997.Additionalsupervisoryoversightisbeingprovideduntiltheabovetraininghasbeencompleted.B.St.LucieTrainingDepartmentimplementedaprograminwhichthemanagersofeachdepartmentareinformed,onaweeklybasis,oftrainingwhichisscheduledfortheirpersonnel.Aspartofthisprocess,weeklyattendanceispresentedtothedepartmentmanagers,whoarenotifiedofanyindividualswhohavenotattendedthescheduledtraining.C.TheSt.LucieMaintenanceManagerrequiredthatdepartmentheadsreviewandconcurwithanychangestoscheduledtrainingandensurethatpersonnelintheirdepartmentsarefullyqualifiedtoperformthetaskswhichtheyhavebeenassigned.D.TrainingDepartmentguidelinesandadministrativerequirementswillbeenhancedtorequirethatqualificationtrainingbecompletedforindividualswhoareperformingnewtasks,andtobetterdefinetheresponsibilityforensuringthattrainingisachievedpriortothetransferoftaskaccountability.ThisactionwillbecompletedbyMarch31,1997.E.ArecentFPLself-assessmentinitiativerecognizedthatthetransferofresponsibilitiesatSt.Luciewasnotalwaysproperlyevaluatedpriortoimplementingsiteorganizationalchanges.FPLhassinceinitiatedactiontoaddresstheweaknessesidentifiedinthe"ChangeManagement"processatSt.Lucieandensurethattheimpactoffutureorganizationalchangeisproperlyassessed,sothatthedefinitionofresponsibilities,adequatetraining,andresourcesareinplacepriortoimplementingsuchchanges,5.FullcompliancewillbeachievedbyMarch31,1997,withthecompletionofthetrainingdescribedinItem4A,above.TechnicalSpecification6,8.1.arequiresthatwrittenproceduresbeestablished,implemented,andmaintainedcoveringtheactivitiesrecommendedinAppendixAofRegulatoryGuide1.33,Revision2,February,1978.AppendixA,paragraphl.dincludesadministrativeproceduresforproceduraladherence.ProcedureQI5-PR/PSL-1,Revision73,"Preparation,Revision,Review/ApprovalOfProcedures,"section5.14.1requiresverbatimcompliancetoproceduresbyallpersonnel.

0L-97-016AttachmentOperatingSurveillanceProcedure64.01,Revision16,"ReactorEngineeringPeriodicTests,ChecksandCalibrations,"Appendix7,"ReactivityDeviationFromDesign,"requiredthatreactivitydeviationresultsbedocumentedintheUnit1PlantPhysicsCurveBook,FigureB.3,"ReactivityDeviationLog,"uponcompletionofthedeterminationofreactivitydefect.Contrarytotheabove,thereactivitydeviationcalculationperformedonOctober8,1996,wasnotdocumentedintheUnit1PlantPhysicsCurveBook.ThisresultedinoperatorsusinganincorrectreactivitydeviationintwoShutdownMarginVerificationsperformedonOctober31andNovember1,1996.ThisisaSeverityLevelIVviolation(SupplementI)applicabletoUnit1only.Bespot&1.FPLconcurswiththeviolation.2.ThecauseoftheviolationwaspersonnelerroronthepartofReactorEngineeringpersonnelwhofailedtoupdatetheUnit1PlantPhysicsCurveBookinaccordancewithproceduralrequirementsfollowingperformanceofamonthlysurveillance.TheprocedureviolationoccurredwhenthePlantPhysicsCurveBookwasnotimmediatelyupdatedwiththecurrentdataafterthereactivitydeviationvaluewascalculatedasrequiredbyOperatingSurveillanceProcedure(OSP)64.01.TheReactorEngineerperformingthesurveillancefailedtoexecuteproperfollow-upandverifythatthedatawasproperlyrecordedinthePlantPhysicsCurveBookpriortoclosingthecorrespondingsurveillanceprocedure.3.A.AConditionReport(CR)waswrittenonNovember5,1996,toevaluatethecauseoftheeventandtodeterminetheappropriatecorrectiveactions.B.TheUnit1ControlRoomplantphysicsdatawasupdatedtoreflectthecurrentvalueforreactivitydeviation,inaccordancewithprocedure,followingdiscoveryoftheaboveconditiononNovember5,1996.C.AreviewofthePlantPhysicsCurveBooksforbothSt.LucieUnits1and2

I97-016AttachmentBepLytomHoticeafYialatianwasperformedtoensurethatnoadditionalmissingdataexisted.Noothermissingdatawasidentifiedduringthereview.4,A.ReactorEngineeringperformedaselfassessmentoftheprocessinplaceforupdatinginformationinthePlantPhysicsCurveBooks.Asaresultofthisassessment,adetailedverificationchecklistwasdevelopedforuseinperformingthePlantPhysicsCurveBookupdates.B.TheReactorEngineeringScheduleofPeriodicTestsandReports,AP-0010127,wasrevisedtorequirethataweeklyreviewofthePlantPhysicsCurveBookbeperformedtoverifythatreactorphysicsdatacontainedinthebookarecurrent.C.AmeetingwasheldwiththeresponsibleReactorEngineeringpersonnel,thePresidentoftheNuclearDivisionandtheVicePresidentofNuclearEngineeringtodiscussthiseventandtheexpectationsofFPLmanagementwithregardtopersonnelperformance.D.ThepersonnelinvolvedinthefailuretoproperlyupdatethereactivitydeviationinformationreceivedappropriatedisciplinaryactioninaccordancewithFPLpolicy.5.FullcompliancewasachievedonNovember5,1996,withthecompletionofItem3B,above.