05000327/FIN-2011002-02
From kanterella
Revision as of 19:42, 20 February 2018 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Finding | |
---|---|
Title | \\\"Failure to Adequately Qualify Molded-Case Circuit Breakers to Safety-Related
Application Through Commercial Grade Dedication\\\" |
Description | The inspectors identified a non-cited violation of 10 CFR 50, Appendix B, Criterion III, Design Control, for the licensees failure to assure that appropriate quality standards were specified and included in design documents and that deviations from such standards were controlled. Specifically, the licensee failed to ensure that the molded case circuit breakers utilized in the station 120VAC vital instrument power boards were properly seismically qualified for their application. The licensee entered this issue into their corrective action program as PERs 264271, 266599, 286156, and 319161. Corrective actions included revision of applicable procedures to perform re-alignment of breakers in the vital instrument power boards. The finding was determined to be greater than minor because it was associated with the design control attribute of the mitigating systems cornerstone and affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the failure to ensure that the 120VAC vital instrumentation board components had proper seismic qualification had the potential to affect the ability of safety-related equipment to perform its required function under design basis conditions. Using Inspection IMC 0609, Significance Determination Process, Attachment 4, Phase 1 - Initial Screening and Characterization of Findings, the finding was determined to have very low safety significance (Green) because it did not represent an actual loss of safety function. No cross-cutting aspect was identified, since the issue was determined to not reflect current licensee performance. |
Site: | Sequoyah |
---|---|
Report | IR 05000327/2011002 Section 1R15 |
Date counted | Mar 31, 2011 (2011Q1) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.15 |
Inspectors (proximate) | R Rodriguez E Guthrie P Higgins C Young M Speck J Montgomery W Deschaine |
INPO aspect | |
' | |
Finding - Sequoyah - IR 05000327/2011002 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Sequoyah) @ 2011Q1
Self-Identified List (Sequoyah)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||