Line 16: Line 16:
| event date = 01/10/2004 13:00 EST
| event date = 01/10/2004 13:00 EST
| last update date = 01/10/2004
| last update date = 01/10/2004
| title = Ts Required Shutdown At Nmp1 Due To Inoperable Msiv
| title = Ts Required Shutdown at Nmp1 Due to Inoperable Msiv
| event text = During the performance of a normal orderly planned shutdown for maintenance a packing leak was discovered on Main Steam Inboard Isolation Valve 01-02 (01-02). Drywall inspection results revealed MSIV 01-02 operator gear housing degraded allowing grease to be lost. Engineering assessment of the condition of the limitorque operator of MSIV 01-02 is not able to provide enough information to support operability of MSIV 01-02. Declaring MSIV 01-02 inoperable. Entering T.S. 3.2.7(b and c). Action required to close one valve in the line having an inoperable valve or initiate a normal orderly shutdown with in one hour and be in cold shutdown within ten hours. Entering T.S. 3.3.4(b and c). Action required to close one valve in the line having an inoperable valve within four hours or reduce reactor coolant temperature to a value less than 215 degrees F within ten hours. Most limiting action required in current condition is 10 hours to be in cold shutdown. 01-02 will be closed as soon as all rods are in.
| event text = During the performance of a normal orderly planned shutdown for maintenance a packing leak was discovered on Main Steam Inboard Isolation Valve 01-02 (01-02). Drywall inspection results revealed MSIV 01-02 operator gear housing degraded allowing grease to be lost. Engineering assessment of the condition of the limitorque operator of MSIV 01-02 is not able to provide enough information to support operability of MSIV 01-02. Declaring MSIV 01-02 inoperable. Entering T.S. 3.2.7(b and c). Action required to close one valve in the line having an inoperable valve or initiate a normal orderly shutdown with in one hour and be in cold shutdown within ten hours. Entering T.S. 3.3.4(b and c). Action required to close one valve in the line having an inoperable valve within four hours or reduce reactor coolant temperature to a value less than 215 degrees F within ten hours. Most limiting action required in current condition is 10 hours to be in cold shutdown. 01-02 will be closed as soon as all rods are in.
The NRC Resident Inspector was notified.
The NRC Resident Inspector was notified.

Latest revision as of 22:24, 1 March 2018

ENS 40436 +/-
Where
Nine Mile Point Constellation icon.png
New York (NRC Region 1)
Reporting
10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown
Time - Person (Reporting Time:+-2.63 h-0.11 days <br />-0.0157 weeks <br />-0.0036 months <br />)
Opened: Frank Payne
15:22 Jan 10, 2004
NRC Officer: Rich Laura
Last Updated: Jan 10, 2004
40436 - NRC Website