Line 16: | Line 16: | ||
| event date = 12/01/2013 06:13 EST | | event date = 12/01/2013 06:13 EST | ||
| last update date = 12/01/2013 | | last update date = 12/01/2013 | ||
| title = Automatic Reactor Scram Due | | title = Automatic Reactor Scram Due to Main Turbine Trip | ||
| event text = While operating at 100% power on 12/01/2013, at 0613 EST, the main turbine tripped on moisture separator hi level. The reactor scrammed along with the main turbine trip. All safety systems responded as designed and expected. There was no radiological release. There were no injuries. | | event text = While operating at 100% power on 12/01/2013, at 0613 EST, the main turbine tripped on moisture separator hi level. The reactor scrammed along with the main turbine trip. All safety systems responded as designed and expected. There was no radiological release. There were no injuries. | ||
During the scram, all rods inserted into the core. The plant is stable in mode 3 in its normal shutdown electrical line up. Decay heat is being removed via the turbine bypass valves dumping steam to the main condenser. | During the scram, all rods inserted into the core. The plant is stable in mode 3 in its normal shutdown electrical line up. Decay heat is being removed via the turbine bypass valves dumping steam to the main condenser. |
Latest revision as of 21:52, 1 March 2018
Where | |
---|---|
Hope Creek New Jersey (NRC Region 1) | |
Reporting | |
10 CFR 50.72(b)(2)(iv)(B), RPS Actuation | |
LER: | 05000354/LER-2013-008 |
Time - Person (Reporting Time:+-1.18 h-0.0492 days <br />-0.00702 weeks <br />-0.00162 months <br />) | |
Opened: | Lindsay Koberlein 10:02 Dec 1, 2013 |
NRC Officer: | Howie Crouch |
Last Updated: | Dec 1, 2013 |
49592 - NRC Website
| |