(Created page by program invented by Mark Hawes)
 
(Created page by program invented by StriderTol)
 
Line 16: Line 16:
| event date = 10/28/2015 06:28 EDT
| event date = 10/28/2015 06:28 EDT
| last update date = 10/28/2015
| last update date = 10/28/2015
| title = Both Trains Of Control Room Emergency Air Conditioning System Inoperable
| title = Both Trains of Control Room Emergency Air Conditioning System Inoperable
| event text = At 0628 [EDT] on 10/28/15, the Salem Unit 1 Control Room Emergency Air Conditioning System (CREACS) train was declared inoperable due to the results of charcoal filter testing not meeting the surveillance requirement. Prior to declaring the Unit 1 train inoperable, the system was operating in the single train filtration operation mode due to refueling outage activities being performed on Unit 2 with the Unit 2 CREACS train inoperable. This resulted in both units' CREACS trains being inoperable.
| event text = At 0628 [EDT] on 10/28/15, the Salem Unit 1 Control Room Emergency Air Conditioning System (CREACS) train was declared inoperable due to the results of charcoal filter testing not meeting the surveillance requirement. Prior to declaring the Unit 1 train inoperable, the system was operating in the single train filtration operation mode due to refueling outage activities being performed on Unit 2 with the Unit 2 CREACS train inoperable. This resulted in both units' CREACS trains being inoperable.
Prior to the event on 10/28/15, Salem Unit 1 was operating in Mode 1 at 100% power and Unit 2 was in Mode 6 with fuel movement in progress.
Prior to the event on 10/28/15, Salem Unit 1 was operating in Mode 1 at 100% power and Unit 2 was in Mode 6 with fuel movement in progress.

Latest revision as of 20:46, 1 March 2018

ENS 51504 +/-
Where
Salem PSEG icon.png
New Jersey (NRC Region 1)
Reporting
10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident
LER: 05000272/LER-2015-007
Regarding Inoperable Control Room Emergency Air Conditioning System Due to Failed Charcoal Filter Surveillance Test
Time - Person (Reporting Time:+2.97 h0.124 days <br />0.0177 weeks <br />0.00407 months <br />)
Opened: Dan Mchugh
13:26 Oct 28, 2015
NRC Officer: Jeff Herrera
Last Updated: Oct 28, 2015