{{#Wiki_filter:_ - - | {{#Wiki_filter:_ - - | ||
DUKE POWER COMPANY Powsm Duitmixo 422 Socin Cuuncu Srazzi, Cruntorrs. N. C. asam 9 | DUKE POWER COMPANY Powsm Duitmixo 422 Socin Cuuncu Srazzi, Cruntorrs. N. C. asam 9 | ||
i W 8 L LI AM O, PAR M ER J R, VeCf Pettietset TtitemoN E:Asta 704 Strane Paoowctiose 373 40e3 il 2 | i W 8 L LI AM O, PAR M ER J R, VeCf Pettietset TtitemoN E:Asta 704 Strane Paoowctiose 373 40e3 il 2 | ||
Revision as of 07:35, 18 February 2020
| ML19341C743 | |
| Person / Time | |
|---|---|
| Site: | Catawba |
| Issue date: | 11/26/1980 |
| From: | Parker W DUKE POWER CO. |
| To: | James O'Reilly NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II) |
| Shared Package | |
| ML19341C738 | List: |
| References | |
| NUDOCS 8103040078 | |
| Download: ML19341C743 (2) | |
Text
_ - -
DUKE POWER COMPANY Powsm Duitmixo 422 Socin Cuuncu Srazzi, Cruntorrs. N. C. asam 9
i W 8 L LI AM O, PAR M ER J R, VeCf Pettietset TtitemoN E:Asta 704 Strane Paoowctiose 373 40e3 il 2
November 26, 1980 Mr. James P. O'Reilly, Director l U. S. Nuclear Regulatory Commission Region II 101 Marietta Street, Suite 3100 Atlanta, Georgia 30303 Re: RII:DKW
! 50-413/80-23 50-414/80-23 1
Dear Mr. O'Reilly:
}
Please find attached a response to Infraction No. 413-414/80 23-01 which was identified in the above referenced Inspection Report.
Duke Power Company does not consider any information contained in this inspection report to be proprietary.
V y truly yours, 7
- d. .
i William O. Parker, Jr.
RWO:vr Attachment ec: NRC - Catawba Resident Inspector i
I
(
l l
181030 4 00'E ,
.- ~ - ___
e 1,
i DUKE POWER COMPANY CATAWBA NUCLEAR STATION Response to Infraction 50-413-414/80-23-01 Infraction
+ As required by 10CFR50, Appendix B, Criterion VII, and as implemented by Duke Power Company Topical Report Section 17.1.7 which states: Duke's quality assurance program requires the control of safety-related items or services purchased from a vendor, subvendor or consultant. Table 17.0-1
- of Duke Power Company Topical Report commits to the requirements of
- Regulatory Guide 1.123, Revision 1, which endorses ANSI N45.2.13-1976.
Paragraph 10.1 of ANSI N45.2.13 requires that the supplier verify that j the item or service being furnished complies with the procurement require-i ments, prior to offering the item or service for acceptance.
Contrary to the above, diesel generator battery racks 1DGBA, 1DGBB, 2DGBA
- and 2DGBB did not meet the seismic requirements of the procurement documents.
The battery racks had been receipt inspected, accepted and installed by the licensee.
1
Response
' Verification of the seismic design is expected from the vendor by 12/15/80.
Duke will submit a final response to the NRC by 12/31/80 after a review of 1 the vendor's records.
i i
i i
- c--..., - - . , - . _ _ _ . _ , , _ _ _ _ , _ __ _ . _ , __