| event date = 07/05/2012 12:58 CDT
| event date = 07/05/2012 12:58 CDT
| last update date = 08/31/2012
| last update date = 08/31/2012
| title = Unanalyzed Condition Due To Blocking Both Reactor Building Railroad Bay Doors
| title = Unanalyzed Condition Due to Blocking Both Reactor Building Railroad Bay Doors
| event text = At 1258 CDT on 07/05/2012, Operations was notified that both panels of Door 45 (south doors for the reactor building railroad bay airlock) were blocked by a man lift.  Blocking both doors represents an unanalyzed condition as a flow path through the door is assumed for pressure relief during postulated HELB events.  The man lift was immediately removed correcting the situation and all work related to Door 45 was stopped. Door 45 was blocked for approximately 20 minutes.
| event text = At 1258 CDT on 07/05/2012, Operations was notified that both panels of Door 45 (south doors for the reactor building railroad bay airlock) were blocked by a man lift.  Blocking both doors represents an unanalyzed condition as a flow path through the door is assumed for pressure relief during postulated HELB events.  The man lift was immediately removed correcting the situation and all work related to Door 45 was stopped. Door 45 was blocked for approximately 20 minutes.
The NRC Resident Inspector has been notified.
The NRC Resident Inspector has been notified.

Latest revision as of 21:03, 1 March 2018

ENS 48072 +/- *RETRACTED*
Where
Monticello Xcel Energy icon.png
Minnesota (NRC Region 3)
Reporting
10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition
Time - Person (Reporting Time:+3.43 h0.143 days <br />0.0204 weeks <br />0.0047 months <br />)
Opened: William Stang
21:24 Jul 5, 2012
NRC Officer: Howie Crouch
Last Updated: Aug 31, 2012
48072 - NRC Website