ATTACHMENT 4
f The following attached Technical Specification pages should be substituted
;                                for the corresponding pages submitted via TSCR No. ,Ls:
Revised Pagest 4,1-8, 4.5-6, 4.7-1 4
d
.i l
1 k
 
t
    .- S                                                                                                                                                                                            .
    -$                                                                                                      TABLE 4.1.1 ( cor.t 'd )                                                              [
    - P2                                                                                                                                                                                  .        '
:c n      Instrument Channel                                            sheck                  Calibrate      Test      Remarks ( Acolies To Tes': and Calibration)
Q.
Q 27. Scram Discharge Volume (Rod Block)                                                                                                                                                      '
a) Water level                                                N/A                    1/20 mos. Every 3        By varying level in switch column high                                                                                            months                                                                          !
b)~ Scram Trip bypass                                          N/A                    N/A          Each re-fueling i                                                                                                                  outage t                                                                                                                                                                                                  i
: 28. Loss of Power a) 4.16 KV-                                                    Daily                  1/24 mos. 1/mo.
Emergency Bus i                Undervoltage (Loss of voltage) 7        b) 4.16 KV Emergency Bus                                      Daily                  1/24 mos. 1/mo.
* Undervoltage (Degraded Voltage) i'
: 29. Drywell High                                                  N/A                    Each re- .Each re-Radiation                                                                              fueling      fueling
; [y  3                                                                                              outage        outage
: c.                                                                                                                                                                                            !
a                                                                                                                                                                                              i
:E.  ~                                                                -
* Calibrate prior to startup and normal shutdown and thereafter check 1/s and test 1/wk until no longer required.
N/A = Not Applicable; 1/s = Once per shift; 1/d = Once per day; 1/3d = Once per three days; 1/wk = Once per week; I 7, Leoend:
1/3 mo = Once every 3 months; 1/18 mos. = Once every 18 months, 1/24 = Once per 24 months t
i o2                                                                                                    . .
; P, The following notes are only for Item 15 of Table 4.1.1:
  .-    A channel may be taken out of service for the purpose of a check, Calibration, test or maintenance without declaring the
        ' channel to be inoperable.
i
' [ ' a.      The channel functional test shall also demonstrate that control room alarm annunciation occurs if any of the following j?            conditions exists:
    ~
!S            1) Instrument indicates measured levels above the alarm setpoint.
: 2) Instrument indicates a downscale failure.
: 3) Instrument controls not set in operate mode.
: 4) Instrument electrical power loss.
q- m. -
y                                    ,V4w=-        -
it m _  w_'-  2
: 4. Reactor Buildino to Suporession chamber Vacuum Dreakers
: a. The reactor building to suppression chamber vacuum breakers and associated instrumentation, including setpoint, shall be checked for proper operation overy three months.
: b. During each refueling outage each vacuum breaker shall be tested l
to determine that the force required to open the vacuum breaker from closed to fully open does not exceed the force specified in Specification 3.5.A.4.a. The air-operated vacuum breaker instrumentation shall be calibrated during each refueling outage.
: 5. Pressure SuDDression Chamher - Drvwell Vacuum Breakers
: a. Ecriodie Onerability Tests i
once each month and following any release of energy which would tend to increase pressure to the suppression chamber, each operable suppression chamber - drywell vacuum breaker shall be exercised. Operation of position switches, indicators and alarms shall be verified monthly by operation of each operable vacuum breaker.
: b. Refuelino Outace Teste (1)    All suppression chamber - drywell vacuum breakers shall be tested to determine the force required to open each valve from fully closed to fully open.
(2)    The suppression chamber - drywell vacuum breaker position indication and alarms systems shall be calibrated and functionally tested.
(3)    At least four of the suppression chamber - drywell vacuum breakers shall be inspected.                      If deficiencies are found, all vacuum breakers shall be inspected and deficiencies corrected such that Specifications 3.5.A.5.a can be met.
(4)  A drywell to suppression chamber leak rate test (interval not to exceed 20 months) shall' demonstrate that with an initial differential pressure of not less than 1.0 poi, the differential pressure decay rate shall not exceed the equivalent of air flow through a 2-inch orifice.
K. Reactor Buildi_ng
: 1. Secondary containment capability tests shall be conducted after                              I isolating the reactor building and placing either Standby Gas Treatment System filter train in operation.
: 2. The tests shall be performed at least once per operating cycle (interval not to exceed 20 months) and shall demonstrate the                          l capability to maintain a h inch of water vacuum under calm wind conditions with a' Standby Gas Treatment System Filter train flow rate of not more than 4000 cfm.
OYSTER CREEK                              4.5-6                    Amendment No.: 14, 52, 132, 141
 
    - . . . - =                                - - -            . . - - ._-. - - .                            ... - _- -.    , - -                _-                - - _ - - - . - .
t
)              . .                  .
4.7 hylXtJARY ELECTR8CA7, POWER hoolicabilltv: Applies to surveillance requirements of the auxiliary
'                                                            electrical supply.                                                                                                                                    l Obieetive:                                  To verify the availability of the auxiliary electrical supply.
Specification:                              A. Diesel Generator                                                                                                                                    j l
: 1. Each diesel generator shall be started and loaded to not                                                                                      i less than 20% rated power every two weeks.                                                                                            l t
1
: 2. The two diesel generators shall be automatically actuated                                                                                      ;
;                                                                          and functionally tested during each refueling outage.
This shall include testing of the diesel generator load                                                                          l i
sequence timers listed in Table 3.1.1.                                                                                                  t
: 3. Each diesel generator shall be given a thorough-                                                                                              i inspection at least once por 24 months during shutdown.                                                                                4 I                                                                4. The diesel generators' fuel supply shall be checked                                                                                            !
following the above tests.
: 5. The diesel generators' starting batteries shall be tested                                                                                    j and monitored the same as the station batteries,                                                                                      ;
specification 4.7.b.                                                                                                                    l I
B. Station Batteries
'                                                                                                                                                                                                                i
: 1. Weekly surveillance will be performe                        to verify the                                                                    [
followings                                                                                                                            j
: a. The active metallic surface of the plates shall be                                                                                I fully covered with electrolyte in all batteries,
: b. The designated pilot cell voltage is greater than or                                                                              I l                                                                                    equal to 2.0 volto and                                                                                                      ,
: c. The overall battery voltage is greater than or equal                                                                              [
to 120 volts (Diesel battery; 112 volts).
: d. The pilot cell specific gravity, corrected to 77'F, is                                                                              ;
greater than or equal to 1.190.                                                                                              !
: 2. Quarterly Surveillance will be performed to verify the                                                                                      [
                                                                                                                                                                                                                  ~
following:
: a. The active metallic surface of the plates shall be                                                                                .
fully covered with electrolyte in all batteries.
: b. The voltage of each' connected cell is greater than or equal to 2.0 volts undet float charge and                                                                                    i r
i OYSTER CREEK                                                                    4.7-1        Amendment No. -15, 55, 60, 141                                                                      l
                    - . - - . . , , . . , - - . .    . , - ,    ..n.--.,            ,  , , - -    , - . . -      - . - - --
                                                                                                                              ,      , . - , - . , ,    .n- ..--..n....-.              , - - , - - - - - . , - ,}}

Latest revision as of 06:25, 6 January 2021

Proposed Tech Specs Change Request 185,extending 24-month Cycle Surveillance to at Least Once Per 24 Months
ML20065M369
Person / Time
Site: Oyster Creek
Issue date: 11/29/1990
From:
GENERAL PUBLIC UTILITIES CORP.
To:
Shared Package
ML20065M367 List:
References
NUDOCS 9012110007
Download: ML20065M369 (4)


Text

.. ..-_ _ . _._____._. _.._.. . _ __. - - _ _ . _ . . _ . . . - . - ... - . _ _ _ _ _ _ _ . . _ . . -

t i

ATTACHMENT 4

f The following attached Technical Specification pages should be substituted

for the corresponding pages submitted via TSCR No. ,Ls

Revised Pagest 4,1-8, 4.5-6, 4.7-1 4

d

.i l

1 k

t

.- S .

-$ TABLE 4.1.1 ( cor.t 'd ) [

- P2 . '

c n Instrument Channel sheck Calibrate Test Remarks ( Acolies To Tes': and Calibration)

Q.

Q 27. Scram Discharge Volume (Rod Block) '

a) Water level N/A 1/20 mos. Every 3 By varying level in switch column high months  !

b)~ Scram Trip bypass N/A N/A Each re-fueling i outage t i

28. Loss of Power a) 4.16 KV- Daily 1/24 mos. 1/mo.

Emergency Bus i Undervoltage (Loss of voltage) 7 b) 4.16 KV Emergency Bus Daily 1/24 mos. 1/mo.

  • Undervoltage (Degraded Voltage) i'
29. Drywell High N/A Each re- .Each re-Radiation fueling fueling
[y 3 outage outage
c.  !

a i

E. ~ -
  • Calibrate prior to startup and normal shutdown and thereafter check 1/s and test 1/wk until no longer required.

N/A = Not Applicable; 1/s = Once per shift; 1/d = Once per day; 1/3d = Once per three days; 1/wk = Once per week; I 7, Leoend:

1/3 mo = Once every 3 months; 1/18 mos. = Once every 18 months, 1/24 = Once per 24 months t

i o2 . .

P, The following notes are only for Item 15 of Table 4.1.1

.- A channel may be taken out of service for the purpose of a check, Calibration, test or maintenance without declaring the

' channel to be inoperable.

i

' [ ' a. The channel functional test shall also demonstrate that control room alarm annunciation occurs if any of the following j? conditions exists:

~

!S 1) Instrument indicates measured levels above the alarm setpoint.

2) Instrument indicates a downscale failure.
3) Instrument controls not set in operate mode.
4) Instrument electrical power loss.

q- m. -

y ,V4w=- -

it m _ w_'- 2

4. Reactor Buildino to Suporession chamber Vacuum Dreakers
a. The reactor building to suppression chamber vacuum breakers and associated instrumentation, including setpoint, shall be checked for proper operation overy three months.
b. During each refueling outage each vacuum breaker shall be tested l

to determine that the force required to open the vacuum breaker from closed to fully open does not exceed the force specified in Specification 3.5.A.4.a. The air-operated vacuum breaker instrumentation shall be calibrated during each refueling outage.

5. Pressure SuDDression Chamher - Drvwell Vacuum Breakers
a. Ecriodie Onerability Tests i

once each month and following any release of energy which would tend to increase pressure to the suppression chamber, each operable suppression chamber - drywell vacuum breaker shall be exercised. Operation of position switches, indicators and alarms shall be verified monthly by operation of each operable vacuum breaker.

b. Refuelino Outace Teste (1) All suppression chamber - drywell vacuum breakers shall be tested to determine the force required to open each valve from fully closed to fully open.

(2) The suppression chamber - drywell vacuum breaker position indication and alarms systems shall be calibrated and functionally tested.

(3) At least four of the suppression chamber - drywell vacuum breakers shall be inspected. If deficiencies are found, all vacuum breakers shall be inspected and deficiencies corrected such that Specifications 3.5.A.5.a can be met.

(4) A drywell to suppression chamber leak rate test (interval not to exceed 20 months) shall' demonstrate that with an initial differential pressure of not less than 1.0 poi, the differential pressure decay rate shall not exceed the equivalent of air flow through a 2-inch orifice.

K. Reactor Buildi_ng

1. Secondary containment capability tests shall be conducted after I isolating the reactor building and placing either Standby Gas Treatment System filter train in operation.
2. The tests shall be performed at least once per operating cycle (interval not to exceed 20 months) and shall demonstrate the l capability to maintain a h inch of water vacuum under calm wind conditions with a' Standby Gas Treatment System Filter train flow rate of not more than 4000 cfm.

OYSTER CREEK 4.5-6 Amendment No.: 14, 52, 132, 141

- . . . - = - - - . . - - ._-. - - . ... - _- -. , - - _- - - _ - - - . - .

t

) . . .

4.7 hylXtJARY ELECTR8CA7, POWER hoolicabilltv: Applies to surveillance requirements of the auxiliary

' electrical supply. l Obieetive: To verify the availability of the auxiliary electrical supply.

Specification: A. Diesel Generator j l

1. Each diesel generator shall be started and loaded to not i less than 20% rated power every two weeks. l t

1

2. The two diesel generators shall be automatically actuated  ;
and functionally tested during each refueling outage.

This shall include testing of the diesel generator load l i

sequence timers listed in Table 3.1.1. t

3. Each diesel generator shall be given a thorough- i inspection at least once por 24 months during shutdown. 4 I 4. The diesel generators' fuel supply shall be checked  !

following the above tests.

5. The diesel generators' starting batteries shall be tested j and monitored the same as the station batteries,  ;

specification 4.7.b. l I

B. Station Batteries

' i

1. Weekly surveillance will be performe to verify the [

followings j

a. The active metallic surface of the plates shall be I fully covered with electrolyte in all batteries,
b. The designated pilot cell voltage is greater than or I l equal to 2.0 volto and ,
c. The overall battery voltage is greater than or equal [

to 120 volts (Diesel battery; 112 volts).

d. The pilot cell specific gravity, corrected to 77'F, is  ;

greater than or equal to 1.190.  !

2. Quarterly Surveillance will be performed to verify the [

~

following:

a. The active metallic surface of the plates shall be .

fully covered with electrolyte in all batteries.

b. The voltage of each' connected cell is greater than or equal to 2.0 volts undet float charge and i r

i OYSTER CREEK 4.7-1 Amendment No. -15, 55, 60, 141 l