ML16335A077: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(Created page by program invented by StriderTol)
 
(One intermediate revision by the same user not shown)
Line 3: Line 3:
| issue date = 11/30/2016
| issue date = 11/30/2016
| title = Emergency Response Data System Changes
| title = Emergency Response Data System Changes
| author name = Bono S M
| author name = Bono S
| author affiliation = Tennessee Valley Authority
| author affiliation = Tennessee Valley Authority
| addressee name =  
| addressee name =  
Line 15: Line 15:


=Text=
=Text=
{{#Wiki_filter:Tennessee Valley Authority , Post Office Box 2000 , Decatur , Alabama 35609-2000 November 30, 2016 ATTN: Document Control Desk U.S. Nuclear Regulatory Commission Washington, D.C. 20555-0001 Browns Ferry Nuclear Plant , Units 1, 2 , and 3 10 CFR 50.4 10 CFR 50 , Appendix E Renewed Facility Operating License Nos. DPR-33 , DPR-52 , and DPR-68 NRC Docket Nos. 50-259 , 50-260 , and 50-296  
{{#Wiki_filter:Tennessee Valley Authority, Post Office Box 2000, Decatur, Alabama 35609-2000 November 30, 2016 10 CFR 50.4 10 CFR 50, Appendix E ATTN : Document Control Desk U.S. Nuclear Regulatory Commission Washington, D.C. 20555-0001 Browns Ferry Nuclear Plant, Units 1, 2, and 3 Renewed Facility Operating License Nos. DPR-33, DPR-52, and DPR-68 NRC Docket Nos. 50-259, 50-260, and 50-296


==Subject:==
==Subject:==
Emergency Response Data System Changes The purpose of this letter is to provide changes to the Emergency Response Data System (EROS), as required by Title 10 of the Code of Federal Regulations (10 CFR) 50 , Appendix E , Section Vl.3 , "Maintaining Emergency Response Data System" for Browns Ferry Nuclear Plant (BFN), Units 1 , 2 , and 3. The Tennessee Valley Authority performed a review of the EROS Data Point Library to identify discrepancies between the EROS Data Point Library and the applicable technical instructions. Several EROS points were changed in the Data Point Library but were not changed in the applicable technical instructions.
Emergency Response Data System Changes The purpose of this letter is to provide changes to the Emergency Response Data System (EROS), as required by Title 10 of the Code of Federal Regulations (10 CFR) 50, Appendix E, Section Vl.3, "Maintaining Emergency Response Data System" for Browns Ferry Nuclear Plant (BFN), Units 1, 2, and 3.
Additionally , these changes were not submitted to the NRC in accordance with 10 CFR 50 , Appendix E , Section Vl.3.a , which requires a notification within 30 days after any software or hardware changes to any transmitted data points identified in the Data Point Library are made. The changes to the EROS Data Point Library include instrument range parameters , alarm/trip set points Modes of operation, how data is processed , unique system description Modes of operation and parameters , plant specific point description titles , and engineer i ng units. This deficiency has been entered into the Corrective Action Program. The changes to the EROS Data Point Library are summarized in the Enclosure. T here are no new regulatory commitments in this letter. Please direct questions concerning this issue to Jamie L. Paul at (256) 729-2636.
The Tennessee Valley Authority performed a review of the EROS Data Point Library to identify discrepancies between the EROS Data Point Library and the applicable technical instructions.
U.S. Nuclear Regulatory Commission Page 2 November 30, 201 6   
Several EROS points were changed in the Data Point Library but were not changed in the applicable technical instructions. Additionally, these changes were not submitted to the NRC in accordance with 10 CFR 50, Appendix E, Section Vl.3.a, which requires a notification within 30 days after any software or hardware changes to any transmitted data points identified in the Data Point Library are made. The changes to the EROS Data Point Library include instrument range parameters, alarm/trip set points Modes of operation, how data is processed, unique system description Modes of operation and parameters, plant specific point description titles, and engineering units. This deficiency has been entered into the Corrective Action Program.
The changes to the EROS Data Point Library are summarized in the Enclosure.
There are no new regulatory commitments in this letter. Please direct questions concerning this issue to Jamie L. Paul at (256) 729-2636.
 
U.S. Nuclear Regulatory Commission Page 2 November 30, 2016


==Enclosure:==
==Enclosure:==
Emergency Response Data System Data Point Library Change cc (w/Enclosure):
NRC Regional Administrator - Region II NRC Senior Resident Inspector - Browns Ferry Nuclear Plant


Emergency Response Data System Data Point Library Change cc (w/Enclosure)
ENCLOSURE Browns Ferry Nuclear Plant Units 1, 2, and 3 Emergency Response Data System Data Point Library Change (See Enclosed)


NRC Regional Administrator
BFN            Emergency Response Data System              1-TI-411 Unit 1            (ERDS) Data Point Library                Rev. 0003 Page 11 of 45 Appendix A (Page 6 of 40)
- Region II  NRC Senior Resident Inspector
ERDS Point Number      4      REAC VES LEV              SPDS0007        Reactor Vessel Water Level Date:                          12/20/2006 Reactor Unit:                  BF1 Data Feeder:                  1 NRC ERDS Parameter:            REAC VES LEV Point ID:                      SPDS0007 Plant Spec Point Desc:        RX WATER LEVEL - COMPOSED GenericCond Desc:              Reactor Vessel Water Level Analog/Digital                A Engr Units/Dig States:        INCHES Engr Units                    N/A Minimum Instr Range:          -268 Maximum Instr Range:          400                500 Zero Point
- Browns Ferry Nuclear Plant


ENCLOSURE  Browns Ferry Nuclear Plant Units 1, 2, and 3  Emergency Response Data System Data Point Library Change
==Reference:==
 
MSSKRT Reference Point Notes:        528 above vessel zero PROC or SENS:                  P Number of Sensors:            11 How Processed:                Weighted Average w/Fault Detect (PSVA)
(See Enclosed)
Sensor Locations:              N/A Alarm/Trip Set Points:        All modes: HIHI=51, HI=39, LO=27, LOLO=2 NID Power Cutoff Level:        N/A NID Power Cut-On              N/A Instrument Failure Mode:      N/A Temperature Compensation:      Y Level Reference Leg:          N/A                          500 Combines one 0 - +400 (floodup), four + 70 (Normal), four -155 -
                              + 60 (Emerg) and two -268 - +32 (post accident) into one wide range indication; therefore, for off normal conditions this point could be difficult to interpret. Instruments are calibrated for normal operating conditions, except for the floodup instrument which is calibrated for atmospheric conditions, and the post accident instruments which are calibrated assuming 212 degrees Fahrenheit water in all lines. Top of Unique System Desc.:          fuel is at - 162.


BFN Unit 1 Emergency Response Data System (ERDS) Data Point Library 1-TI-411 Rev. 0003 Page 11 of 45 Appendix A (Page 6 of 40)
BFN           Emergency Response Data System       1-TI-411 Unit 1            (ERDS) Data Point Library         Rev. 0003 Page 12 of 45 Appendix A (Page 7 of 40)
ERDS Point Number 4 REAC VES LEV SPDS0007 Reactor Vessel Water Level Date: 12/20/2006 Reactor Unit: BF1 Data Feeder: 1 NRC ERDS Parameter: REAC VES LEV Point ID: SPDS0007 Plant Spec Point Desc: RX WATER LEVEL - COMPOSED GenericCond Desc: Reactor Vessel Water Level    Analog/Digital A Engr Units/Dig States: INCHES Engr Units N/A Minimum Instr Range: -268 Maximum Instr Range: 400 Zero Point  
ERDS Point Number     5      MAIN FD FLOW      CALC040    Feedwater Flow into the Reactor Date:                           12/20/2006 Reactor Unit:                   BF1 Data Feeder:                     1 NRC ERDS Parameter:             MAIN FD FLOW Point ID:                       CALC040 Plant Spec Point Desc:           RFW FLOW TO REACTOR GenericCond Desc:               Feedwater Flow into the Reactor Analog/Digital:                  A Engr Units/Dig States:           MLB/HR Engr Units                       N/A Minimum Instr Range:             0 Maximum Instr Range:             20 Zero Point  


==Reference:==
==Reference:==
MSSKRT Reference Point Notes: 528" above vessel zero    PROC or SENS: P Number of Sensors: 11 How Processed: Weighted Average w/Fault Detect (PSVA)
N/A Reference Point Notes:           N/A PROC or SENS:                   P Number of Sensors:               2 How Processed:                   Sum of RFW LINE A and RFW LINE B Sensor Locations:               N/A Alarm/Trip Set Points:           Run: HIHI=14.8, HI=14.7 (EPU values HIHI=17.1, HI=17.0)
Sensor Locations:   N/A Alarm/Trip Set Points: All modes
All modes: HIHI=17.1, HI=17.0 NID Power Cutoff Level:           N/A NID Power Cut-On:                N/A Instrument Failure Mode:         N/A Temperature Compensation:         N Level Reference Leg:             N/A Unique System Desc.:             Sum of feedflow instruments (3-78A & 3-78B),
: HIHI=51, HI=39, LO=27, LOLO=2
uncompensated
 
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: Y Level Reference Leg: N/A Unique System Desc.: Combines one 0 - +400 (floodup), four + 70 (Normal), four -155 - + 60 (Emerg) and two -268 - +32 (post accident) into one wide range indication; therefore, for off normal conditions this point could be difficult to interpret. Instruments are calibrated for normal operating conditions, except for the floodup instrument which is calibrated for atmospheric conditions, and the post accident instruments which are calibrated assuming 212 degrees Fahrenheit water in all lines. Top of fuel is at - 162".


BFN Unit 1 Emergency Response Data System (ERDS) Data Point Library 1-TI-411 Rev. 0003 Page 12 of 45 Appendix A (Page 7 of 40)
BFN           Emergency Response Data System     1-TI-411 Unit 1            (ERDS) Data Point Library       Rev. 0003 Page 26 of 45 Appendix A (Page 21 of 40)
ERDS Point Number 5 MAIN FD FLOW CALC040 Feedwater Flow into the Reactor Date: 12/20/2006 Reactor Unit: BF1 Data Feeder: 1 NRC ERDS Parameter: MAIN FD FLOW Point ID: CALC040 Plant Spec Point Desc: RFW FLOW TO REACTOR GenericCond Desc: Feedwater Flow into the Reactor    Analog/DigitalA Engr Units/Dig States: MLB/HR Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 20 Zero Point  
ERDS Point Number 19          MN STEAM RAD          90-138  Rad Level - Main Steam Line B Date:                           12/20/2006 Reactor Unit:                   BF1 Data Feeder:                   1 NRC ERDS Parameter:             MN STEAM RAD Point ID:                       90-138 Plant Spec Point Desc:         MAIN STM LINE B RAD LEVEL GenericCond Desc:               Rad Level -Main Steam Line B Analog/Digital                 A Engr Units/Dig States:         MR/HR Engr Units                     N/A Minimum Instr Range:           1.0 Maximum Instr Range:           1000000 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: Sum of RFW LINE A and RFW LINE B Sensor Locations:   N/A Alarm/Trip Set Points: Run: HIHI=14.8, HI=14.7  (EPU values HIHI=17.1, HI=17.0)
N/A Reference Point Notes:         N/A PROC or SENS:                   S Number of Sensors:             1 How Processed:                 SALG Sensor Locations:               Main Steam Tunnel Alarm/Trip Set Points:         All modes: HIHI=1500, HI=750 NID Power Cutoff Level:       N/A NID Power Cut-On               N/A Instrument Failure Mode:       LOW Temperature Compensation:     N Level Reference Leg:           N/A Unique System Desc.:
NID Power Cutoff Level: N/A NID Power Cut-OnN/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc.: Sum of feedfl ow instruments (3-78A & 3-78B), uncompensated
Deleted page


BFN Unit 1 Emergency Response Data System (ERDS) Data Point Library 1-TI-411 Rev. 0003 Page 26 of 45 Appendix A (Page 21 of 40)
BFN           Emergency Response Data System       1-TI-411 Unit 1              (ERDS) Data Point Library       Rev. 0003 Page 27 of 45 Appendix A (Page 22 of 40)
ERDS Point Number 19 MN STEAM RAD 90-138 Rad Level - Main Steam Line B Date: 12/20/2006 Reactor Unit: BF1 Data Feeder: 1 NRC ERDS Parameter: MN STEAM RAD Point ID: 90-138 Plant Spec Point Desc: MAIN STM LINE B RAD LEVEL GenericCond Desc: Rad Level -Main Steam Line B    Analog/Digital A Engr Units/Dig States: MR/HR Engr Units N/A Minimum Instr Range: 1.0 Maximum Instr Range: 1000000 Zero Point  
ERDS Point Number       20      MN STEAM RAD         90-139  Rad Level - Main Steam Line D Date:                           12/20/2006 Reactor Unit:                   BF1 Data Feeder:                   1 NRC ERDS Parameter:           MN STEAM RAD Point ID:                       90-139 Plant Spec Point Desc:         MAIN STM LINE D RAD LEVEL GenericCond Desc:             Rad Level -Main Steam Line D Analog/Digital                 A Engr Units/Dig States:         MR/HR Engr Units                     N/A Minimum Instr Range:           1.0 Maximum Instr Range:           1000000 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A   PROC or SENS: S Number of Sensors: 1 How Processed: SALG Sensor Locations:   Main Steam Tunnel Alarm/Trip Set Points: All modes: HIHI=1500, HI=750 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc.:  
N/A Reference Point Notes:         N/A PROC or SENS:                   S Number of Sensors:             1 How Processed:                 SALG Sensor Locations:               Main Steam Tunnel Alarm/Trip Set Points:         All modes: HIHI=1500, HI=750 NID Power Cutoff Level:         N/A NID Power Cut-On               N/A Instrument Failure Mode:       LOW Temperature Compensation:     N Level Reference Leg:           N/A Unique System Desc.:
Deleted page


BFN Unit 1 Emergency Response Data System (ERDS) Data Point Library 1-TI-411 Rev. 0003 Page 27 of 45 Appendix A (Page 22 of 40)
BFN           Emergency Response Data System     1-TI-411 Unit 1            (ERDS) Data Point Library       Rev. 0003 Page 28 of 45 Appendix A (Page 23 of 40)
ERDS Point Number 20 MN STEAM RAD 90-139 Rad Level - Main Steam Line D Date: 12/20/2006   Reactor Unit: BF1 Data Feeder: 1 NRC ERDS Parameter: MN STEAM RAD Point ID: 90-139 Plant Spec Point Desc: MAIN STM LINE D RAD LEVEL GenericCond Desc: Rad Level -Main Steam Line D    Analog/Digital A Engr Units/Dig States: MR/HR Engr Units N/A Minimum Instr Range: 1.0 Maximum Instr Range: 1000000 Zero Point  
ERDS Point Number 21          DW PRESS                SPDS0009    Drywell Pressure Date:                         12/20/2006 Reactor Unit:                 BF1 Data Feeder:                   1 NRC ERDS Parameter:           DW PRESS Point ID:                     SPDS0009 Plant Spec Point Desc:         DRYWELL PRESSURE - COMPOSED GenericCond Desc:             Drywell Pressure Analog/Digital                 A Engr Units/Dig States:         PSIG Engr Units                     N/A Minimum Instr Range:           -15 Maximum Instr Range:           300 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A   PROC or SENS: S Number of Sensors: 1 How Processed: SALG Sensor Locations:   Main Steam Tunnel Alarm/Trip Set Points: All modes: HIHI=1500, HI=750 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc.:   
N/A Reference Point Notes:         N/A PROC or SENS:                 P Number of Sensors:             6 How Processed:                 Weighted Average w/Fault Detect (PSVA)
Sensor Locations:             N/A Alarm/Trip Set Points:         See Below NID Power Cutoff Level:       N/A NID Power Cut-On               N/A Instrument Failure Mode:       N/A Temperature Compensation:     N Level Reference Leg:           N/A Unique System Desc.:          Alarm:    Run:        HIHI=2.45, HI=1.96, LO=1.15, LOLO=1.1 Startup:    HIHI=2.45, HI=1.96, LO=1.15, LOLO=1.1 ShutdownHIHI=2.45, HI=1.96, LO=1.15, LOLO=1.1 Refuel:    HIHI=2.45, HI=1.96


BFN Unit 1 Emergency Response Data System (ERDS) Data Point Library 1-TI-411 Rev. 0003 Page 28 of 45 Appendix A (Page 23 of 40)
BFN           Emergency Response Data System           1-TI-411 Unit 1              (ERDS) Data Point Library             Rev. 0003 Page 32 of 45 Appendix A (Page 27 of 40)
ERDS Point Number 21 DW PRESS SPDS0009 Drywell Pressure Date: 12/20/2006   Reactor Unit: BF1 Data Feeder: 1 NRC ERDS Parameter: DW PRESS Point ID: SPDS0009 Plant Spec Point Desc: DRY WELL PRESSURE - COMPOSED GenericCond Desc:
ERDS Point Number       25    H2 CONC              76-39          Drywell or Torus Hydrogen Level Date:                         12/20/2006 Reactor Unit:                 BF1 Data Feeder:                   1 NRC ERDS Parameter:           H2 CONC Hydrogen Point ID:                     76-39 Plant Spec Point Desc:         DRYWELL H2 CONCENTRATION Generic Cond Desc:             Drywell or Torus Hydrogen Level Analog/Digital                 A Engr Units/Dig States:         %
Drywell Pressure    Analog/Digital A Engr Units/Dig States: PSIG Engr Units N/A Minimum Instr Range: -15 Maximum Instr Range: 300 Zero Point  
Engr Units                     N/A Minimum Instr Range:           0 Maximum Instr Range:           10 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A   PROC or SENS: P Number of Sensors: 6 How Processed: Weighted Average w/Fault Detect (PSVA) Sensor Locations:   N/A Alarm/Trip Set Points: See Below NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc.: Alarm: Run: HIHI
N/A Reference Point Notes:         N/A PROC or SENS:                 P Polynomial Number of Sensors:             1 How Processed:                 Weighted Average w/Fault Detect (PSVA)
=2.45, HI=1.96, LO=1.15, LOLO=1.1    Startup: HIHI=2.45, HI
Sensor Locations:             N/A Alarm/Trip Set Points:         All modes: HIHI=2.4 HI=2.0 LOLO=0.10 NID Power Cutoff Level:       N/A NID Power Cut-On               N/A Instrument Failure Mode:       N/A Temperature Compensation:     N Level Reference Leg:           N/A Sensor input can be switched between the Torus and Drywell, Unique System Desc.:           therefore this point may be difficult to interpret.
=1.96, LO=1.15, LOLO=1.1    Shutdown: HIHI=2.45, HI
=1.96, LO=1.15, LOLO=1.1    Refuel: HIHI=2.45, HI=1.96


BFN Unit 1 Emergency Response Data System (ERDS) Data Point Library 1-TI-411 Rev. 0003 Page 32 of 45 Appendix A (Page 27 of 40)
BFN           Emergency Response Data System         1-TI-411 Unit 1            (ERDS) Data Point Library           Rev. 0003 Page 34 of 45 Appendix A (Page 29 of 40)
ERDS Point Number 25 H2 CONC 76-39 Drywell or Torus Hydrogen Level Date: 12/20/2006   Reactor Unit: BF1 Data Feeder: 1 NRC ERDS Parameter: H2 CONC Point ID: 76-39 Plant Spec Point Desc: DRYWELL H2 CONCENTRATION Generic Cond Desc: Drywel l or Torus Hydrogen Level   Analog/Digital A Engr Units/Dig States: % Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 10  Zero Point  
Condensate Storage Tank #1 ERDS Point Number 27          CST LEVEL                  2-169 (UNIT 1) Level Date:                         12/20/2006 Reactor Unit:                 BF1 Data Feeder:                 1 NRC ERDS Parameter:           CST LEVEL Point ID:                     2-169 Plant Spec Point Desc:       CST #1 (UNIT 1) LEVEL GenericCond Desc:             Condensate Storage Tank Level Analog/Digital               A             FT Engr Units/Dig States:       FEET Engr Units                   28 feet = 375,000 GALLONS Minimum Instr Range:         0       2 Maximum Instr Range:         32 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A    PROC or SENS: P Number of Sensors: 1 How Processed: Weighted Average w/Fault Detect (PSVA) Sensor Locations:   N/A Alarm/Trip Set Points: All modes:
Below Reference Point Notes:       2 feet above bottom of tank PROC or SENS:                 S Number of Sensors:           1 How Processed:               Polynomial Sensor Locations:             N/A        N/A Alarm/Trip Set Points:       All modes: HIHI=29 HI=27 LO=12 LOLO=10 NID Power Cutoff Level:       N/A NID Power Cut-On             N/A Instrument Failure Mode:     LOW Temperature Compensation:     N Level Reference Leg:         N/A Unique System Desc.:         Zero level reference point is 2 feet above bottom of tank.
HIHI=2.4  HI=2.0  LOLO=0.10 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc.: Sensor input can be switched between the Torus and Drywell, therefore this point may be difficult to interpret.  
N/A


BFN Unit 1 Emergency Response Data System (ERDS) Data Point Library 1-TI-411 Rev. 0003 Page 34 of 45 Appendix A (Page 29 of 40)
BFN               Emergency Response Data           2-TI-411 Unit 2          System (ERDS) Data Point Library     Rev. 0003 Page 10 of 45 Appendix A (Page 5 of 40)
ERDS Point Number 27 CST LEVEL 2-169Condensate Storage Tank #1 (UNIT 1) Level Date: 12/20/2006  Reactor Unit: BF1 Data Feeder: 1 NRC ERDS Parameter: CST LEVEL Point ID: 2-169 Plant Spec Point Desc: CST #1 (UNIT 1) LEVEL GenericCond Desc: Condens ate Storage Tank Level    Analog/Digital A Engr Units/Dig States: FEET Engr Units 28 feet = 375,000 GALLONS Minimum Instr Range: 0 Maximum Instr Range: 32 Zero Point  
ERDS Point Number: 3        NI SOURC RNG      SPDS0041      Reactor Power - Source Range Date:                             12/18/2000 Reactor Unit:                     BF2 Data Feeder:                     1 NRC ERDS Parameter:               NI SOURC RNG Point ID:                         SPDS0041 Plant Spec Point Desc:           RX POWER SRM - AVG GenericCond Desc:                 Reactor Power - Source Range Analog/Digital:                  A Engr Units/Dig States:           CPS Engr Units                       N/A 0.1 Minimum Instr Range:             1 Maximum Instr Range:             1000000 Zero Point  


==Reference:==
==Reference:==
Below Reference Point Notes: 2 feet above bottom of tank    PROC or SENS:  S Number of Sensors: 1 How Processed: Polynomial Sensor Locations:   N/A Alarm/Trip Set Points: All modes:
N/A Reference Point Notes:           N/A PROC or SENS                     P Number of Sensors:               4 How Processed:                   Average of healthy inputs (HAVE)
HIHI=29  HI=27  LO=12  LOLO=10 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc.: Zero level referenc e point is 2 feet above bottom of tank.
Sensor Locations:                 N/A Alarm/Trip Set Points:           See Below NID Power Cutoff Level:           N/A NID Power Cut-On                 N/A Instrument Failure Mode:         N/A Temperature Compensation:         N Level Reference Leg:             N/A Unique System Desc:               Alarm: Startup/Shutdown/Refuel: HIHI=500000, HI=100000, LO=5, LOLO=3
 
BFN Unit 2 Emergency Response Data System (ERDS) Data Point Library 2-TI-411 Rev. 0003 Page 10 of 45 Appendix A (Page 5 of 40)
ERDS Point Number: 3 NI SOURC RNG SPDS0041 Reactor Power - Source Range Date:  12/18/2000 Reactor Unit: BF2 Data Feeder:  1 NRC ERDS Parameter:  NI SOURC RNG Point ID:  SPDS0041 Plant Spec Point Desc:  RX POWER SRM - AVG GenericCond Desc:  Reactor Power - Source Range


Analog/Digital: A Engr Units/Dig States: CPS Engr Units N/A Minimum Instr Range: 1 Maximum Instr Range: 1000000 Zero Point  
BFN                Emergency Response Data              2-TI-411 Unit 2          System (ERDS) Data Point Library        Rev. 0003 Page 11 of 45 Appendix A (Page 6 of 40)
ERDS Point Number:      4    REAC VES LEV        SPDS0007      Reactor Vessel Water Level Date:                            12/18/2000 Reactor Unit:                    BF2 Data Feeder:                      1 NRC ERDS Parameter:              REAC VES LEV Point ID:                        SPDS0007 Plant Spec Point Desc:            RX WATER LEVEL - COMPOSED GenericCond Desc:                Reactor Vessel Water Level Analog/Digital:                   A Engr Units/Dig States:           INCHES Engr Units                       N/A Minimum Instr Range:             -268 Maximum Instr Range:             400        500 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A PROC or SENS P Number of Sensors: 4 How Processed: Average of healthy inputs (HAVE) Sensor Locations: N/A Alarm/Trip Set Points: See Below
MSSKRT Reference Point Notes:           528" above vessel zero PROC or SENS                     P Number of Sensors:               11 How Processed:                   Weighted Average w/Fault Detect (PSVA)
 
Sensor Locations:                 N/A Alarm/Trip Set Points:           All modes: HIHI=51, HI=39, LO=27, LOLO=2 NID Power Cutoff Level:           N/A NID Power Cut-On                 N/A Instrument Failure Mode:         N/A Temperature Compensation:         Y Level Reference Leg:             N/A                       500 Unique System Desc:               Combines one 0 - +400 (floodup), four +70 (Normal), four -155 - +60 (Emerg) and two -268 - +32 (post accident) into one wide range indication; therefore, for off normal conditions this point could be difficult to interpret. Instruments are calibrated for normal operating conditions, except for the floodup instrument which is calibrated for atmospheric conditions, and the post accident instruments which are calibrated assuming 212 degrees Faranheit water in all lines. Top of fuel is at
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Alarm: Star tup/Shutdown/Ref uel: HIHI=500000, HI=100000, LO=5, LOLO=3
                                  -162".
 
BFN Unit 2 Emergency Response Data System (ERDS) Data Point Library 2-TI-411 Rev. 0003 Page 11 of 45 Appendix A (Page 6 of 40)
ERDS Point Number: 4 REAC VES LEV SPDS0007 Reactor Vessel Water Level Date:  12/18/2000 Reactor Unit:  BF2 Data Feeder:  1 NRC ERDS Parameter:  REAC VES LEV Point ID:  SPDS0007 Plant Spec Point Desc:  RX WATER LEVEL - COMPOSED GenericCond Desc:  Reactor Vessel Water Level


Analog/Digital: A Engr Units/Dig States: INCHES Engr Units N/A Minimum Instr Range: -268 Maximum Instr Range: 400 Zero Point  
BFN                Emergency Response Data            2-TI-411 Unit 2          System (ERDS) Data Point Library      Rev. 0003 Page 13 of 45 Appendix A (Page 8 of 40)
ERDS Point Number: 6          RCIC FLOW        71-36        Core Isolation Cooling Flow Date:                            12/18/2000 Reactor Unit:                    BF2 Data Feeder:                      1 NRC ERDS Parameter:              RCIC FLOW Point ID:                        71-36 Plant Spec Point Desc:            RCIC PUMP DISCHARGE FLOW GenericCond Desc:                Core Isolation Cooling Flow Analog/Digital:                   A Engr Units/Dig States:           GPM Engr Units                       N/A Minimum Instr Range:             0 Maximum Instr Range:             700 Zero Point  


==Reference:==
==Reference:==
MSSKRT Reference Point Notes: 528" above vessel zero PROC or SENS P Number of Sensors: 11 How Processed: Weighted Average w/Fault Detect (PSVA) Sensor Locations: N/A Alarm/Trip Set Points: All modes:
N/A Reference Point Notes:           N/A PROC or SENS                     S Number of Sensors:               1              SQRT How Processed:                   Polynomial Sensor Locations:                 Downstream of Min Flow Line Alarm/Trip Set Points:           All modes: HIHI=625 NID Power Cutoff Level:           N/A NID Power Cut-On                 N/A Instrument Failure Mode:         LOW Temperature Compensation:         N Level Reference Leg:             N/A Unique System Desc:
HIHI=51, HI=39, LO=27, LOLO=2 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: Y Level Reference Leg: N/A Unique System Desc: Combines one 0 - +400 (floodup), four +70 (Normal), four -155 - +60 (Emerg) and two -268 - +32 (post accident) into one wide range indication; therefore, for off normal conditions this point could be difficult to


interpret. Instruments are calibrated for normal operating
BFN               Emergency Response Data         2-TI-411 Unit 2          System (ERDS) Data Point Library   Rev. 0003 Page 20 of 45 Appendix A (Page 15 of 40)
 
ERDS Point Number: 13          CND A/E RAD    SPDS0047    Condensor Air Ejector Rad Level Date:                           12/18/2000 Reactor Unit:                   BF2 Data Feeder:                     1 NRC ERDS Parameter:             CND A/E RAD TREATMENT-AVG Point ID:                       SPDS0047 Plant Spec Point Desc:           OFFGAS POST TREATMENT AVG GenericCond Desc:               Condensor Air Ejector Rad Level Analog/Digital:                 A Engr Units/Dig States:           CPS Engr Units                       N/A 0.1 Minimum Instr Range:             1 Maximum Instr Range:             1000000 Zero Point  
conditions, except for the floodup instrument which is calibrated for atmospheric conditions, and the post
 
accident instruments whic h are calibrated assuming 212 degrees Faranheit water in all lines. Top of fuel is at
-162".
BFN Unit 2 Emergency Response Data System (ERDS) Data Point Library 2-TI-411 Rev. 0003 Page 13 of 45 Appendix A (Page 8 of 40)
ERDS Point Number: 6 RCIC FLOW 71-36 Core Isolation Cooling Flow Date: 12/18/2000 Reactor Unit: BF2 Data Feeder: 1 NRC ERDS Parameter: RCIC FLOW Point ID: 71-36 Plant Spec Point Desc: RCIC PUMP DISCHARGE FLOW GenericCond Desc: Core Isolation Cooling Flow
 
Analog/Digital: A Engr Units/Dig States: GPM Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 700 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: Polynomial Sensor Locations: Downstream of Min Flow Line Alarm/Trip Set Points: All modes: HIHI=625
N/A Reference Point Notes:           N/A PROC or SENS                     P Number of Sensors:               2 How Processed:                   Healthy Average (HAVE)
 
Sensor Locations:               N/A Alarm/Trip Set Points:           See Below NID Power Cutoff Level:         N/A NID Power Cut-On                 N/A Instrument Failure Mode:         N/A Temperature Compensation:       N Level Reference Leg:             N/A Unique System Desc:             Alarm: Run/Startup:      HIHI=290000, HI=58000, LOLO=10 Shutdown/Refuel: LOLO=10
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:  


BFN Unit 2 Emergency Response Data System (ERDS) Data Point Library 2-TI-411 Rev. 0003 Page 20 of 45 Appendix A (Page 15 of 40)
BFN               Emergency Response Data           2-TI-411 Unit 2          System (ERDS) Data Point Library     Rev. 0003 Page 22 of 45 Appendix A (Page 17 of 40)
ERDS Point Number: 13 CND A/E RAD SPDS0047 Condensor Air Ejector Rad Level Date: 12/18/2000 Reactor Unit: BF2 Data Feeder: 1 NRC ERDS Parameter: CND A/E RAD Point ID: SPDS0047 Plant Spec Point Desc:
ERDS Point Number: 15          DW RAD           90-272A      Drywell Radiation - 135 Deg Date:                           12/18/2000 Reactor Unit:                   BF2 Data Feeder:                     1 NRC ERDS Parameter:             DW RAD Point ID:                       90-272A Plant Spec Point Desc:           DW RAD-RX 555, 135 DEG AZIMUTH GenericCond Desc:               Drywell Radiation - 135 Deg Analog/Digital:                 A Engr Units/Dig States:           R/HR Engr Units                       N/A   0.1 Minimum Instr Range:             1 Maximum Instr Range:             10000000 Zero Point  
OFFGAS POST TREATMENT AVG GenericCond Desc: Condensor Air Ejector Rad Level
 
Analog/Digital: A Engr Units/Dig States: CPS Engr Units N/A Minimum Instr Range: 1 Maximum Instr Range: 1000000 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A PROC or SENS P Number of Sensors: 2 How Processed: Healthy Average (HAVE) Sensor Locations: N/A Alarm/Trip Set Points: See Below
N/A Reference Point Notes:           N/A PROC or SENS                     S Number of Sensors:               1 How Processed:                   SALG Sensor Locations:               At Level 555, 135 Degree Azimuth Alarm/Trip Set Points:           All modes:      HIHI=1440, HI=1000 NID Power Cutoff Level:          N/A NID Power Cut-On                N/A Instrument Failure Mode:        LOW Temperature Compensation:        N Level Reference Leg:            N/A Unique System Desc:


NID Power Cutoff Level:  N/A NID Power Cut-On  N/A Instrument Failure Mode:  N/A Temperature Compensation:  N Level Reference Leg:  N/A Unique System Desc:  Alarm:Run/Startup: HIHI=290000, HI=58000, LOLO=10 Shutdown/Refuel: LOLO=10
BFN               Emergency Response Data           2-TI-411 Unit 2          System (ERDS) Data Point Library     Rev. 0003 Page 23 of 45 Appendix A (Page 18 of 40)
 
ERDS Point Number: 16          DW RAD           90-273A    Drywell Radiation - 270 Deg Date:                           12/18/2000 Reactor Unit:                   BF2 Data Feeder:                     1 NRC ERDS Parameter:             DW RAD Point ID:                       90-273A Plant Spec Point Desc:           DW RAD-RX 560, 270 DEG AZIMUTH GenericCond Desc:               Drywell Radiation - 270 Deg Analog/Digital:                 A Engr Units/Dig States:           R/HR Engr Units                       N/A 0.1 Minimum Instr Range:             1 Maximum Instr Range:             10000000 Zero Point  
BFN Unit 2 Emergency Response Data System (ERDS) Data Point Library 2-TI-411 Rev. 0003 Page 22 of 45 Appendix A (Page 17 of 40)
ERDS Point Number: 15 DW RAD 90-272A Drywell Radiation - 135 Deg Date: 12/18/2000 Reactor Unit: BF2 Data Feeder: 1 NRC ERDS Parameter: DW RAD Point ID: 90-272A Plant Spec Point Desc: DW RAD-RX 555, 135 DEG AZIMUTH GenericCond Desc: Drywel l Radiation - 135 Deg  
 
Analog/Digital: A Engr Units/Dig States: R/HR Engr Units N/A Minimum Instr Range: 1 Maximum Instr Range: 10000000 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: SALG Sensor Locations: At Lev el 555, 135 Degree Azimuth Alarm/Trip Set Points: All modes: HIHI=1440, HI=1000  
N/A Reference Point Notes:           N/A PROC or SENS                     S Number of Sensors:               1 How Processed:                   SALG Sensor Locations:               At Level 560, 270 Degree Azimuth Alarm/Trip Set Points:           All modes: HIHI=1440, HI=1000 NID Power Cutoff Level:         N/A NID Power Cut-On                 N/A Instrument Failure Mode:         LOW Temperature Compensation:       N Level Reference Leg:             N/A Unique System Desc:
 
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:  
 
BFN Unit 2 Emergency Response Data System (ERDS) Data Point Library 2-TI-411 Rev. 0003 Page 23 of 45 Appendix A (Page 18 of 40)
ERDS Point Number: 16 DW RAD 90-273A Drywell Radiation - 270 Deg Date:  12/18/2000 Reactor Unit:  BF2 Data Feeder:  1 NRC ERDS Parameter:  DW RAD Point ID:  90-273A Plant Spec Point Desc:  DW RAD-RX 560, 270 DEG AZIMUTH GenericCond Desc:  Drywel l Radiation - 270 Deg


Analog/Digital: A Engr Units/Dig States: R/HR Engr Units N/A Minimum Instr Range: 1 Maximum Instr Range: 10000000 Zero Point  
BFN                Emergency Response Data          2-TI-411 Unit 2          System (ERDS) Data Point Library    Rev. 0003 Page 26 of 45 Appendix A (Page 21 of 40)
ERDS Point Number:    19        MN STEAM RAD        90-138  Rad Level - Main Steam Line B Date:                            12/18/2000 Reactor Unit:                    BF2 Data Feeder:                      1 NRC ERDS Parameter:              MN STEAM RAD Point ID:                        90-138 Plant Spec Point Desc:            MAIN STM LINE B RAD LEVEL GenericCond Desc:                Rad Level - Main Steam Line B Analog/Digital:                   A Engr Units/Dig States:           MR/HR Engr Units                       N/A Minimum Instr Range:             1 Maximum Instr Range:             1000000 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: SALG Sensor Locations: At Lev el 560, 270 Degree Azimuth Alarm/Trip Set Points: All modes: HIHI=1440, HI=1000
N/A Reference Point Notes:           N/A PROC or SENS                     S Number of Sensors:               1 How Processed:                   SALG Sensor Locations:                 Main Steam Tunnel Alarm/Trip Set Points:           All modes: HIHI=7200, HI=3600 NID Power Cutoff Level:           N/A NID Power Cut-On                 N/A Instrument Failure Mode:         LOW Temperature Compensation:         N Level Reference Leg:             N/A Unique System Desc:
 
Deleted page
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:  
 
BFN Unit 2 Emergency Response Data System (ERDS) Data Point Library 2-TI-411 Rev. 0003 Page 26 of 45 Appendix A (Page 21 of 40)
ERDS Point Number: 19 MN STEAM RAD 90-138 Rad Level - Main Steam Line B Date:  12/18/2000 Reactor Unit:  BF2 Data Feeder:  1 NRC ERDS Parameter:  MN STEAM RAD Point ID:  90-138 Plant Spec Point Desc:  MAIN STM LINE B RAD LEVEL GenericCond Desc:  Rad Level - Main Steam Line B


Analog/Digital: A Engr Units/Dig States: MR/HR Engr Units N/A Minimum Instr Range: 1 Maximum Instr Range: 1000000 Zero Point  
BFN                Emergency Response Data          2-TI-411 Unit 2          System (ERDS) Data Point Library    Rev. 0003 Page 27 of 45 Appendix A (Page 22 of 40)
ERDS Point Number:    20        MN STEAM RAD      90-139  Rad Level - Main Steam Line D Date:                            12/18/2000 Reactor Unit:                    BF2 Data Feeder:                    1 NRC ERDS Parameter:              MN STEAM RAD Point ID:                        90-139 Plant Spec Point Desc:          MAIN STM LINE D RAD LEVEL GenericCond Desc:                Rad Level - Main Steam Line D Analog/Digital:                 A Engr Units/Dig States:           MR/HR Engr Units                       N/A Minimum Instr Range:             1 Maximum Instr Range:             1000000 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: SALG Sensor Locations: Main Steam Tunnel Alarm/Trip Set Points: All modes: HIHI=7200, HI=3600  
N/A Reference Point Notes:           N/A PROC or SENS                     S Number of Sensors:               1 How Processed:                   SALG Sensor Locations:               Main Steam Tunnel Alarm/Trip Set Points:           All modes: HIHI=7200, HI=3600 NID Power Cutoff Level:         N/A NID Power Cut-On                 N/A Instrument Failure Mode:         LOW Temperature Compensation:       N Level Reference Leg:             N/A Unique System Desc:
 
Deleted page
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:  
 
BFN Unit 2 Emergency Response Data System (ERDS) Data Point Library 2-TI-411 Rev. 0003 Page 27 of 45 Appendix A (Page 22 of 40)
ERDS Point Number: 20 MN STEAM RAD 90-139 Rad Level - Main Steam Line D Date:  12/18/2000 Reactor Unit:  BF2 Data Feeder:  1 NRC ERDS Parameter:  MN STEAM RAD Point ID:  90-139 Plant Spec Point Desc:  MAIN STM LINE D RAD LEVEL GenericCond Desc:  Rad Level - Main Steam Line D


Analog/Digital: A Engr Units/Dig States: MR/HR Engr Units N/A Minimum Instr Range: 1 Maximum Instr Range: 1000000 Zero Point  
BFN                Emergency Response Data              2-TI-411 Unit 2          System (ERDS) Data Point Library        Rev. 0003 Page 33 of 45 Appendix A (Page 28 of 40)
ERDS Point Number:    26      O2 CONC        76-43          Drywell or Torus Oxygen Level Date:                              12/18/2000 Reactor Unit:                      BF2 Data Feeder:                      1 NRC ERDS Parameter:                O2 CONC Point ID:                          76-43 Plant Spec Point Desc:            DRYWELL OXYGEN CONCENTRATION GenericCond Desc:                  Drywell or Torus Oxygen Level Analog/Digital:                   A Engr Units/Dig States:             %
Engr Units                         N/A Minimum Instr Range:               0 25 Maximum Instr Range:               5 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: SALG Sensor Locations: Main Steam Tunnel Alarm/Trip Set Points: All modes: HIHI=7200, HI=3600
N/A Reference Point Notes:             N/A PROC or SENS                       S Number of Sensors:                 1 How Processed:                     Polynomial Sensor Locations:                 N/A Alarm/Trip Set Points:             All modes: HIHI=4.5, HI=4.0, LOLO=0.10 NID Power Cutoff Level:           N/A NID Power Cut-On                   N/A Instrument Failure Mode:           LOW Temperature Compensation:         N Level Reference Leg:               N/A Unique System Desc:               There are 2 sensors that can be switched between the Torus and Drywell. Normally 1 is set to each; therefore, this point may be difficult to interpret.
 
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:  
 
BFN Unit 2 Emergency Response Data System (ERDS) Data Point Library 2-TI-411 Rev. 0003 Page 33 of 45 Appendix A (Page 28 of 40)
ERDS Point Number: 26 O2 CONC 76-43 Drywell or Torus Oxygen Level Date:  12/18/2000 Reactor Unit:  BF2 Data Feeder:  1 NRC ERDS Parameter:  O2 CONC Point ID:  76-43 Plant Spec Point Desc:  DRYWELL OXYGEN CONCENTRATION GenericCond Desc:  Drywel l or Torus Oxygen Level


Analog/Digital: A Engr Units/Dig States: % Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 5 Zero Point  
BFN                Emergency Response Data            2-TI-411 Unit 2          System (ERDS) Data Point Library      Rev. 0003 Page 34 of 45 Appendix A (Page 29 of 40)
ERDS Point Number:    27      CST LEVEL        2-161      Condensate Storage Tank Level Date:                            12/18/2000 Reactor Unit:                    BF2 Data Feeder:                      1 NRC ERDS Parameter:              CST LEVEL Point ID:                        2-161 Plant Spec Point Desc:            CST #2 (UNIT 2) LEVEL GenericCond Desc:                Condensate Storage Tank Level Analog/Digital:                   A           FT Engr Units/Dig States:           FEET Engr Units                       28 feet = 375,000 GALLONS Minimum Instr Range:             0       2 Maximum Instr Range:             32 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: Polynomial Sensor Locations: N/A Alarm/Trip Set Points: All m odes: HIHI=4.5, HI=4.0, LOLO=0.10 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: There are 2 sens ors that can be switched between the Torus and Drywell. Normally 1 is set to each; therefore, this point may be difficult to interpret.  
Below Reference Point Notes:           2 feet above bottom of tank PROC or SENS                     S Number of Sensors:               1 How Processed:                   Polynomial Sensor Locations:                 N/A Alarm/Trip Set Points:           All modes: HIHI=29, HI=27, LO=12, LOLO=10 NID Power Cutoff Level:           N/A NID Power Cut-On                 N/A Instrument Failure Mode:         LOW Temperature Compensation:         N Level Reference Leg:             N/A Unique System Desc:               Zero point reference is 2 feet above the bottom of the tank.
N/A


BFN Unit 2 Emergency Response Data System (ERDS) Data Point Library 2-TI-411 Rev. 0003 Page 34 of 45 Appendix A (Page 29 of 40)
BFN               Emergency Response Data           2-TI-411 Unit 2         System (ERDS) Data Point Library     Rev. 0003 Page 41 of 45 Appendix A (Page 36 of 40)
ERDS Point Number: 27 CST LEVEL 2-161 Condensate Storage Tank Level Date:  12/18/2000 Reactor Unit:  BF2 Data Feeder:  1 NRC ERDS Parameter:  CST LEVEL Point ID:  2-161 Plant Spec Point Desc:  CST #2 (UNIT 2) LEVEL GenericCond Desc:  Condens ate Storage Tank Level
ERDS Point Number:     34     STAB CLASS         CALC524 Stability Class Upper Date:                             09/19/2012 Reactor Unit:                     BF2 Data Feeder:                       1 NRC ERDS Parameter:               STAB CLASS               STACK LVL ATM STAB Point ID:                         CALC524                 CLASS (15 MIN)
 
Plant Spec Point Desc:             Stability Class Upper GenericCond Desc:                 Air Stability Upper Analog/Digital:
Analog/Digital:  A Engr Units/Dig States:  FEET Engr Units  28 feet = 375,000 GALLONS Minimum Instr Range:  0 Maximum Instr Range:  32 Zero Point
Engr Units/Dig States:             STABA Engr Units Minimum Instr Range:
 
==Reference:==
Below Reference Point Notes:  2 feet above bottom of tank PROC or SENS  S Number of Sensors:  1 How Processed:  Polynomial Sensor Locations:  N/A Alarm/Trip Set Points:  All modes:
HIHI=29, HI=27, LO=12, LOLO=10 NID Power Cutoff Level:  N/A NID Power Cut-On  N/A Instrument Failure Mode:  LOW Temperature Compensation:  N Level Reference Leg:  N/A Unique System Desc:  Zero point refer ence is 2 feet above the bottom of the tank.
BFN Unit 2 Emergency Response Data System (ERDS) Data Point Library 2-TI-411 Rev. 0003 Page 41 of 45 Appendix A (Page 36 of 40)
ERDS Point Number: 34 STAB CLASS CALC524Stability Class Upper Date: 09/19/2012 Reactor Unit: BF2 Data Feeder: 1 NRC ERDS Parameter: STAB CLASS Point ID: CALC524 Plant Spec Point Desc: Stability Class Upper GenericCond Desc: Air Stability Upper Analog/Digital:
Engr Units/Dig States: STABA Engr Units Minimum Instr Range:
Maximum Instr Range:
Maximum Instr Range:
Zero Point  
Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A PROC or SENS P Number of Sensors: 2 How Processed:   Sensor Locations:   Alarm/Trip Set Points: No Alarms NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Differential Te mperature Upper-Lower (deg C)   Difference   > <= Stability Class Point Value  
N/A Reference Point Notes:             N/A PROC or SENS                       P Number of Sensors:                 2 How Processed:
  -1.9 A 1 -1.9 -1.7 B 2  
Sensor Locations:
-1.7 -1.5 C 3 -1.5 -0.5 D 4 -0.5 1.5 E 5 1.5 4.0 F 6 4.0 G 7  
Alarm/Trip Set Points:             No Alarms NID Power Cutoff Level:           N/A NID Power Cut-On                   N/A Instrument Failure Mode:           N/A Temperature Compensation:         N Level Reference Leg:               N/A Unique System Desc:               Differential Temperature Upper-Lower (deg C)
Difference
                              >                 <=             Stability Class Point Value
                                                -1.9                   A             1
                              -1.9             -1.7                   B             2
                              -1.7             -1.5                   C             3
                              -1.5             -0.5                   D             4
                              -0.5             1.5                   E             5 1.5               4.0                   F             6 4.0                                     G             7


BFN Unit 2 Emergency Response Data System (ERDS) Data Point Library 2-TI-411 Rev. 0003 Page 42 of 45 Appendix A (Page 37 of 40)
BFN               Emergency Response Data             2-TI-411 Unit 2          System (ERDS) Data Point Library       Rev. 0003 Page 42 of 45 Appendix A (Page 37 of 40)
ERDS Point Number: 35 STAB CLASS CALC525 Air Stability Intermediate Date: 09/19/2012 Reactor Unit: BF2 Data Feeder: 1 NRC ERDS Parameter: STAB CLASS Point ID: CALC525 Plant Spec Point Desc: Stability Class Intermediate GenericCond Desc: Air Stability Intermediate  
ERDS Point Number:     35     STAB CLASS         CALC525     Air Stability Intermediate Date:                             09/19/2012 Reactor Unit:                     BF2 Data Feeder:                       1 NRC ERDS Parameter:               STAB CLASS                       OVERALL ATM STAB Point ID:                         CALC525                         CLASS (15 MIN)
 
Plant Spec Point Desc:             Stability Class Intermediate GenericCond Desc:                 Air Stability Intermediate Analog/Digital:
Analog/Digital:   Engr Units/Dig States: STABA Engr Units Minimum Instr Range:   Maximum Instr Range:   Zero Point  
Engr Units/Dig States:             STABA Engr Units Minimum Instr Range:
Maximum Instr Range:
Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A PROC or SENS P Number of Sensors: 2 How Processed:   Sensor Locations:   Alarm/Trip Set Points: No Alarms  
N/A Reference Point Notes:             N/A PROC or SENS                       P Number of Sensors:                 2 How Processed:
Sensor Locations:
Alarm/Trip Set Points:             No Alarms NID Power Cutoff Level:            N/A NID Power Cut-On                  N/A Instrument Failure Mode:          N/A Temperature Compensation:          N Level Reference Leg:              N/A Unique System Desc:                Differential Temperature Upper-Intermed. (deg C)
Difference
                              >                  <=              Stability Class Point Value
                                                  -1.9                    A              1
                              -1.9              -1.7                    B              2
                              -1.7              -1.5                    C              3
                              -1.5              -0.5                    D              4
                              -0.5              1.5                      E              5 1.5                4.0                      F              6 4.0                                        G              7


NID Power Cutoff Level:  N/A NID Power Cut-On  N/A Instrument Failure Mode:  N/A Temperature Compensation:  N Level Reference Leg:  N/A Unique System Desc:  Differential Te mperature Upper-Int ermed. (deg C)  Difference  > <= Stability Class Point Value
BFN                Emergency Response Data              2-TI-411 Unit 2         System (ERDS) Data Point Library       Rev. 0003 Page 43 of 45 Appendix A (Page 38 of 40)
  -1.9 A 1  -1.9 -1.7 B 2 -1.7 -1.5 C 3
ERDS Point Number:     36     STAB CLASS         CALC526 Air Stability Lower Date:                             09/19/2012 Reactor Unit:                     BF2 Data Feeder:                       1 NRC ERDS Parameter:               STAB CLASS Point ID:                         CALC526                   GRND LVL ATM STAB Plant Spec Point Desc:             Stability Class Lower     CLASS (15 MIN)
-1.5 -0.5 D 4  -0.5 1.5 E 5  1.5 4.0 F 6 4.0  G 7
GenericCond Desc:                 Air Stability Lower Analog/Digital:
 
Engr Units/Dig States:             STABA Engr Units Minimum Instr Range:
BFN Unit 2 Emergency Response Data System (ERDS) Data Point Library 2-TI-411 Rev. 0003 Page 43 of 45 Appendix A (Page 38 of 40)
Maximum Instr Range:
ERDS Point Number: 36 STAB CLASS CALC526Air Stability Lower Date: 09/19/2012 Reactor Unit: BF2 Data Feeder: 1 NRC ERDS Parameter: STAB CLASS Point ID: CALC526 Plant Spec Point Desc: Stability Class Lower GenericCond Desc: Air Stability Lower  
Zero Point  
 
Analog/Digital:   Engr Units/Dig States: STABA Engr Units Minimum Instr Range:   Maximum Instr Range:   Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A PROC or SENS P Number of Sensors: 2 How Processed:   Sensor Locations:   Alarm/Trip Set Points: No ALarms  
N/A Reference Point Notes:             N/A PROC or SENS                       P Number of Sensors:                 2 How Processed:
 
Sensor Locations:
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Differential Te mperature Intermed-Lower (deg C)   Difference   > <= Stability Class Point Value  
Alarm/Trip Set Points:             No ALarms NID Power Cutoff Level:           N/A NID Power Cut-On                   N/A Instrument Failure Mode:           LOW Temperature Compensation:         N Level Reference Leg:               N/A Unique System Desc:               Differential Temperature Intermed-Lower (deg C)
  -1.9 A 1 -1.9 -1.7 B 2 -1.7 -1.5 C 3  
Difference
-1.5 -0.5 D 4 -0.5 1.5 E 5 1.5 4.0 F 6 4.0 G 7  
                              >                 <=             Stability Class Point Value
 
                                                  -1.9                   A             1
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 9 of 45 Appendix A (Page 4 of 40)
                              -1.9               -1.7                   B             2
ERDS Point Number: 2 NI INTER RNG CALCO45 Reactor Power - Intermediate Rng Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: NI INTER RNG Point ID: CALCO45 Plant Spec Point Desc: AVERAGE OF 8 IRM'S GenericCond Desc: Reactor Power - Intermediate Rng
                              -1.7               -1.5                   C             3
                              -1.5               -0.5                   D             4
                              -0.5               1.5                     E             5 1.5               4.0                     F             6 4.0                                       G             7


Analog/Digital: A Engr Units/Dig States: %SCALE Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 125 Zero Point  
BFN                Emergency Response Data              3-TI-411 Unit 3          System (ERDS) Data Point Library        Rev. 0003 Page 9 of 45 Appendix A (Page 4 of 40)
ERDS Point Number:      2    NI INTER RNG        CALCO45      Reactor Power - Intermediate Rng Date:                          12/19/2000                CALC045 Reactor Unit:                  BF3 Data Feeder:                  1 NRC ERDS Parameter:            NI INTER RNG Point ID:                      CALCO45                CALC045 Plant Spec Point Desc:        AVERAGE OF 8 IRM'S GenericCond Desc:              Reactor Power - Intermediate Rng Analog/Digital:               A Engr Units/Dig States:         %SCALE Engr Units                     N/A Minimum Instr Range:           0 Maximum Instr Range:           125 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A  
N/A Reference Point Notes:         N/A PROC or SENS                  P Number of Sensors:            8                AVE How Processed:                Average (AVG)
Sensor Locations:              N/A Alarm/Trip Set Points:        See Below NID Power Cutoff Level:        N/A NID Power Cut-On              N/A Instrument Failure Mode:      N/A Temperature Compensation:      N Level Reference Leg:          N/A Unique System Desc:            Since the IRMs have a range switch this average is difficult to interpret.
Alarm:        Run:          HIHI=120 Startup:      HIHI=108 HI=80 LO=20 LOLO=15 Shutdown:      HIHI=50 HI=25 Refuel:        HIHI=50 HI=25


PROC or SENS P Number of Sensors: 8 How Processed: Average (AVG)
BFN               Emergency Response Data                   3-TI-411 Unit 3          System (ERDS) Data Point Library             Rev. 0003 Page 11 of 45 Appendix A (Page 6 of 40)
Sensor Locations: N/A Alarm/Trip Set Points: See Below
ERDS Point Number:     4   REAC VES LEV         SPDS0007         Reactor Vessel Water Level Date:                         12/19/2000 Reactor Unit:                 BF3 Data Feeder:                 1 NRC ERDS Parameter:           REAC VES LEV Point ID:                     SPDS0007 Plant Spec Point Desc:       RX WATER LEVEL - COMPOSED GenericCond Desc:             Reactor Vessel Water Level Analog/Digital:               A Engr Units/Dig States:       INCHES Engr Units                   N/A Minimum Instr Range:         -268 Maximum Instr Range:         400           500 Zero Point  
 
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Since the IRMs have a range switch this average is difficult to interpret.
 
Alarm: Run: HIHI=120 Startup: HIHI=108 HI=80 LO=20 LOLO=15 Shutdown: HIHI=50 HI=25  Refuel: HIHI=50 HI=25
 
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 11 of 45 Appendix A (Page 6 of 40)
ERDS Point Number: 4 REAC VES LEV SPDS0007 Reactor Vessel Water Level Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: REAC VES LEV Point ID: SPDS0007 Plant Spec Point Desc: RX WATER LEVEL - COMPOSED GenericCond Desc: Reactor Vessel Water Level  
 
Analog/Digital: A Engr Units/Dig States: INCHES Engr Units N/A Minimum Instr Range: -268 Maximum Instr Range: 400 Zero Point  


==Reference:==
==Reference:==
MSSKRT Reference Point Notes: 528" above vessel zero  
MSSKRT Reference Point Notes:       528" above vessel zero PROC or SENS                  P Number of Sensors:            11 How Processed:                Weighted Average w/Fault Detect (PSVA)
Sensor Locations:            N/A Alarm/Trip Set Points:        All modes: HIHI=51 HI=39 LO=27 LOLO=2 NID Power Cutoff Level:      N/A              RUN/SU/SD NID Power Cut-On              N/A Instrument Failure Mode:      N/A Temperature Compensation:    Y                              500 Level Reference Leg:          N/A Unique System Desc:          Combines one 0 - +400 (floodup), four +70 (Normal), four
                              -155 - +60 (Emerg) and two -268 - +32 (post accident) into one wide range indication; therefore, for off normal conditions this point could be difficult to interpret. Instruments are calibrated for normal operating conditions, except for the floodup instrument which is calibrated for atmospheric conditions, and the post accident instruments which are calibrated assuming 212 degrees Faranheit water in all lines. Top of fuel is at -162".


PROC or SENS P Number of Sensors: 11 How Processed: Weighted Average w/Fault Detect (PSVA)
BFN                Emergency Response Data              3-TI-411 Unit 3           System (ERDS) Data Point Library       Rev. 0003 Page 12 of 45 Appendix A (Page 7 of 40)
Sensor Locations: N/A Alarm/Trip Set Points: All modes:  HIHI=51 HI=39 LO=27 LOLO=2
ERDS Point Number:     5   MAIN FD FLOW       CALCO40       Feedwater Flow into the Reactor Date:                         12/19/2000               CALC040 Reactor Unit:                 BF3 Data Feeder:                 1 NRC ERDS Parameter:           MAIN FD FLOW Point ID:                     CALCO40               CALC040 Plant Spec Point Desc:       RFW FLOW TO REACTOR GenericCond Desc:             Feedwater Flow into the Reactor Analog/Digital:               A Engr Units/Dig States:       MLB/HR Engr Units                   N/A Minimum Instr Range:         0     20 Maximum Instr Range:         16 Zero Point  
 
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: Y Level Reference Leg: N/A Unique System Desc: Combines one 0 - +400 (floodup), four +70 (Normal), four -155 - +60 (Emerg) and two -268 - +32 (post accident) into one wide range indication; therefore, for off normal conditions this point could be difficult to interpret. Instruments are calibrated for normal operating conditions, except for the floodup instrument which is calibrated for atmospheric conditions, and the post accident instruments which are calibrated assuming 212 degrees Faranheit water in all lines. Top of fuel is at -162".
 
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 12 of 45 Appendix A (Page 7 of 40)
ERDS Point Number: 5 MAIN FD FLOW CALCO40 Feedwater Flow into the Reactor Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: MAIN FD FLOW Point ID: CALCO40 Plant Spec Point Desc: RFW FLOW TO REACTOR GenericCond Desc: Feedwater Flow into the Reactor  
 
Analog/Digital: A Engr Units/Dig States: MLB/HR Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 16 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A  
N/A Reference Point Notes:       N/A PROC or SENS                 P Number of Sensors:           2 How Processed:               Sum of RFW LINE A and RFW LINE B Sensor Locations:             N/A Alarm/Trip Set Points:       Run: HIHI=14.8 HI=14.7 NID Power Cutoff Level:       N/A NID Power Cut-On             N/A Instrument Failure Mode:     N/A Temperature Compensation:     N Level Reference Leg:         N/A Unique System Desc:           Sum of feedflow instruments, uncompensated
 
PROC or SENS P Number of Sensors: 2 How Processed: Sum of RFW LINE A and RFW LINE B Sensor Locations: N/A Alarm/Trip Set Points: Run: HIHI=14.8 HI=14.7  
 
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Sum of feedflow instruments, uncompensated  
 
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 13 of 45 Appendix A (Page 8 of 40)
ERDS Point Number: 6 RCIC FLOW 71-36 Core Isolation Cooling Flow Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: RCIC FLOW Point ID: 71-36 Plant Spec Point Desc: RCIC PUMP DISCHARGE FLOW GenericCond Desc: Core Isolation Cooling Flow


Analog/Digital: A Engr Units/Dig States: GPM Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 700 Zero Point  
BFN                Emergency Response Data        3-TI-411 Unit 3          System (ERDS) Data Point Library  Rev. 0003 Page 13 of 45 Appendix A (Page 8 of 40)
ERDS Point Number:      6    RCIC FLOW          71-36    Core Isolation Cooling Flow Date:                        12/19/2000 Reactor Unit:                BF3 Data Feeder:                  1 NRC ERDS Parameter:          RCIC FLOW Point ID:                    71-36 Plant Spec Point Desc:        RCIC PUMP DISCHARGE FLOW GenericCond Desc:            Core Isolation Cooling Flow Analog/Digital:               A Engr Units/Dig States:       GPM Engr Units                   N/A Minimum Instr Range:         0 Maximum Instr Range:         700 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A  
N/A Reference Point Notes:       N/A PROC or SENS                 S             SQRT Number of Sensors:           1 How Processed:               Polynomial Sensor Locations:             Downstream of Min Flow Line Alarm/Trip Set Points:       All modes: HIHI=625 RUN/SU/SD NID Power Cutoff Level:       N/A NID Power Cut-On             N/A Instrument Failure Mode:     LOW Temperature Compensation:     N Level Reference Leg:         N/A Unique System Desc:
 
PROC or SENS S Number of Sensors: 1 How Processed: Polynomial Sensor Locations: Downstream of Min Flow Line Alarm/Trip Set Points: All modes: HIHI=625  
 
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:
 
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 14 of 45 Appendix A (Page 9 of 40)
ERDS Point Number: 7 RCS PRESSURE SPDS0008 Reactor Coolant System Pressure Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: RCS PRESSURE Point ID: SPDS0008 Plant Spec Point Desc: RX PRESSURE - COMPOSED GenericCond Desc: Reactor Coolant System Pressure


Analog/Digital: A Engr Units/Dig States: PSIG Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 1500 Zero Point  
BFN                Emergency Response Data                3-TI-411 Unit 3          System (ERDS) Data Point Library          Rev. 0003 Page 14 of 45 Appendix A (Page 9 of 40)
ERDS Point Number:      7    RCS PRESSURE      SPDS0008        Reactor Coolant System Pressure Date:                        12/19/2000 Reactor Unit:                BF3 Data Feeder:                  1 NRC ERDS Parameter:          RCS PRESSURE Point ID:                    SPDS0008 Plant Spec Point Desc:        RX PRESSURE - COMPOSED GenericCond Desc:            Reactor Coolant System Pressure Analog/Digital:               A Engr Units/Dig States:       PSIG Engr Units                   N/A Minimum Instr Range:         0 Maximum Instr Range:         1500 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A  
N/A Reference Point Notes:       N/A PROC or SENS                 P Number of Sensors:           6 How Processed:               Weighted Average w/Fault Detect (PSVA)
 
Sensor Locations:             N/A Alarm/Trip Set Points:       See Below NID Power Cutoff Level:       N/A NID Power Cut-On             N/A Instrument Failure Mode:     N/A Temperature Compensation:     Y Level Reference Leg:         N/A Unique System Desc:           Instruments are calibrated for rated operating conditions.
PROC or SENS P Number of Sensors: 6 How Processed: Weighted Average w/Fault Detect (PSVA)
Alarm:   Run:           HIHI=1073 HI=1070 LO=918 LOLO=915 Startup:       HIHI=1073 HI=1070 LO=918 LOLO=915 Shutdown:     HIHI=1073 HI=1070 Refuel:       HIHI=1073 HI=1070
Sensor Locations: N/A Alarm/Trip Set Points: See Below  
 
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: Y Level Reference Leg: N/A Unique System Desc: Instruments are calibrated for rated operating conditions.
Alarm: Run: HIHI=1073 HI=1070 LO=918 LOLO=915 Startup: HIHI=1073 HI=1070 LO=918 LOLO=915 Shutdown: HIHI=1073 HI=1070 Refuel: HIHI=1073 HI=1070  


BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 15 of 45 Appendix A (Page 10 of 40)
BFN               Emergency Response Data             3-TI-411 Unit 3          System (ERDS) Data Point Library       Rev. 0003 Page 15 of 45 Appendix A (Page 10 of 40)
ERDS Point Number: 8 HPCI FLOW 73-33 High Pressure Coolant Inj. Flow Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: HPCI FLOW Point ID: 73-33 Plant Spec Point Desc: HPCI Pump Discharge Flow GenericCond Desc: High Pressure Coolant Inj. Flow  
ERDS Point Number:     8   HPCI FLOW       73-33           High Pressure Coolant Inj. Flow Date:                         12/19/2000 Reactor Unit:                 BF3 Data Feeder:                 1 NRC ERDS Parameter:           HPCI FLOW Point ID:                     73-33 Plant Spec Point Desc:       HPCI Pump Discharge Flow GenericCond Desc:             High Pressure Coolant Inj. Flow Analog/Digital:               A Engr Units/Dig States:       GPM Engr Units                   N/A Minimum Instr Range:         0 Maximum Instr Range:         6000 Zero Point  
 
Analog/Digital: A Engr Units/Dig States: GPM Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 6000 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A  
N/A Reference Point Notes:       N/A PROC or SENS                  S Number of Sensors:            1 How Processed:                Polynomial Sensor Locations:            Downstream of Min Flow Line Alarm/Trip Set Points:        All modes: HIHI=5200 RUN/SU/SD NID Power Cutoff Level:      N/A NID Power Cut-On              N/A Instrument Failure Mode:      LOW Temperature Compensation:    N Level Reference Leg:          N/A Unique System Desc:


PROC or SENS S Number of Sensors: 1 How Processed: Polynomial Sensor Locations: Downstream of Min Flow Line Alarm/Trip Set Points: All modes:  HIHI=5200
BFN               Emergency Response Data             3-TI-411 Unit 3          System (ERDS) Data Point Library       Rev. 0003 Page 16 of 45 Appendix A (Page 11 of 40)
 
ERDS Point Number:     9   LPCI FLOW         74-50         LPCI - RHR System 1 Flow Date:                         12/19/2000 Reactor Unit:                 BF3 Data Feeder:                   1 NRC ERDS Parameter:           LPCI FLOW Point ID:                     74-50 Plant Spec Point Desc:         RHR SYS I FLOW GenericCond Desc:             LPCI - RHR System 1 Flow Analog/Digital:               A Engr Units/Dig States:         GPM Engr Units                     N/A Minimum Instr Range:           0 Maximum Instr Range:           25000 Zero Point  
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: 
 
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 16 of 45 Appendix A (Page 11 of 40)
ERDS Point Number: 9 LPCI FLOW 74-50 LPCI - RHR System 1 Flow Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: LPCI FLOW Point ID: 74-50 Plant Spec Point Desc: RHR SYS I FLOW GenericCond Desc: LPCI - RHR System 1 Flow  
 
Analog/Digital: A Engr Units/Dig States: GPM Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 25000 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A  
N/A Reference Point Notes:         N/A PROC or SENS                  S Number of Sensors:            1 How Processed:                Polynomial Sensor Locations:              Downstream of HX and Before Sprays Alarm/Trip Set Points:        All Modes: HIHI=20000 HI=13000 RUN/SU/SD NID Power Cutoff Level:        N/A NID Power Cut-On              N/A Instrument Failure Mode:      LOW Temperature Compensation:      N Level Reference Leg:          N/A Unique System Desc:


PROC or SENS S Number of Sensors: 1 How Processed: Polynomial Sensor Locations: Downstream of HX and Before Sprays Alarm/Trip Set Points: All Modes:  HIHI=20000 HI=13000
BFN               Emergency Response Data             3-TI-411 Unit 3          System (ERDS) Data Point Library       Rev. 0003 Page 17 of 45 Appendix A (Page 12 of 40)
 
ERDS Point Number:     10   LPCI FLOW         74-64         LPCI - RHR System II Flow Date:                         12/19/2000 Reactor Unit:                 BF3 Data Feeder:                   1 NRC ERDS Parameter:           LPCI FLOW Point ID:                     74-64 Plant Spec Point Desc:         RHR SYS II FLOW GenericCond Desc:             LPCI - RHR System II Flow Analog/Digital:               A Engr Units/Dig States:         GPM Engr Units                     N/A Minimum Instr Range:           0 Maximum Instr Range:           25000 Zero Point  
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: 
 
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 17 of 45 Appendix A (Page 12 of 40)
ERDS Point Number: 10 LPCI FLOW 74-64 LPCI - RHR System II Flow Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: LPCI FLOW Point ID: 74-64 Plant Spec Point Desc: RHR SYS II FLOW GenericCond Desc: LPCI - RHR System II Flow  
 
Analog/Digital: A Engr Units/Dig States: GPM Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 25000 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A  
N/A Reference Point Notes:         N/A PROC or SENS                  S Number of Sensors:            1 How Processed:                Polynomial Sensor Locations:              Downstream of HX and Before Sprays Alarm/Trip Set Points:        All modes: HIHI=20000 HI=13000 RUN/SU/SD NID Power Cutoff Level:        N/A NID Power Cut-On              N/A Instrument Failure Mode:      LOW Temperature Compensation:      N Level Reference Leg:          N/A Unique System Desc:


PROC or SENS S Number of Sensors: 1 How Processed: Polynomial Sensor Locations: Downstream of HX and Before Sprays Alarm/Trip Set Points: All modes:  HIHI=20000 HI=13000
BFN               Emergency Response Data         3-TI-411 Unit 3          System (ERDS) Data Point Library   Rev. 0003 Page 18 of 45 Appendix A (Page 13 of 40)
 
ERDS Point Number:     11   CR SPRAY FL       75-21       Core Spray - System I Flow Date:                         12/19/2000 Reactor Unit:                 BF3 Data Feeder:                 1 NRC ERDS Parameter:           CR SPRAY FL Point ID:                     75-21 Plant Spec Point Desc:       CORE SPRAY SYS I FLOW GenericCond Desc:             Core Spray - System I Flow Analog/Digital:               A Engr Units/Dig States:       GPM Engr Units                   N/A Minimum Instr Range:         0 Maximum Instr Range:         10000 Zero Point  
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: 
 
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 18 of 45 Appendix A (Page 13 of 40)
ERDS Point Number: 11 CR SPRAY FL 75-21 Core Spray - System I Flow Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: CR SPRAY FL Point ID: 75-21 Plant Spec Point Desc: CORE SPRAY SYS I FLOW GenericCond Desc: Core Spray - System I Flow  
 
Analog/Digital: A Engr Units/Dig States: GPM Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 10000 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A  
N/A Reference Point Notes:       N/A PROC or SENS                 S Number of Sensors:           1 How Processed:               Polynomial Sensor Locations:             Downstream of Min Flow Line Alarm/Trip Set Points:       All modes: HIHI=6300 HI=6275 RUN/SU/SD NID Power Cutoff Level:       N/A NID Power Cut-On             N/A Instrument Failure Mode:     LOW Temperature Compensation:     N Level Reference Leg:         N/A Unique System Desc:
 
PROC or SENS S Number of Sensors: 1 How Processed: Polynomial Sensor Locations: Downstream of Min Flow Line Alarm/Trip Set Points: All modes: HIHI=6300 HI=6275  
 
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:
 
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 19 of 45 Appendix A (Page 14 of 40)
ERDS Point Number: 12 CR SPRAY FL 75-49 Core Spray - System II Flow Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: CR SPRAY FL Point ID: 75-49 Plant Spec Point Desc: CORE SPRAY SYS II FLOW GenericCond Desc: Core Spray - System II Flow


Analog/Digital: A Engr Units/Dig States: GPM Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 10000 Zero Point  
BFN                Emergency Response Data          3-TI-411 Unit 3          System (ERDS) Data Point Library    Rev. 0003 Page 19 of 45 Appendix A (Page 14 of 40)
ERDS Point Number:      12  CR SPRAY FL      75-49        Core Spray - System II Flow Date:                          12/19/2000 Reactor Unit:                  BF3 Data Feeder:                  1 NRC ERDS Parameter:            CR SPRAY FL Point ID:                      75-49 Plant Spec Point Desc:        CORE SPRAY SYS II FLOW GenericCond Desc:              Core Spray - System II Flow Analog/Digital:               A Engr Units/Dig States:         GPM Engr Units                     N/A Minimum Instr Range:           0 Maximum Instr Range:           10000 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A  
N/A Reference Point Notes:         N/A PROC or SENS                   S Number of Sensors:             1 How Processed:                 Polynomial Sensor Locations:             Downstream of Min Flow Line Alarm/Trip Set Points:         All modes: HIHI=6300 HI=6275 RUN/SU/SD NID Power Cutoff Level:       N/A NID Power Cut-On               N/A Instrument Failure Mode:       LOW Temperature Compensation:     N Level Reference Leg:           N/A Unique System Desc:
 
PROC or SENS S Number of Sensors: 1 How Processed: Polynomial Sensor Locations: Downstream of Min Flow Line Alarm/Trip Set Points: All modes: HIHI=6300 HI=6275 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:
 
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 21 of 45 Appendix A (Page 16 of 40)
ERDS Point Number: 14 CND A/E RAD 90-157 Offgas Pre Treatment Avg Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: CND A/E RAD Point ID: 90-157 Plant Spec Point Desc: OFFGAS PRE TREATMENT AVG GenericCond Desc: Offgas Pre Treatment Avg


Analog/Digital: A Engr Units/Dig States: MR/HR Engr Units N/A Minimum Instr Range: .1 Maximum Instr Range: 1000000 Zero Point  
BFN                Emergency Response Data            3-TI-411 Unit 3          System (ERDS) Data Point Library      Rev. 0003 Page 21 of 45 Appendix A (Page 16 of 40)
ERDS Point Number:      14  CND A/E RAD      90-157      Offgas Pre Treatment Avg Date:                          12/19/2000 Reactor Unit:                  BF3 Data Feeder:                  1 NRC ERDS Parameter:            CND A/E RAD Point ID:                      90-157 Plant Spec Point Desc:        OFFGAS PRE TREATMENT AVG GenericCond Desc:              Offgas Pre Treatment Avg RADIATION Analog/Digital:               A Engr Units/Dig States:         MR/HR Engr Units                     N/A       1 Minimum Instr Range:           .1 Maximum Instr Range:           1000000 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A  
N/A Reference Point Notes:         N/A PROC or SENS                  S Number of Sensors:            1 How Processed:                SALG Sensor Locations:              N/A Alarm/Trip Set Points:        Run/Startup: HIHI=1690 HI=845 LOLO=1 NID Power Cutoff Level:        N/A NID Power Cut-On              N/A Instrument Failure Mode:      Downscale Temperature Compensation:      N Level Reference Leg:          N/A Unique System Desc:


PROC or SENS S Number of Sensors: 1 How Processed: SALG Sensor Locations: N/A Alarm/Trip Set Points: Run/Startup:  HIHI=1690 HI=845 LOLO=1
BFN                 Emergency Response Data           3-TI-411 Unit 3          System (ERDS) Data Point Library       Rev. 0003 Page 22 of 45 Appendix A (Page 17 of 40)
 
ERDS Point Number:       15   DW RAD           90-272A     Drywell Radiation - 45 Deg Date:                         12/19/2000 Reactor Unit:                 BF3 Data Feeder:                   1 NRC ERDS Parameter:           DW RAD Point ID:                     90-272A Plant Spec Point Desc:         DW RAD-RX 582, 45 DEG AZIMUTH GenericCond Desc:             Drywell Radiation - 45 Deg Analog/Digital:               A Engr Units/Dig States:         R/HR Engr Units                     N/A     0.1 Minimum Instr Range:           1 Maximum Instr Range:           10000000 Zero Point  
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: Downscale Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: 
 
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 22 of 45 Appendix A (Page 17 of 40)
ERDS Point Number: 15 DW RAD 90-272A Drywell Radiation - 45 Deg Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: DW RAD Point ID: 90-272A Plant Spec Point Desc: DW RAD-RX 582, 45 DEG AZIMUTH GenericCond Desc: Drywell Radiation - 45 Deg  
 
Analog/Digital: A Engr Units/Dig States: R/HR Engr Units N/A Minimum Instr Range: 1 Maximum Instr Range: 10000000 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A  
N/A Reference Point Notes:         N/A PROC or SENS                   S Number of Sensors:             1 How Processed:                 SALG Sensor Locations:             At Level 582, 45 Degree Azimuth Alarm/Trip Set Points:         All modes: HIHI=1440 HI=1000 RUN/SU/SD NID Power Cutoff Level:        N/A NID Power Cut-On              N/A Instrument Failure Mode:      LOW Temperature Compensation:      N Level Reference Leg:          N/A Unique System Desc:
 
PROC or SENS S Number of Sensors: 1 How Processed: SALG Sensor Locations: At Level 582, 45 Degree Azimuth Alarm/Trip Set Points: All modes: HIHI=1440 HI=1000  


NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: 
BFN                 Emergency Response Data             3-TI-411 Unit 3          System (ERDS) Data Point Library       Rev. 0003 Page 23 of 45 Appendix A (Page 18 of 40)
 
ERDS Point Number:       16   DW RAD           90-273A     Drywell Radiation - 270 Deg Date:                         12/19/2000 Reactor Unit:                 BF3 Data Feeder:                   1 NRC ERDS Parameter:           DW RAD Point ID:                     90-273A Plant Spec Point Desc:         DW RAD-RX 560, 270 DEG AZIMUTH GenericCond Desc:             Drywell Radiation - 270 Deg Analog/Digital:               A Engr Units/Dig States:         R/HR Engr Units                     N/A   0.1 Minimum Instr Range:           1 Maximum Instr Range:           10000000 Zero Point  
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 23 of 45 Appendix A (Page 18 of 40)
ERDS Point Number: 16 DW RAD 90-273A Drywell Radiation - 270 Deg Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: DW RAD Point ID: 90-273A Plant Spec Point Desc: DW RAD-RX 560, 270 DEG AZIMUTH GenericCond Desc: Drywell Radiation - 270 Deg  
 
Analog/Digital: A Engr Units/Dig States: R/HR Engr Units N/A Minimum Instr Range: 1 Maximum Instr Range: 10000000 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A  
N/A Reference Point Notes:         N/A PROC or SENS                   S Number of Sensors:             1 How Processed:                 SALG Sensor Locations:             At Level 560, 270 Degree Azimuth Alarm/Trip Set Points:         All modes: HIHI=1440 HI=1000 RUN/SU/SD NID Power Cutoff Level:       N/A NID Power Cut-On               N/A Instrument Failure Mode:       LOW Temperature Compensation:     N Level Reference Leg:           N/A Unique System Desc:
 
PROC or SENS S Number of Sensors: 1 How Processed: SALG Sensor Locations: At Level 560, 270 Degree Azimuth Alarm/Trip Set Points: All modes: HIHI=1440 HI=1000  
 
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:
 
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 24 of 45 Appendix A (Page 19 of 40)
ERDS Point Number: 17 MN STEAM RAD 90-136 Rad Level - Main Steam Line A Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: MN STEAM RAD Point ID: 90-136 Plant Spec Point Desc: MAIN STM LINE A RAD LEVEL GenericCond Desc: Rad Level - Main Steam Line A


Analog/Digital: A Engr Units/Dig States: MR/HR Engr Units N/A Minimum Instr Range: 1 Maximum Instr Range: 1000000 Zero Point  
BFN                Emergency Response Data            3-TI-411 Unit 3          System (ERDS) Data Point Library        Rev. 0003 Page 24 of 45 Appendix A (Page 19 of 40)
ERDS Point Number:      17  MN STEAM RAD      90-136      Rad Level - Main Steam Line A Date:                          12/19/2000 Reactor Unit:                  BF3 Data Feeder:                  1 NRC ERDS Parameter:            MN STEAM RAD Point ID:                      90-136 Plant Spec Point Desc:        MAIN STM LINE A RAD LEVEL GenericCond Desc:              Rad Level - Main Steam Line A Analog/Digital:               A Engr Units/Dig States:         MR/HR Engr Units                     N/A Minimum Instr Range:           1 Maximum Instr Range:           1000000 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A  
N/A Reference Point Notes:         N/A PROC or SENS                   S Number of Sensors:             1 How Processed:                 SALG Sensor Locations:             Main Steam Tunnel Alarm/Trip Set Points:         All modes: HIHI=1500 HI=750 RUN/SU/SD NID Power Cutoff Level:       N/A NID Power Cut-On               N/A Instrument Failure Mode:       LOW Temperature Compensation:     N Level Reference Leg:           N/A Unique System Desc:
 
PROC or SENS S Number of Sensors: 1 How Processed: SALG Sensor Locations: Main Steam Tunnel Alarm/Trip Set Points: All modes: HIHI=1500 HI=750  
 
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:
 
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 25 of 45 Appendix A (Page 20 of 40)
ERDS Point Number: 18 MN STEAM RAD 90-137 Rad Level - Main Steam Line C Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: MN STEAM RAD Point ID: 90-137 Plant Spec Point Desc: MAIN STM LINE C RAD LEVEL GenericCond Desc: Rad Level - Main Steam Line C


Analog/Digital: A Engr Units/Dig States: MR/HR Engr Units N/A Minimum Instr Range: 1 Maximum Instr Range: 1000000 Zero Point  
BFN                Emergency Response Data            3-TI-411 Unit 3          System (ERDS) Data Point Library        Rev. 0003 Page 25 of 45 Appendix A (Page 20 of 40)
ERDS Point Number:      18  MN STEAM RAD      90-137      Rad Level - Main Steam Line C Date:                          12/19/2000 Reactor Unit:                  BF3 Data Feeder:                  1 NRC ERDS Parameter:            MN STEAM RAD Point ID:                      90-137 Plant Spec Point Desc:        MAIN STM LINE C RAD LEVEL GenericCond Desc:              Rad Level - Main Steam Line C Analog/Digital:               A Engr Units/Dig States:         MR/HR Engr Units                     N/A Minimum Instr Range:           1 Maximum Instr Range:           1000000 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A  
N/A Reference Point Notes:         N/A PROC or SENS                   S Number of Sensors:             1 How Processed:                 SALG Sensor Locations:             Main Steam Tunnel Alarm/Trip Set Points:         All modes: HIHI=1500 HI=750 RUN/SU/SD NID Power Cutoff Level:       N/A NID Power Cut-On               N/A Instrument Failure Mode:       LOW Temperature Compensation:     N Level Reference Leg:           N/A Unique System Desc:
 
PROC or SENS S Number of Sensors: 1 How Processed: SALG Sensor Locations: Main Steam Tunnel Alarm/Trip Set Points: All modes: HIHI=1500 HI=750  
 
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:
 
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 26 of 45 Appendix A (Page 21 of 40)
ERDS Point Number: 19 MN STEAM RAD 90-138 Rad Level - Main Steam Line B Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: MN STEAM RAD Point ID: 90-138 Plant Spec Point Desc: MAIN STM LINE B RAD LEVEL GenericCond Desc: Rad Level - Main Steam Line B


Analog/Digital: A Engr Units/Dig States: MR/HR Engr Units N/A Minimum Instr Range: 1 Maximum Instr Range: 1000000 Zero Point  
BFN                Emergency Response Data            3-TI-411 Unit 3          System (ERDS) Data Point Library        Rev. 0003 Page 26 of 45 Appendix A (Page 21 of 40)
ERDS Point Number:      19  MN STEAM RAD      90-138      Rad Level - Main Steam Line B Date:                          12/19/2000 Reactor Unit:                  BF3 Data Feeder:                  1 NRC ERDS Parameter:            MN STEAM RAD Point ID:                      90-138 Plant Spec Point Desc:        MAIN STM LINE B RAD LEVEL GenericCond Desc:              Rad Level - Main Steam Line B Analog/Digital:               A Engr Units/Dig States:         MR/HR Engr Units                     N/A Minimum Instr Range:           1 Maximum Instr Range:           1000000 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A  
N/A Reference Point Notes:         N/A PROC or SENS                  S Number of Sensors:            1 How Processed:                SALG Sensor Locations:              Main Steam Tunnel Alarm/Trip Set Points:        All modes: HIHI=1500 HI=750 NID Power Cutoff Level:        N/A NID Power Cut-On              N/A Instrument Failure Mode:      LOW Temperature Compensation:      N Level Reference Leg:          N/A Unique System Desc:
Deleted page


PROC or SENS S Number of Sensors: 1 How Processed: SALG Sensor Locations: Main Steam Tunnel Alarm/Trip Set Points: All modes:  HIHI=1500 HI=750
BFN                 Emergency Response Data             3-TI-411 Unit 3          System (ERDS) Data Point Library       Rev. 0003 Page 27 of 45 Appendix A (Page 22 of 40)
 
ERDS Point Number:       20   MN STEAM RAD       90-139     Rad Level - Main Steam Line D Date:                         12/19/2000 Reactor Unit:                 BF3 Data Feeder:                   1 NRC ERDS Parameter:           MN STEAM RAD Point ID:                     90-139 Plant Spec Point Desc:         MAIN STM LINE D RAD LEVEL GenericCond Desc:             Rad Level - Main Steam Line D Analog/Digital:               A Engr Units/Dig States:         MR/HR Engr Units                     N/A Minimum Instr Range:           1 Maximum Instr Range:           1000000 Zero Point  
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: 
 
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 27 of 45 Appendix A (Page 22 of 40)
ERDS Point Number: 20 MN STEAM RAD 90-139 Rad Level - Main Steam Line D Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: MN STEAM RAD Point ID: 90-139 Plant Spec Point Desc: MAIN STM LINE D RAD LEVEL GenericCond Desc: Rad Level - Main Steam Line D  
 
Analog/Digital: A Engr Units/Dig States: MR/HR Engr Units N/A Minimum Instr Range: 1 Maximum Instr Range: 1000000 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A  
N/A Reference Point Notes:         N/A PROC or SENS                   S Number of Sensors:             1 How Processed:                 SALG Sensor Locations:             Main Steam Tunnel Alarm/Trip Set Points:         All modes: HIHI=1500 HI=750 NID Power Cutoff Level:        N/A NID Power Cut-On              N/A Instrument Failure Mode:      LOW Temperature Compensation:      N Level Reference Leg:          N/A Unique System Desc:
 
Deleted page
PROC or SENS S Number of Sensors: 1 How Processed: SALG Sensor Locations: Main Steam Tunnel Alarm/Trip Set Points: All modes: HIHI=1500 HI=750  


NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: 
BFN               Emergency Response Data             3-TI-411 Unit 3          System (ERDS) Data Point Library       Rev. 0003 Page 28 of 45 Appendix A (Page 23 of 40)
 
ERDS Point Number:     21   DW PRESS           SPDS0009 Drywell Pressure Date:                         12/19/2000 Reactor Unit:                 BF3 Data Feeder:                 1 NRC ERDS Parameter:           DW PRESS Point ID:                     SPDS0009 Plant Spec Point Desc:       DRYWELL PRESSURE - COMPOSED GenericCond Desc:             Drywell Pressure Analog/Digital:               A Engr Units/Dig States:       PSIG Engr Units                   N/A Minimum Instr Range:         -15 Maximum Instr Range:         300 Zero Point  
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 28 of 45 Appendix A (Page 23 of 40)
ERDS Point Number: 21 DW PRESS SPDS0009Drywell Pressure Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: DW PRESS Point ID: SPDS0009 Plant Spec Point Desc: DRYWELL PRESSURE - COMPOSED GenericCond Desc: Drywell Pressure  
 
Analog/Digital: A Engr Units/Dig States: PSIG Engr Units N/A Minimum Instr Range: -15 Maximum Instr Range: 300 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A  
N/A Reference Point Notes:       N/A PROC or SENS                  P Number of Sensors:            6 How Processed:                Weighted Average w/Fault Detect (PSVA)
Sensor Locations:            N/A Alarm/Trip Set Points:        See below NID Power Cutoff Level:      N/A NID Power Cut-On              N/A Instrument Failure Mode:      N/A Temperature Compensation:    N Level Reference Leg:          N/A Unique System Desc:          Alarm:    Run:              HIHI=2.45 HI=1.96 LO=1.15 LOLO=1.1 Startup/Shutdown/
Refuel:            HIHI=2.45 HI=1.96


PROC or SENS P Number of Sensors: 6 How Processed: Weighted Average w/Fault Detect (PSVA)
BFN               Emergency Response Data             3-TI-411 Unit 3          System (ERDS) Data Point Library       Rev. 0003 Page 29 of 45 Appendix A (Page 24 of 40)
Sensor Locations: N/A Alarm/Trip Set Points: See below
ERDS Point Number:     22   DW TEMP             SPDS0010 Drywell Temperature Date:                         12/19/2000 Reactor Unit:                 BF3 Data Feeder:                 1 NRC ERDS Parameter:           DW TEMP Point ID:                     SPDS0010 Plant Spec Point Desc:       DRYWELL TEMPERATURE - COMPOSED GenericCond Desc:             Drywell Temperature Analog/Digital:               A Engr Units/Dig States:       DEGF Engr Units                   N/A Minimum Instr Range:         0 Maximum Instr Range:         400 Zero Point  
 
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Alarm: Run: HIHI=2.45 HI=1.96 LO=1.15 LOLO=1.1  Startup/Shutdown/Refuel: HIHI=2.45 HI=1.96
 
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 29 of 45 Appendix A (Page 24 of 40)
ERDS Point Number: 22 DW TEMP SPDS0010Drywell Temperature Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: DW TEMP Point ID: SPDS0010 Plant Spec Point Desc: DRYWELL TEMPERATURE - COMPOSED GenericCond Desc: Drywell Temperature  
 
Analog/Digital: A Engr Units/Dig States: DEGF Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 400 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A  
N/A Reference Point Notes:       N/A PROC or SENS                 P Number of Sensors:           2 How Processed:               Weighted Average w/Fault Detect (PSVA)
 
PROC or SENS P Number of Sensors: 2 How Processed: Weighted Average w/Fault Detect (PSVA)
Sensor Locations:
Sensor Locations:
Alarm/Trip Set Points: See Below  
Alarm/Trip Set Points:       See Below NID Power Cutoff Level:       N/A NID Power Cut-On             N/A Instrument Failure Mode:     N/A Temperature Compensation:     N Level Reference Leg:         N/A Unique System Desc:           Alarm:   Run:               HIHI=160 HI=145 LO=100 LOLO=70 Startup:           HIHI=160 HI=145 LO=90 LOLO=70 Shutdown/Refuel:   HIHI=160 HI=145 LO=65 LOLO=60
 
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Alarm: Run: HIHI=160 HI=145 LO=100 LOLO=70   Startup: HIHI=160 HI=145 LO=90 LOLO=70   Shutdown/Refuel: HIHI=160 HI=145 LO=65 LOLO=60  
 
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 30 of 45 Appendix A (Page 25 of 40)
ERDS Point Number: 23 SP TEMP SPDS0016 Suppression Pool Temperature Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: SP TEMP Point ID: SPDS0016 Plant Spec Point Desc: SUPPR PL WTR TEMP - COMPOSED GenericCond Desc: Suppression Pool Temperature


Analog/Digital: A Engr Units/Dig States: DEGF Engr Units N/A Minimum Instr Range: 30 Maximum Instr Range: 230 Zero Point  
BFN                Emergency Response Data                3-TI-411 Unit 3          System (ERDS) Data Point Library          Rev. 0003 Page 30 of 45 Appendix A (Page 25 of 40)
ERDS Point Number:      23  SP TEMP        SPDS0016          Suppression Pool Temperature Date:                        12/19/2000 Reactor Unit:                BF3 Data Feeder:                  1 NRC ERDS Parameter:          SP TEMP Point ID:                    SPDS0016 Plant Spec Point Desc:        SUPPR PL WTR TEMP - COMPOSED GenericCond Desc:            Suppression Pool Temperature Analog/Digital:               A Engr Units/Dig States:       DEGF Engr Units                   N/A Minimum Instr Range:         30 Maximum Instr Range:         230 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A  
N/A Reference Point Notes:       N/A PROC or SENS                 P Number of Sensors:           16 How Processed:               Average (PSVA)
 
Sensor Locations:             Around Circumference of Torus Alarm/Trip Set Points:       All modes: HIHI=95 HI=93 LOLO=50 RUN/SU/SD NID Power Cutoff Level:       N/A NID Power Cut-On             N/A Instrument Failure Mode:     N/A Temperature Compensation:     N Level Reference Leg:         N/A Unique System Desc:           There are 4 inputs actually scanned by the computer. Two of these 4 are made of 8 individual sensors that are hardware averaged. The other 2 are selected individual sensors from the total 16 sensors.
PROC or SENS P Number of Sensors: 16 How Processed: Average (PSVA)
Sensor Locations: Around Circumference of Torus Alarm/Trip Set Points: All modes: HIHI=95 HI=93 LOLO=50  
 
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: There are 4 inputs actually scanned by the computer. Two of these 4 are made of 8 individual sensors that are hardware averaged. The other 2 are selected individual sensors from the total 16 sensors.  
 
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 31 of 45 Appendix A (Page 26 of 40)
ERDS Point Number: 24 SP LEVEL SPDS0013 Suppression Pool Water Level Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: SP LEVEL Point ID: SPDS0013 Plant Spec Point Desc: SUPPR PL WTR LVL (IN) - COMPOSED GenericCond Desc: Suppression Pool Water Level


Analog/Digital: A Engr Units/Dig States: INCHES Engr Units N/A Minimum Instr Range: -181.45 Maximum Instr Range: 58.55 Zero Point  
BFN                Emergency Response Data              3-TI-411 Unit 3          System (ERDS) Data Point Library        Rev. 0003 Page 31 of 45 Appendix A (Page 26 of 40)
ERDS Point Number:      24  SP LEVEL      SPDS0013        Suppression Pool Water Level Date:                        12/19/2000 Reactor Unit:                BF3 Data Feeder:                  1 NRC ERDS Parameter:          SP LEVEL Point ID:                    SPDS0013 Plant Spec Point Desc:        SUPPR PL WTR LVL (IN) - COMPOSED GenericCond Desc:            Suppression Pool Water Level Analog/Digital:               A Engr Units/Dig States:       INCHES Engr Units                   N/A Minimum Instr Range:         -181.45 Maximum Instr Range:         58.55 Zero Point  


==Reference:==
==Reference:==
Below Reference Point Notes: 181.45 inches above Torus Bottom  
Below Reference Point Notes:       181.45 inches above Torus Bottom PROC or SENS                  P Number of Sensors:            4 How Processed:                Weighted Average w/Fault Detect (PSVA)
Sensor Locations:            N/A Alarm/Trip Set Points:        See Below NID Power Cutoff Level:      N/A NID Power Cut-On              N/A Instrument Failure Mode:      N/A Temperature Compensation:    N Level Reference Leg:          N/A Unique System Desc:          All modes: HIHI = -1 HI = -2 LO = -5.5 LOLO = -6.25 RUN/SU/SD


PROC or SENS P Number of Sensors: 4 How Processed: Weighted Average w/Fault Detect (PSVA)
BFN                Emergency Response Data                3-TI-411 Unit 3           System (ERDS) Data Point Library           Rev. 0003 Page 32 of 45 Appendix A (Page 27 of 40)
Sensor Locations: N/A Alarm/Trip Set Points: See Below
ERDS Point Number:     25   H2 CONC           SPDS0017       Drywell or Torus Hydrogen Level Date:                         12/19/2000 Reactor Unit:                 BF3 Data Feeder:                 1 NRC ERDS Parameter:           H2 CONC Point ID:                     SPDS0017 Plant Spec Point Desc:       DRYWELL H2 - COMPOSED GenericCond Desc:             Drywell or Torus Hydrogen Level Analog/Digital:               A Engr Units/Dig States:       %
 
Engr Units                   N/A Minimum Instr Range:         0 Maximum Instr Range:         20 Zero Point  
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: All modes:  HIHI = -1 HI = -2 LO = -5.5 LOLO = -6.25
 
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 32 of 45 Appendix A (Page 27 of 40)
ERDS Point Number: 25 H2 CONC SPDS0017 Drywell or Torus Hydrogen Level Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: H2 CONC Point ID: SPDS0017 Plant Spec Point Desc: DRYWELL H2 - COMPOSED GenericCond Desc: Drywell or Torus Hydrogen Level  
 
Analog/Digital: A Engr Units/Dig States: %
Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 20 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A  
N/A Reference Point Notes:       N/A PROC or SENS                 P Number of Sensors:           2 How Processed:               Weighted Average w/Fault Detect (PSVA)
 
Sensor Locations:             N/A Alarm/Trip Set Points:       All modes: HIHI=2.4 HI=2.0 LOLO=0.10 RUN/SU/SD NID Power Cutoff Level:      N/A NID Power Cut-On              N/A Instrument Failure Mode:      N/A Temperature Compensation:    N Level Reference Leg:          N/A Unique System Desc:          There are 2 sensors that can be switched between the Torus and Drywell. Normally 1 is set to each; therefore, this point may be difficult to interpret.
PROC or SENS P Number of Sensors: 2 How Processed: Weighted Average w/Fault Detect (PSVA)
Sensor Locations: N/A Alarm/Trip Set Points: All modes: HIHI=2.4 HI=2.0 LOLO=0.10  


NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: There are 2 sensors that can be switched between the Torus and Drywell. Normally 1 is set to each; therefore, this point may be difficult to interpret.
BFN               Emergency Response Data                 3-TI-411 Unit 3          System (ERDS) Data Point Library           Rev. 0003 Page 33 of 45 Appendix A (Page 28 of 40)
 
ERDS Point Number:     26   O2 CONC           76-43         Drywell or Torus Oxygen Level Date:                         12/19/2000 Reactor Unit:                 BF3 Data Feeder:                 1 NRC ERDS Parameter:           O2 CONC Point ID:                     76-43 Plant Spec Point Desc:       DRYWELL OXYGEN CONCENTRATION GenericCond Desc:             Drywell or Torus Oxygen Level Analog/Digital:               A Engr Units/Dig States:       %
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 33 of 45 Appendix A (Page 28 of 40)
Engr Units                   N/A Minimum Instr Range:         0       25 Maximum Instr Range:         5 Zero Point  
ERDS Point Number: 26 O2 CONC 76-43 Drywell or Torus Oxygen Level Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: O2 CONC Point ID: 76-43 Plant Spec Point Desc: DRYWELL OXYGEN CONCENTRATION GenericCond Desc: Drywell or Torus Oxygen Level  
 
Analog/Digital: A Engr Units/Dig States: %
Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 5 Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A  
N/A Reference Point Notes:       N/A PROC or SENS                  S Number of Sensors:            1 How Processed:                Polynomial Sensor Locations:            N/A Alarm/Trip Set Points:        All modes: HIHI=4.5 HI=4.0 LOLO=0.10 RUN/SU/SD NID Power Cutoff Level:      N/A NID Power Cut-On              N/A Instrument Failure Mode:      LOW Temperature Compensation:    N Level Reference Leg:          N/A Unique System Desc:          There are 2 sensors that can be switched between the Torus and Drywell. Normally 1 is set to each; therefore, this point may be difficult to interpret.


PROC or SENS S Number of Sensors: 1 How Processed: Polynomial Sensor Locations: N/A Alarm/Trip Set Points: All modes:  HIHI=4.5 HI=4.0 LOLO=0.10
BFN               Emergency Response Data               3-TI-411 Unit 3          System (ERDS) Data Point Library         Rev. 0003 Page 34 of 45 Appendix A (Page 29 of 40)
 
ERDS Point Number:     27   CST LEVEL       2-165             Condensate Storage Tank Level Date:                         12/19/2000 Reactor Unit:                 BF3 Data Feeder:                 1 NRC ERDS Parameter:           CST LEVEL Point ID:                     2-165 Plant Spec Point Desc:       CST #3 (UNIT 3) LEVEL GenericCond Desc:             Condensate Storage Tank Level FT Analog/Digital:               A Engr Units/Dig States:       FEET Engr Units                   28 feet = 375,000 GALLONS Minimum Instr Range:         0         2 Maximum Instr Range:         32 Zero Point  
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: There are 2 sensors that can be switched between the Torus and Drywell. Normally 1 is set to each; therefore, this point may be difficult to interpret.
 
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 34 of 45 Appendix A (Page 29 of 40)
ERDS Point Number: 27 CST LEVEL 2-165 Condensate Storage Tank Level Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: CST LEVEL Point ID: 2-165 Plant Spec Point Desc: CST #3 (UNIT 3) LEVEL GenericCond Desc: Condensate Storage Tank Level  
 
Analog/Digital: A Engr Units/Dig States: FEET Engr Units 28 feet = 375,000 GALLONS Minimum Instr Range: 0 Maximum Instr Range: 32 Zero Point  


==Reference:==
==Reference:==
Below Reference Point Notes: 2 feet above bottom of tank  
Below Reference Point Notes:       2 feet above bottom of tank PROC or SENS                  S Number of Sensors:            1 How Processed:                Polynomial Sensor Locations:            N/A Alarm/Trip Set Points:        All modes: HIHI=29 HI=27 LO=12 LOLO=10 RUN/SU/SD NID Power Cutoff Level:      N/A NID Power Cut-On              N/A Instrument Failure Mode:      LOW Temperature Compensation:    N Level Reference Leg:          N/A Unique System Desc:          Zero point reference is 2 feet above the bottom of the tank.
N/A


PROC or SENS S Number of Sensors: 1 How Processed: Polynomial Sensor Locations: N/A Alarm/Trip Set Points: All modes:  HIHI=29 HI=27 LO=12 LOLO=10
BFN               Emergency Response Data                 3-TI-411 Unit 3          System (ERDS) Data Point Library           Rev. 0003 Page 41 of 45 Appendix A (Page 36 of 40)
 
ERDS Point Number:     34   STAB CLASS       CALC524         Stability Class Upper Date:                         09/19/2012 Reactor Unit:                 BF3 Data Feeder:                 1 NRC ERDS Parameter:           STAB CLASS               STACK LVL ATM STAB Point ID:                     CALC524                   CLASS (15 MIN)
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Zero point reference is 2 feet above the bottom of the tank.
Plant Spec Point Desc:       Stability Class Upper GenericCond Desc:             Stability Class Upper Analog/Digital:
 
Engr Units/Dig States:       STABA Engr Units Minimum Instr Range:
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 41 of 45 Appendix A (Page 36 of 40)
Maximum Instr Range:
ERDS Point Number: 34 STAB CLASS CALC524 Stability Class Upper Date: 09/19/2012 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: STAB CLASS Point ID: CALC524 Plant Spec Point Desc: Stability Class Upper GenericCond Desc: Stability Class Upper Analog/Digital:
Zero Point  
Engr Units/Dig States: STABA Engr Units Minimum Instr Range: Maximum Instr Range: Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A PROC or SENS P Number of Sensors: 2 How Processed: Sensor Locations: Alarm/Trip Set Points: No Alarms NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Differential Temperature Upper-Lower (deg C)
N/A Reference Point Notes:       N/A PROC or SENS                 P Number of Sensors:           2 How Processed:
Difference  
Sensor Locations:
> <= Stability Class Point Value
Alarm/Trip Set Points:       No Alarms NID Power Cutoff Level:       N/A NID Power Cut-On             N/A Instrument Failure Mode:     N/A Temperature Compensation:     N Level Reference Leg:         N/A Unique System Desc:           Differential Temperature Upper-Lower (deg C)
  -1.9 A 1   -1.9 -1.7 B 2   -1.7 -1.5 C 3
Difference
-1.5 -0.5 D 4
                                >       <=     Stability Class     Point Value
-0.5 1.5 E 5 1.5 4.0 F 6   4.0 G 7
                                        -1.9           A                 1
                                -1.9     -1.7           B                 2
                                -1.7     -1.5           C                 3
                                -1.5     -0.5           D                 4
                                -0.5     1.5           E                 5 1.5       4.0           F                 6 4.0                     G                 7


BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 42 of 45 Appendix A (Page 37 of 40)
BFN               Emergency Response Data                   3-TI-411 Unit 3          System (ERDS) Data Point Library             Rev. 0003 Page 42 of 45 Appendix A (Page 37 of 40)
ERDS Point Number: 35 STAB CLASS CALC525 Air Stability Intermediate Date: 09/19/2012 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: STAB CLASS Point ID: CALC525 Plant Spec Point Desc: Stability Class Intermediate GenericCond Desc: Air Stability Intermediate  
ERDS Point Number:     35   STAB CLASS         CALC525         Air Stability Intermediate Date:                         09/19/2012 Reactor Unit:                 BF3 Data Feeder:                 1 NRC ERDS Parameter:           STAB CLASS Point ID:                     CALC525                           OVERALL ATM STAB Plant Spec Point Desc:       Stability Class Intermediate     CLASS (15 MIN)
 
GenericCond Desc:             Air Stability Intermediate Analog/Digital:
Analog/Digital:
Engr Units/Dig States:       STABA Engr Units Minimum Instr Range:
Engr Units/Dig States: STABA Engr Units Minimum Instr Range: Maximum Instr Range:
Maximum Instr Range:
Zero Point  
Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A  
N/A Reference Point Notes:       N/A PROC or SENS                 P Number of Sensors:           2 How Processed:
 
PROC or SENS P Number of Sensors: 2 How Processed:
Sensor Locations:
Sensor Locations:
Alarm/Trip Set Points: No Alarms  
Alarm/Trip Set Points:       No Alarms NID Power Cutoff Level:      N/A NID Power Cut-On              N/A Instrument Failure Mode:      N/A Temperature Compensation:    N Level Reference Leg:          N/A Unique System Desc:          Differential Temperature Upper-Intermed. (deg C)
Difference
                                >        <=    Stability Class    Point Value
                                          -1.9          A                  1
                                -1.9      -1.7          B                  2
                                -1.7      -1.5          C                  3
                                -1.5      -0.5          D                  4
                                -0.5      1.5            E                  5 1.5      4.0            F                  6 4.0                      G                  7


NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Differential Temperature Upper-Intermed.  (deg C)  Difference    > <= Stability Class Point Value 
BFN                Emergency Response Data                  3-TI-411 Unit 3           System (ERDS) Data Point Library             Rev. 0003 Page 43 of 45 Appendix A (Page 38 of 40)
  -1.9 A 1 
ERDS Point Number:     36   STAB CLASS       CALC526           Air Stability Lower Date:                         09/19/2012 Reactor Unit:                 BF3 Data Feeder:                 1 NRC ERDS Parameter:           STAB CLASS                         GRND LVL ATM STAB Point ID:                     CALC526 CLASS (15 MIN)
-1.9 -1.7 B 2 
Plant Spec Point Desc:       Stability Class Lower GenericCond Desc:             Air Stability Lower Analog/Digital:
-1.7 -1.5 C 3   -1.5 -0.5 D 4  -0.5 1.5 E 5 1.5 4.0 F 6 4.0  G 7 
Engr Units/Dig States:       STABA Engr Units Minimum Instr Range:
 
Maximum Instr Range:
BFN Unit 3 Emergency Response Data System (ERDS) Data Point Library 3-TI-411 Rev. 0003 Page 43 of 45 Appendix A (Page 38 of 40)
ERDS Point Number: 36 STAB CLASS CALC526 Air Stability Lower Date: 09/19/2012 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: STAB CLASS Point ID: CALC526 Plant Spec Point Desc: Stability Class Lower GenericCond Desc: Air Stability Lower  
 
Analog/Digital:
Engr Units/Dig States: STABA Engr Units Minimum Instr Range: Maximum Instr Range:
Zero Point  
Zero Point  


==Reference:==
==Reference:==
N/A Reference Point Notes: N/A  
N/A Reference Point Notes:       N/A PROC or SENS                 P Number of Sensors:           2 How Processed:
 
PROC or SENS P Number of Sensors: 2 How Processed:
Sensor Locations:
Sensor Locations:
Alarm/Trip Set Points: No ALarms  
Alarm/Trip Set Points:       No ALarms NID Power Cutoff Level:       N/A NID Power Cut-On             N/A Instrument Failure Mode:     LOW Temperature Compensation:     N Level Reference Leg:         N/A Unique System Desc:           Differential Temperature Intermed-Lower (deg C)
 
Difference
NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Differential Temperature Intermed-Lower (deg C)   Difference     > <= Stability Class Point Value
                                >         <=     Stability Class     Point Value
  -1.9 A 1
                                          -1.9           A                   1
-1.9 -1.7 B 2
                                -1.9     -1.7           B                   2
-1.7 -1.5 C 3   -1.5 -0.5 D 4   -0.5 1.5 E 5 1.5 4.0 F 6 4.0 G 7}}
                                -1.7     -1.5           C                   3
                                -1.5     -0.5           D                   4
                                -0.5     1.5           E                   5 1.5       4.0           F                   6 4.0                     G                   7}}

Latest revision as of 11:33, 30 October 2019

Emergency Response Data System Changes
ML16335A077
Person / Time
Site: Browns Ferry  Tennessee Valley Authority icon.png
Issue date: 11/30/2016
From: Bono S
Tennessee Valley Authority
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML16335A077 (50)


Text

Tennessee Valley Authority, Post Office Box 2000, Decatur, Alabama 35609-2000 November 30, 2016 10 CFR 50.4 10 CFR 50, Appendix E ATTN : Document Control Desk U.S. Nuclear Regulatory Commission Washington, D.C. 20555-0001 Browns Ferry Nuclear Plant, Units 1, 2, and 3 Renewed Facility Operating License Nos. DPR-33, DPR-52, and DPR-68 NRC Docket Nos. 50-259, 50-260, and 50-296

Subject:

Emergency Response Data System Changes The purpose of this letter is to provide changes to the Emergency Response Data System (EROS), as required by Title 10 of the Code of Federal Regulations (10 CFR) 50, Appendix E, Section Vl.3, "Maintaining Emergency Response Data System" for Browns Ferry Nuclear Plant (BFN), Units 1, 2, and 3.

The Tennessee Valley Authority performed a review of the EROS Data Point Library to identify discrepancies between the EROS Data Point Library and the applicable technical instructions.

Several EROS points were changed in the Data Point Library but were not changed in the applicable technical instructions. Additionally, these changes were not submitted to the NRC in accordance with 10 CFR 50, Appendix E, Section Vl.3.a, which requires a notification within 30 days after any software or hardware changes to any transmitted data points identified in the Data Point Library are made. The changes to the EROS Data Point Library include instrument range parameters, alarm/trip set points Modes of operation, how data is processed, unique system description Modes of operation and parameters, plant specific point description titles, and engineering units. This deficiency has been entered into the Corrective Action Program.

The changes to the EROS Data Point Library are summarized in the Enclosure.

There are no new regulatory commitments in this letter. Please direct questions concerning this issue to Jamie L. Paul at (256) 729-2636.

U.S. Nuclear Regulatory Commission Page 2 November 30, 2016

Enclosure:

Emergency Response Data System Data Point Library Change cc (w/Enclosure):

NRC Regional Administrator - Region II NRC Senior Resident Inspector - Browns Ferry Nuclear Plant

ENCLOSURE Browns Ferry Nuclear Plant Units 1, 2, and 3 Emergency Response Data System Data Point Library Change (See Enclosed)

BFN Emergency Response Data System 1-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0003 Page 11 of 45 Appendix A (Page 6 of 40)

ERDS Point Number 4 REAC VES LEV SPDS0007 Reactor Vessel Water Level Date: 12/20/2006 Reactor Unit: BF1 Data Feeder: 1 NRC ERDS Parameter: REAC VES LEV Point ID: SPDS0007 Plant Spec Point Desc: RX WATER LEVEL - COMPOSED GenericCond Desc: Reactor Vessel Water Level Analog/Digital A Engr Units/Dig States: INCHES Engr Units N/A Minimum Instr Range: -268 Maximum Instr Range: 400 500 Zero Point

Reference:

MSSKRT Reference Point Notes: 528 above vessel zero PROC or SENS: P Number of Sensors: 11 How Processed: Weighted Average w/Fault Detect (PSVA)

Sensor Locations: N/A Alarm/Trip Set Points: All modes: HIHI=51, HI=39, LO=27, LOLO=2 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: Y Level Reference Leg: N/A 500 Combines one 0 - +400 (floodup), four + 70 (Normal), four -155 -

+ 60 (Emerg) and two -268 - +32 (post accident) into one wide range indication; therefore, for off normal conditions this point could be difficult to interpret. Instruments are calibrated for normal operating conditions, except for the floodup instrument which is calibrated for atmospheric conditions, and the post accident instruments which are calibrated assuming 212 degrees Fahrenheit water in all lines. Top of Unique System Desc.: fuel is at - 162.

BFN Emergency Response Data System 1-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0003 Page 12 of 45 Appendix A (Page 7 of 40)

ERDS Point Number 5 MAIN FD FLOW CALC040 Feedwater Flow into the Reactor Date: 12/20/2006 Reactor Unit: BF1 Data Feeder: 1 NRC ERDS Parameter: MAIN FD FLOW Point ID: CALC040 Plant Spec Point Desc: RFW FLOW TO REACTOR GenericCond Desc: Feedwater Flow into the Reactor Analog/Digital: A Engr Units/Dig States: MLB/HR Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 20 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: Sum of RFW LINE A and RFW LINE B Sensor Locations: N/A Alarm/Trip Set Points: Run: HIHI=14.8, HI=14.7 (EPU values HIHI=17.1, HI=17.0)

All modes: HIHI=17.1, HI=17.0 NID Power Cutoff Level: N/A NID Power Cut-On: N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc.: Sum of feedflow instruments (3-78A & 3-78B),

uncompensated

BFN Emergency Response Data System 1-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0003 Page 26 of 45 Appendix A (Page 21 of 40)

ERDS Point Number 19 MN STEAM RAD 90-138 Rad Level - Main Steam Line B Date: 12/20/2006 Reactor Unit: BF1 Data Feeder: 1 NRC ERDS Parameter: MN STEAM RAD Point ID: 90-138 Plant Spec Point Desc: MAIN STM LINE B RAD LEVEL GenericCond Desc: Rad Level -Main Steam Line B Analog/Digital A Engr Units/Dig States: MR/HR Engr Units N/A Minimum Instr Range: 1.0 Maximum Instr Range: 1000000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: SALG Sensor Locations: Main Steam Tunnel Alarm/Trip Set Points: All modes: HIHI=1500, HI=750 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc.:

Deleted page

BFN Emergency Response Data System 1-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0003 Page 27 of 45 Appendix A (Page 22 of 40)

ERDS Point Number 20 MN STEAM RAD 90-139 Rad Level - Main Steam Line D Date: 12/20/2006 Reactor Unit: BF1 Data Feeder: 1 NRC ERDS Parameter: MN STEAM RAD Point ID: 90-139 Plant Spec Point Desc: MAIN STM LINE D RAD LEVEL GenericCond Desc: Rad Level -Main Steam Line D Analog/Digital A Engr Units/Dig States: MR/HR Engr Units N/A Minimum Instr Range: 1.0 Maximum Instr Range: 1000000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: SALG Sensor Locations: Main Steam Tunnel Alarm/Trip Set Points: All modes: HIHI=1500, HI=750 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc.:

Deleted page

BFN Emergency Response Data System 1-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0003 Page 28 of 45 Appendix A (Page 23 of 40)

ERDS Point Number 21 DW PRESS SPDS0009 Drywell Pressure Date: 12/20/2006 Reactor Unit: BF1 Data Feeder: 1 NRC ERDS Parameter: DW PRESS Point ID: SPDS0009 Plant Spec Point Desc: DRYWELL PRESSURE - COMPOSED GenericCond Desc: Drywell Pressure Analog/Digital A Engr Units/Dig States: PSIG Engr Units N/A Minimum Instr Range: -15 Maximum Instr Range: 300 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 6 How Processed: Weighted Average w/Fault Detect (PSVA)

Sensor Locations: N/A Alarm/Trip Set Points: See Below NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc.: Alarm: Run: HIHI=2.45, HI=1.96, LO=1.15, LOLO=1.1 Startup: HIHI=2.45, HI=1.96, LO=1.15, LOLO=1.1 Shutdown: HIHI=2.45, HI=1.96, LO=1.15, LOLO=1.1 Refuel: HIHI=2.45, HI=1.96

BFN Emergency Response Data System 1-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0003 Page 32 of 45 Appendix A (Page 27 of 40)

ERDS Point Number 25 H2 CONC 76-39 Drywell or Torus Hydrogen Level Date: 12/20/2006 Reactor Unit: BF1 Data Feeder: 1 NRC ERDS Parameter: H2 CONC Hydrogen Point ID: 76-39 Plant Spec Point Desc: DRYWELL H2 CONCENTRATION Generic Cond Desc: Drywell or Torus Hydrogen Level Analog/Digital A Engr Units/Dig States:  %

Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 10 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Polynomial Number of Sensors: 1 How Processed: Weighted Average w/Fault Detect (PSVA)

Sensor Locations: N/A Alarm/Trip Set Points: All modes: HIHI=2.4 HI=2.0 LOLO=0.10 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Sensor input can be switched between the Torus and Drywell, Unique System Desc.: therefore this point may be difficult to interpret.

BFN Emergency Response Data System 1-TI-411 Unit 1 (ERDS) Data Point Library Rev. 0003 Page 34 of 45 Appendix A (Page 29 of 40)

Condensate Storage Tank #1 ERDS Point Number 27 CST LEVEL 2-169 (UNIT 1) Level Date: 12/20/2006 Reactor Unit: BF1 Data Feeder: 1 NRC ERDS Parameter: CST LEVEL Point ID: 2-169 Plant Spec Point Desc: CST #1 (UNIT 1) LEVEL GenericCond Desc: Condensate Storage Tank Level Analog/Digital A FT Engr Units/Dig States: FEET Engr Units 28 feet = 375,000 GALLONS Minimum Instr Range: 0 2 Maximum Instr Range: 32 Zero Point

Reference:

Below Reference Point Notes: 2 feet above bottom of tank PROC or SENS: S Number of Sensors: 1 How Processed: Polynomial Sensor Locations: N/A N/A Alarm/Trip Set Points: All modes: HIHI=29 HI=27 LO=12 LOLO=10 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc.: Zero level reference point is 2 feet above bottom of tank.

N/A

BFN Emergency Response Data 2-TI-411 Unit 2 System (ERDS) Data Point Library Rev. 0003 Page 10 of 45 Appendix A (Page 5 of 40)

ERDS Point Number: 3 NI SOURC RNG SPDS0041 Reactor Power - Source Range Date: 12/18/2000 Reactor Unit: BF2 Data Feeder: 1 NRC ERDS Parameter: NI SOURC RNG Point ID: SPDS0041 Plant Spec Point Desc: RX POWER SRM - AVG GenericCond Desc: Reactor Power - Source Range Analog/Digital: A Engr Units/Dig States: CPS Engr Units N/A 0.1 Minimum Instr Range: 1 Maximum Instr Range: 1000000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS P Number of Sensors: 4 How Processed: Average of healthy inputs (HAVE)

Sensor Locations: N/A Alarm/Trip Set Points: See Below NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Alarm: Startup/Shutdown/Refuel: HIHI=500000, HI=100000, LO=5, LOLO=3

BFN Emergency Response Data 2-TI-411 Unit 2 System (ERDS) Data Point Library Rev. 0003 Page 11 of 45 Appendix A (Page 6 of 40)

ERDS Point Number: 4 REAC VES LEV SPDS0007 Reactor Vessel Water Level Date: 12/18/2000 Reactor Unit: BF2 Data Feeder: 1 NRC ERDS Parameter: REAC VES LEV Point ID: SPDS0007 Plant Spec Point Desc: RX WATER LEVEL - COMPOSED GenericCond Desc: Reactor Vessel Water Level Analog/Digital: A Engr Units/Dig States: INCHES Engr Units N/A Minimum Instr Range: -268 Maximum Instr Range: 400 500 Zero Point

Reference:

MSSKRT Reference Point Notes: 528" above vessel zero PROC or SENS P Number of Sensors: 11 How Processed: Weighted Average w/Fault Detect (PSVA)

Sensor Locations: N/A Alarm/Trip Set Points: All modes: HIHI=51, HI=39, LO=27, LOLO=2 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: Y Level Reference Leg: N/A 500 Unique System Desc: Combines one 0 - +400 (floodup), four +70 (Normal), four -155 - +60 (Emerg) and two -268 - +32 (post accident) into one wide range indication; therefore, for off normal conditions this point could be difficult to interpret. Instruments are calibrated for normal operating conditions, except for the floodup instrument which is calibrated for atmospheric conditions, and the post accident instruments which are calibrated assuming 212 degrees Faranheit water in all lines. Top of fuel is at

-162".

BFN Emergency Response Data 2-TI-411 Unit 2 System (ERDS) Data Point Library Rev. 0003 Page 13 of 45 Appendix A (Page 8 of 40)

ERDS Point Number: 6 RCIC FLOW 71-36 Core Isolation Cooling Flow Date: 12/18/2000 Reactor Unit: BF2 Data Feeder: 1 NRC ERDS Parameter: RCIC FLOW Point ID: 71-36 Plant Spec Point Desc: RCIC PUMP DISCHARGE FLOW GenericCond Desc: Core Isolation Cooling Flow Analog/Digital: A Engr Units/Dig States: GPM Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 700 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 SQRT How Processed: Polynomial Sensor Locations: Downstream of Min Flow Line Alarm/Trip Set Points: All modes: HIHI=625 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:

BFN Emergency Response Data 2-TI-411 Unit 2 System (ERDS) Data Point Library Rev. 0003 Page 20 of 45 Appendix A (Page 15 of 40)

ERDS Point Number: 13 CND A/E RAD SPDS0047 Condensor Air Ejector Rad Level Date: 12/18/2000 Reactor Unit: BF2 Data Feeder: 1 NRC ERDS Parameter: CND A/E RAD TREATMENT-AVG Point ID: SPDS0047 Plant Spec Point Desc: OFFGAS POST TREATMENT AVG GenericCond Desc: Condensor Air Ejector Rad Level Analog/Digital: A Engr Units/Dig States: CPS Engr Units N/A 0.1 Minimum Instr Range: 1 Maximum Instr Range: 1000000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS P Number of Sensors: 2 How Processed: Healthy Average (HAVE)

Sensor Locations: N/A Alarm/Trip Set Points: See Below NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Alarm: Run/Startup: HIHI=290000, HI=58000, LOLO=10 Shutdown/Refuel: LOLO=10

BFN Emergency Response Data 2-TI-411 Unit 2 System (ERDS) Data Point Library Rev. 0003 Page 22 of 45 Appendix A (Page 17 of 40)

ERDS Point Number: 15 DW RAD 90-272A Drywell Radiation - 135 Deg Date: 12/18/2000 Reactor Unit: BF2 Data Feeder: 1 NRC ERDS Parameter: DW RAD Point ID: 90-272A Plant Spec Point Desc: DW RAD-RX 555, 135 DEG AZIMUTH GenericCond Desc: Drywell Radiation - 135 Deg Analog/Digital: A Engr Units/Dig States: R/HR Engr Units N/A 0.1 Minimum Instr Range: 1 Maximum Instr Range: 10000000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: SALG Sensor Locations: At Level 555, 135 Degree Azimuth Alarm/Trip Set Points: All modes: HIHI=1440, HI=1000 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:

BFN Emergency Response Data 2-TI-411 Unit 2 System (ERDS) Data Point Library Rev. 0003 Page 23 of 45 Appendix A (Page 18 of 40)

ERDS Point Number: 16 DW RAD 90-273A Drywell Radiation - 270 Deg Date: 12/18/2000 Reactor Unit: BF2 Data Feeder: 1 NRC ERDS Parameter: DW RAD Point ID: 90-273A Plant Spec Point Desc: DW RAD-RX 560, 270 DEG AZIMUTH GenericCond Desc: Drywell Radiation - 270 Deg Analog/Digital: A Engr Units/Dig States: R/HR Engr Units N/A 0.1 Minimum Instr Range: 1 Maximum Instr Range: 10000000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: SALG Sensor Locations: At Level 560, 270 Degree Azimuth Alarm/Trip Set Points: All modes: HIHI=1440, HI=1000 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:

BFN Emergency Response Data 2-TI-411 Unit 2 System (ERDS) Data Point Library Rev. 0003 Page 26 of 45 Appendix A (Page 21 of 40)

ERDS Point Number: 19 MN STEAM RAD 90-138 Rad Level - Main Steam Line B Date: 12/18/2000 Reactor Unit: BF2 Data Feeder: 1 NRC ERDS Parameter: MN STEAM RAD Point ID: 90-138 Plant Spec Point Desc: MAIN STM LINE B RAD LEVEL GenericCond Desc: Rad Level - Main Steam Line B Analog/Digital: A Engr Units/Dig States: MR/HR Engr Units N/A Minimum Instr Range: 1 Maximum Instr Range: 1000000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: SALG Sensor Locations: Main Steam Tunnel Alarm/Trip Set Points: All modes: HIHI=7200, HI=3600 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:

Deleted page

BFN Emergency Response Data 2-TI-411 Unit 2 System (ERDS) Data Point Library Rev. 0003 Page 27 of 45 Appendix A (Page 22 of 40)

ERDS Point Number: 20 MN STEAM RAD 90-139 Rad Level - Main Steam Line D Date: 12/18/2000 Reactor Unit: BF2 Data Feeder: 1 NRC ERDS Parameter: MN STEAM RAD Point ID: 90-139 Plant Spec Point Desc: MAIN STM LINE D RAD LEVEL GenericCond Desc: Rad Level - Main Steam Line D Analog/Digital: A Engr Units/Dig States: MR/HR Engr Units N/A Minimum Instr Range: 1 Maximum Instr Range: 1000000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: SALG Sensor Locations: Main Steam Tunnel Alarm/Trip Set Points: All modes: HIHI=7200, HI=3600 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:

Deleted page

BFN Emergency Response Data 2-TI-411 Unit 2 System (ERDS) Data Point Library Rev. 0003 Page 33 of 45 Appendix A (Page 28 of 40)

ERDS Point Number: 26 O2 CONC 76-43 Drywell or Torus Oxygen Level Date: 12/18/2000 Reactor Unit: BF2 Data Feeder: 1 NRC ERDS Parameter: O2 CONC Point ID: 76-43 Plant Spec Point Desc: DRYWELL OXYGEN CONCENTRATION GenericCond Desc: Drywell or Torus Oxygen Level Analog/Digital: A Engr Units/Dig States:  %

Engr Units N/A Minimum Instr Range: 0 25 Maximum Instr Range: 5 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: Polynomial Sensor Locations: N/A Alarm/Trip Set Points: All modes: HIHI=4.5, HI=4.0, LOLO=0.10 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: There are 2 sensors that can be switched between the Torus and Drywell. Normally 1 is set to each; therefore, this point may be difficult to interpret.

BFN Emergency Response Data 2-TI-411 Unit 2 System (ERDS) Data Point Library Rev. 0003 Page 34 of 45 Appendix A (Page 29 of 40)

ERDS Point Number: 27 CST LEVEL 2-161 Condensate Storage Tank Level Date: 12/18/2000 Reactor Unit: BF2 Data Feeder: 1 NRC ERDS Parameter: CST LEVEL Point ID: 2-161 Plant Spec Point Desc: CST #2 (UNIT 2) LEVEL GenericCond Desc: Condensate Storage Tank Level Analog/Digital: A FT Engr Units/Dig States: FEET Engr Units 28 feet = 375,000 GALLONS Minimum Instr Range: 0 2 Maximum Instr Range: 32 Zero Point

Reference:

Below Reference Point Notes: 2 feet above bottom of tank PROC or SENS S Number of Sensors: 1 How Processed: Polynomial Sensor Locations: N/A Alarm/Trip Set Points: All modes: HIHI=29, HI=27, LO=12, LOLO=10 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Zero point reference is 2 feet above the bottom of the tank.

N/A

BFN Emergency Response Data 2-TI-411 Unit 2 System (ERDS) Data Point Library Rev. 0003 Page 41 of 45 Appendix A (Page 36 of 40)

ERDS Point Number: 34 STAB CLASS CALC524 Stability Class Upper Date: 09/19/2012 Reactor Unit: BF2 Data Feeder: 1 NRC ERDS Parameter: STAB CLASS STACK LVL ATM STAB Point ID: CALC524 CLASS (15 MIN)

Plant Spec Point Desc: Stability Class Upper GenericCond Desc: Air Stability Upper Analog/Digital:

Engr Units/Dig States: STABA Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS P Number of Sensors: 2 How Processed:

Sensor Locations:

Alarm/Trip Set Points: No Alarms NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Differential Temperature Upper-Lower (deg C)

Difference

> <= Stability Class Point Value

-1.9 A 1

-1.9 -1.7 B 2

-1.7 -1.5 C 3

-1.5 -0.5 D 4

-0.5 1.5 E 5 1.5 4.0 F 6 4.0 G 7

BFN Emergency Response Data 2-TI-411 Unit 2 System (ERDS) Data Point Library Rev. 0003 Page 42 of 45 Appendix A (Page 37 of 40)

ERDS Point Number: 35 STAB CLASS CALC525 Air Stability Intermediate Date: 09/19/2012 Reactor Unit: BF2 Data Feeder: 1 NRC ERDS Parameter: STAB CLASS OVERALL ATM STAB Point ID: CALC525 CLASS (15 MIN)

Plant Spec Point Desc: Stability Class Intermediate GenericCond Desc: Air Stability Intermediate Analog/Digital:

Engr Units/Dig States: STABA Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS P Number of Sensors: 2 How Processed:

Sensor Locations:

Alarm/Trip Set Points: No Alarms NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Differential Temperature Upper-Intermed. (deg C)

Difference

> <= Stability Class Point Value

-1.9 A 1

-1.9 -1.7 B 2

-1.7 -1.5 C 3

-1.5 -0.5 D 4

-0.5 1.5 E 5 1.5 4.0 F 6 4.0 G 7

BFN Emergency Response Data 2-TI-411 Unit 2 System (ERDS) Data Point Library Rev. 0003 Page 43 of 45 Appendix A (Page 38 of 40)

ERDS Point Number: 36 STAB CLASS CALC526 Air Stability Lower Date: 09/19/2012 Reactor Unit: BF2 Data Feeder: 1 NRC ERDS Parameter: STAB CLASS Point ID: CALC526 GRND LVL ATM STAB Plant Spec Point Desc: Stability Class Lower CLASS (15 MIN)

GenericCond Desc: Air Stability Lower Analog/Digital:

Engr Units/Dig States: STABA Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS P Number of Sensors: 2 How Processed:

Sensor Locations:

Alarm/Trip Set Points: No ALarms NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Differential Temperature Intermed-Lower (deg C)

Difference

> <= Stability Class Point Value

-1.9 A 1

-1.9 -1.7 B 2

-1.7 -1.5 C 3

-1.5 -0.5 D 4

-0.5 1.5 E 5 1.5 4.0 F 6 4.0 G 7

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 9 of 45 Appendix A (Page 4 of 40)

ERDS Point Number: 2 NI INTER RNG CALCO45 Reactor Power - Intermediate Rng Date: 12/19/2000 CALC045 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: NI INTER RNG Point ID: CALCO45 CALC045 Plant Spec Point Desc: AVERAGE OF 8 IRM'S GenericCond Desc: Reactor Power - Intermediate Rng Analog/Digital: A Engr Units/Dig States: %SCALE Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 125 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS P Number of Sensors: 8 AVE How Processed: Average (AVG)

Sensor Locations: N/A Alarm/Trip Set Points: See Below NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Since the IRMs have a range switch this average is difficult to interpret.

Alarm: Run: HIHI=120 Startup: HIHI=108 HI=80 LO=20 LOLO=15 Shutdown: HIHI=50 HI=25 Refuel: HIHI=50 HI=25

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 11 of 45 Appendix A (Page 6 of 40)

ERDS Point Number: 4 REAC VES LEV SPDS0007 Reactor Vessel Water Level Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: REAC VES LEV Point ID: SPDS0007 Plant Spec Point Desc: RX WATER LEVEL - COMPOSED GenericCond Desc: Reactor Vessel Water Level Analog/Digital: A Engr Units/Dig States: INCHES Engr Units N/A Minimum Instr Range: -268 Maximum Instr Range: 400 500 Zero Point

Reference:

MSSKRT Reference Point Notes: 528" above vessel zero PROC or SENS P Number of Sensors: 11 How Processed: Weighted Average w/Fault Detect (PSVA)

Sensor Locations: N/A Alarm/Trip Set Points: All modes: HIHI=51 HI=39 LO=27 LOLO=2 NID Power Cutoff Level: N/A RUN/SU/SD NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: Y 500 Level Reference Leg: N/A Unique System Desc: Combines one 0 - +400 (floodup), four +70 (Normal), four

-155 - +60 (Emerg) and two -268 - +32 (post accident) into one wide range indication; therefore, for off normal conditions this point could be difficult to interpret. Instruments are calibrated for normal operating conditions, except for the floodup instrument which is calibrated for atmospheric conditions, and the post accident instruments which are calibrated assuming 212 degrees Faranheit water in all lines. Top of fuel is at -162".

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 12 of 45 Appendix A (Page 7 of 40)

ERDS Point Number: 5 MAIN FD FLOW CALCO40 Feedwater Flow into the Reactor Date: 12/19/2000 CALC040 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: MAIN FD FLOW Point ID: CALCO40 CALC040 Plant Spec Point Desc: RFW FLOW TO REACTOR GenericCond Desc: Feedwater Flow into the Reactor Analog/Digital: A Engr Units/Dig States: MLB/HR Engr Units N/A Minimum Instr Range: 0 20 Maximum Instr Range: 16 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS P Number of Sensors: 2 How Processed: Sum of RFW LINE A and RFW LINE B Sensor Locations: N/A Alarm/Trip Set Points: Run: HIHI=14.8 HI=14.7 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Sum of feedflow instruments, uncompensated

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 13 of 45 Appendix A (Page 8 of 40)

ERDS Point Number: 6 RCIC FLOW 71-36 Core Isolation Cooling Flow Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: RCIC FLOW Point ID: 71-36 Plant Spec Point Desc: RCIC PUMP DISCHARGE FLOW GenericCond Desc: Core Isolation Cooling Flow Analog/Digital: A Engr Units/Dig States: GPM Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 700 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS S SQRT Number of Sensors: 1 How Processed: Polynomial Sensor Locations: Downstream of Min Flow Line Alarm/Trip Set Points: All modes: HIHI=625 RUN/SU/SD NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 14 of 45 Appendix A (Page 9 of 40)

ERDS Point Number: 7 RCS PRESSURE SPDS0008 Reactor Coolant System Pressure Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: RCS PRESSURE Point ID: SPDS0008 Plant Spec Point Desc: RX PRESSURE - COMPOSED GenericCond Desc: Reactor Coolant System Pressure Analog/Digital: A Engr Units/Dig States: PSIG Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 1500 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS P Number of Sensors: 6 How Processed: Weighted Average w/Fault Detect (PSVA)

Sensor Locations: N/A Alarm/Trip Set Points: See Below NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: Y Level Reference Leg: N/A Unique System Desc: Instruments are calibrated for rated operating conditions.

Alarm: Run: HIHI=1073 HI=1070 LO=918 LOLO=915 Startup: HIHI=1073 HI=1070 LO=918 LOLO=915 Shutdown: HIHI=1073 HI=1070 Refuel: HIHI=1073 HI=1070

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 15 of 45 Appendix A (Page 10 of 40)

ERDS Point Number: 8 HPCI FLOW 73-33 High Pressure Coolant Inj. Flow Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: HPCI FLOW Point ID: 73-33 Plant Spec Point Desc: HPCI Pump Discharge Flow GenericCond Desc: High Pressure Coolant Inj. Flow Analog/Digital: A Engr Units/Dig States: GPM Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 6000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: Polynomial Sensor Locations: Downstream of Min Flow Line Alarm/Trip Set Points: All modes: HIHI=5200 RUN/SU/SD NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 16 of 45 Appendix A (Page 11 of 40)

ERDS Point Number: 9 LPCI FLOW 74-50 LPCI - RHR System 1 Flow Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: LPCI FLOW Point ID: 74-50 Plant Spec Point Desc: RHR SYS I FLOW GenericCond Desc: LPCI - RHR System 1 Flow Analog/Digital: A Engr Units/Dig States: GPM Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 25000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: Polynomial Sensor Locations: Downstream of HX and Before Sprays Alarm/Trip Set Points: All Modes: HIHI=20000 HI=13000 RUN/SU/SD NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 17 of 45 Appendix A (Page 12 of 40)

ERDS Point Number: 10 LPCI FLOW 74-64 LPCI - RHR System II Flow Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: LPCI FLOW Point ID: 74-64 Plant Spec Point Desc: RHR SYS II FLOW GenericCond Desc: LPCI - RHR System II Flow Analog/Digital: A Engr Units/Dig States: GPM Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 25000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: Polynomial Sensor Locations: Downstream of HX and Before Sprays Alarm/Trip Set Points: All modes: HIHI=20000 HI=13000 RUN/SU/SD NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 18 of 45 Appendix A (Page 13 of 40)

ERDS Point Number: 11 CR SPRAY FL 75-21 Core Spray - System I Flow Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: CR SPRAY FL Point ID: 75-21 Plant Spec Point Desc: CORE SPRAY SYS I FLOW GenericCond Desc: Core Spray - System I Flow Analog/Digital: A Engr Units/Dig States: GPM Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 10000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: Polynomial Sensor Locations: Downstream of Min Flow Line Alarm/Trip Set Points: All modes: HIHI=6300 HI=6275 RUN/SU/SD NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 19 of 45 Appendix A (Page 14 of 40)

ERDS Point Number: 12 CR SPRAY FL 75-49 Core Spray - System II Flow Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: CR SPRAY FL Point ID: 75-49 Plant Spec Point Desc: CORE SPRAY SYS II FLOW GenericCond Desc: Core Spray - System II Flow Analog/Digital: A Engr Units/Dig States: GPM Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 10000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: Polynomial Sensor Locations: Downstream of Min Flow Line Alarm/Trip Set Points: All modes: HIHI=6300 HI=6275 RUN/SU/SD NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 21 of 45 Appendix A (Page 16 of 40)

ERDS Point Number: 14 CND A/E RAD 90-157 Offgas Pre Treatment Avg Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: CND A/E RAD Point ID: 90-157 Plant Spec Point Desc: OFFGAS PRE TREATMENT AVG GenericCond Desc: Offgas Pre Treatment Avg RADIATION Analog/Digital: A Engr Units/Dig States: MR/HR Engr Units N/A 1 Minimum Instr Range: .1 Maximum Instr Range: 1000000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: SALG Sensor Locations: N/A Alarm/Trip Set Points: Run/Startup: HIHI=1690 HI=845 LOLO=1 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: Downscale Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 22 of 45 Appendix A (Page 17 of 40)

ERDS Point Number: 15 DW RAD 90-272A Drywell Radiation - 45 Deg Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: DW RAD Point ID: 90-272A Plant Spec Point Desc: DW RAD-RX 582, 45 DEG AZIMUTH GenericCond Desc: Drywell Radiation - 45 Deg Analog/Digital: A Engr Units/Dig States: R/HR Engr Units N/A 0.1 Minimum Instr Range: 1 Maximum Instr Range: 10000000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: SALG Sensor Locations: At Level 582, 45 Degree Azimuth Alarm/Trip Set Points: All modes: HIHI=1440 HI=1000 RUN/SU/SD NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 23 of 45 Appendix A (Page 18 of 40)

ERDS Point Number: 16 DW RAD 90-273A Drywell Radiation - 270 Deg Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: DW RAD Point ID: 90-273A Plant Spec Point Desc: DW RAD-RX 560, 270 DEG AZIMUTH GenericCond Desc: Drywell Radiation - 270 Deg Analog/Digital: A Engr Units/Dig States: R/HR Engr Units N/A 0.1 Minimum Instr Range: 1 Maximum Instr Range: 10000000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: SALG Sensor Locations: At Level 560, 270 Degree Azimuth Alarm/Trip Set Points: All modes: HIHI=1440 HI=1000 RUN/SU/SD NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 24 of 45 Appendix A (Page 19 of 40)

ERDS Point Number: 17 MN STEAM RAD 90-136 Rad Level - Main Steam Line A Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: MN STEAM RAD Point ID: 90-136 Plant Spec Point Desc: MAIN STM LINE A RAD LEVEL GenericCond Desc: Rad Level - Main Steam Line A Analog/Digital: A Engr Units/Dig States: MR/HR Engr Units N/A Minimum Instr Range: 1 Maximum Instr Range: 1000000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: SALG Sensor Locations: Main Steam Tunnel Alarm/Trip Set Points: All modes: HIHI=1500 HI=750 RUN/SU/SD NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 25 of 45 Appendix A (Page 20 of 40)

ERDS Point Number: 18 MN STEAM RAD 90-137 Rad Level - Main Steam Line C Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: MN STEAM RAD Point ID: 90-137 Plant Spec Point Desc: MAIN STM LINE C RAD LEVEL GenericCond Desc: Rad Level - Main Steam Line C Analog/Digital: A Engr Units/Dig States: MR/HR Engr Units N/A Minimum Instr Range: 1 Maximum Instr Range: 1000000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: SALG Sensor Locations: Main Steam Tunnel Alarm/Trip Set Points: All modes: HIHI=1500 HI=750 RUN/SU/SD NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 26 of 45 Appendix A (Page 21 of 40)

ERDS Point Number: 19 MN STEAM RAD 90-138 Rad Level - Main Steam Line B Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: MN STEAM RAD Point ID: 90-138 Plant Spec Point Desc: MAIN STM LINE B RAD LEVEL GenericCond Desc: Rad Level - Main Steam Line B Analog/Digital: A Engr Units/Dig States: MR/HR Engr Units N/A Minimum Instr Range: 1 Maximum Instr Range: 1000000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: SALG Sensor Locations: Main Steam Tunnel Alarm/Trip Set Points: All modes: HIHI=1500 HI=750 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:

Deleted page

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 27 of 45 Appendix A (Page 22 of 40)

ERDS Point Number: 20 MN STEAM RAD 90-139 Rad Level - Main Steam Line D Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: MN STEAM RAD Point ID: 90-139 Plant Spec Point Desc: MAIN STM LINE D RAD LEVEL GenericCond Desc: Rad Level - Main Steam Line D Analog/Digital: A Engr Units/Dig States: MR/HR Engr Units N/A Minimum Instr Range: 1 Maximum Instr Range: 1000000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: SALG Sensor Locations: Main Steam Tunnel Alarm/Trip Set Points: All modes: HIHI=1500 HI=750 NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc:

Deleted page

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 28 of 45 Appendix A (Page 23 of 40)

ERDS Point Number: 21 DW PRESS SPDS0009 Drywell Pressure Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: DW PRESS Point ID: SPDS0009 Plant Spec Point Desc: DRYWELL PRESSURE - COMPOSED GenericCond Desc: Drywell Pressure Analog/Digital: A Engr Units/Dig States: PSIG Engr Units N/A Minimum Instr Range: -15 Maximum Instr Range: 300 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS P Number of Sensors: 6 How Processed: Weighted Average w/Fault Detect (PSVA)

Sensor Locations: N/A Alarm/Trip Set Points: See below NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Alarm: Run: HIHI=2.45 HI=1.96 LO=1.15 LOLO=1.1 Startup/Shutdown/

Refuel: HIHI=2.45 HI=1.96

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 29 of 45 Appendix A (Page 24 of 40)

ERDS Point Number: 22 DW TEMP SPDS0010 Drywell Temperature Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: DW TEMP Point ID: SPDS0010 Plant Spec Point Desc: DRYWELL TEMPERATURE - COMPOSED GenericCond Desc: Drywell Temperature Analog/Digital: A Engr Units/Dig States: DEGF Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 400 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS P Number of Sensors: 2 How Processed: Weighted Average w/Fault Detect (PSVA)

Sensor Locations:

Alarm/Trip Set Points: See Below NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Alarm: Run: HIHI=160 HI=145 LO=100 LOLO=70 Startup: HIHI=160 HI=145 LO=90 LOLO=70 Shutdown/Refuel: HIHI=160 HI=145 LO=65 LOLO=60

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 30 of 45 Appendix A (Page 25 of 40)

ERDS Point Number: 23 SP TEMP SPDS0016 Suppression Pool Temperature Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: SP TEMP Point ID: SPDS0016 Plant Spec Point Desc: SUPPR PL WTR TEMP - COMPOSED GenericCond Desc: Suppression Pool Temperature Analog/Digital: A Engr Units/Dig States: DEGF Engr Units N/A Minimum Instr Range: 30 Maximum Instr Range: 230 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS P Number of Sensors: 16 How Processed: Average (PSVA)

Sensor Locations: Around Circumference of Torus Alarm/Trip Set Points: All modes: HIHI=95 HI=93 LOLO=50 RUN/SU/SD NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: There are 4 inputs actually scanned by the computer. Two of these 4 are made of 8 individual sensors that are hardware averaged. The other 2 are selected individual sensors from the total 16 sensors.

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 31 of 45 Appendix A (Page 26 of 40)

ERDS Point Number: 24 SP LEVEL SPDS0013 Suppression Pool Water Level Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: SP LEVEL Point ID: SPDS0013 Plant Spec Point Desc: SUPPR PL WTR LVL (IN) - COMPOSED GenericCond Desc: Suppression Pool Water Level Analog/Digital: A Engr Units/Dig States: INCHES Engr Units N/A Minimum Instr Range: -181.45 Maximum Instr Range: 58.55 Zero Point

Reference:

Below Reference Point Notes: 181.45 inches above Torus Bottom PROC or SENS P Number of Sensors: 4 How Processed: Weighted Average w/Fault Detect (PSVA)

Sensor Locations: N/A Alarm/Trip Set Points: See Below NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: All modes: HIHI = -1 HI = -2 LO = -5.5 LOLO = -6.25 RUN/SU/SD

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 32 of 45 Appendix A (Page 27 of 40)

ERDS Point Number: 25 H2 CONC SPDS0017 Drywell or Torus Hydrogen Level Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: H2 CONC Point ID: SPDS0017 Plant Spec Point Desc: DRYWELL H2 - COMPOSED GenericCond Desc: Drywell or Torus Hydrogen Level Analog/Digital: A Engr Units/Dig States:  %

Engr Units N/A Minimum Instr Range: 0 Maximum Instr Range: 20 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS P Number of Sensors: 2 How Processed: Weighted Average w/Fault Detect (PSVA)

Sensor Locations: N/A Alarm/Trip Set Points: All modes: HIHI=2.4 HI=2.0 LOLO=0.10 RUN/SU/SD NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: There are 2 sensors that can be switched between the Torus and Drywell. Normally 1 is set to each; therefore, this point may be difficult to interpret.

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 33 of 45 Appendix A (Page 28 of 40)

ERDS Point Number: 26 O2 CONC 76-43 Drywell or Torus Oxygen Level Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: O2 CONC Point ID: 76-43 Plant Spec Point Desc: DRYWELL OXYGEN CONCENTRATION GenericCond Desc: Drywell or Torus Oxygen Level Analog/Digital: A Engr Units/Dig States:  %

Engr Units N/A Minimum Instr Range: 0 25 Maximum Instr Range: 5 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS S Number of Sensors: 1 How Processed: Polynomial Sensor Locations: N/A Alarm/Trip Set Points: All modes: HIHI=4.5 HI=4.0 LOLO=0.10 RUN/SU/SD NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: There are 2 sensors that can be switched between the Torus and Drywell. Normally 1 is set to each; therefore, this point may be difficult to interpret.

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 34 of 45 Appendix A (Page 29 of 40)

ERDS Point Number: 27 CST LEVEL 2-165 Condensate Storage Tank Level Date: 12/19/2000 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: CST LEVEL Point ID: 2-165 Plant Spec Point Desc: CST #3 (UNIT 3) LEVEL GenericCond Desc: Condensate Storage Tank Level FT Analog/Digital: A Engr Units/Dig States: FEET Engr Units 28 feet = 375,000 GALLONS Minimum Instr Range: 0 2 Maximum Instr Range: 32 Zero Point

Reference:

Below Reference Point Notes: 2 feet above bottom of tank PROC or SENS S Number of Sensors: 1 How Processed: Polynomial Sensor Locations: N/A Alarm/Trip Set Points: All modes: HIHI=29 HI=27 LO=12 LOLO=10 RUN/SU/SD NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Zero point reference is 2 feet above the bottom of the tank.

N/A

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 41 of 45 Appendix A (Page 36 of 40)

ERDS Point Number: 34 STAB CLASS CALC524 Stability Class Upper Date: 09/19/2012 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: STAB CLASS STACK LVL ATM STAB Point ID: CALC524 CLASS (15 MIN)

Plant Spec Point Desc: Stability Class Upper GenericCond Desc: Stability Class Upper Analog/Digital:

Engr Units/Dig States: STABA Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS P Number of Sensors: 2 How Processed:

Sensor Locations:

Alarm/Trip Set Points: No Alarms NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Differential Temperature Upper-Lower (deg C)

Difference

> <= Stability Class Point Value

-1.9 A 1

-1.9 -1.7 B 2

-1.7 -1.5 C 3

-1.5 -0.5 D 4

-0.5 1.5 E 5 1.5 4.0 F 6 4.0 G 7

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 42 of 45 Appendix A (Page 37 of 40)

ERDS Point Number: 35 STAB CLASS CALC525 Air Stability Intermediate Date: 09/19/2012 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: STAB CLASS Point ID: CALC525 OVERALL ATM STAB Plant Spec Point Desc: Stability Class Intermediate CLASS (15 MIN)

GenericCond Desc: Air Stability Intermediate Analog/Digital:

Engr Units/Dig States: STABA Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS P Number of Sensors: 2 How Processed:

Sensor Locations:

Alarm/Trip Set Points: No Alarms NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: N/A Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Differential Temperature Upper-Intermed. (deg C)

Difference

> <= Stability Class Point Value

-1.9 A 1

-1.9 -1.7 B 2

-1.7 -1.5 C 3

-1.5 -0.5 D 4

-0.5 1.5 E 5 1.5 4.0 F 6 4.0 G 7

BFN Emergency Response Data 3-TI-411 Unit 3 System (ERDS) Data Point Library Rev. 0003 Page 43 of 45 Appendix A (Page 38 of 40)

ERDS Point Number: 36 STAB CLASS CALC526 Air Stability Lower Date: 09/19/2012 Reactor Unit: BF3 Data Feeder: 1 NRC ERDS Parameter: STAB CLASS GRND LVL ATM STAB Point ID: CALC526 CLASS (15 MIN)

Plant Spec Point Desc: Stability Class Lower GenericCond Desc: Air Stability Lower Analog/Digital:

Engr Units/Dig States: STABA Engr Units Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS P Number of Sensors: 2 How Processed:

Sensor Locations:

Alarm/Trip Set Points: No ALarms NID Power Cutoff Level: N/A NID Power Cut-On N/A Instrument Failure Mode: LOW Temperature Compensation: N Level Reference Leg: N/A Unique System Desc: Differential Temperature Intermed-Lower (deg C)

Difference

> <= Stability Class Point Value

-1.9 A 1

-1.9 -1.7 B 2

-1.7 -1.5 C 3

-1.5 -0.5 D 4

-0.5 1.5 E 5 1.5 4.0 F 6 4.0 G 7