{{#Wiki_filter:BFN-26 Table 11.6-1 Cooling Tower Mechanical Design Parameters (Helper Mode, non-EPU Conditions) Cooling Tower No. 1 2 3 4 5 6 7 Number of Cells 16 16 16 16 16 16 28 Design Flow Rate (GPM) 275,000 275,000 275,000 275,000 275,000 275,000 410,000 Cold Water Temperature (ºF) 84 84 90.8 91 90 90.8 90 Wet Bulb Temperature (ºF) 55 55 82 80 82 82 82 Range (ºF) 31.7 31.7 22.9 28.2 28.5 22.9 28.5 | {{#Wiki_filter:BFN-26 Table 11.6-1 Cooling Tower Mechanical Design Parameters (Helper Mode, non-EPU Conditions) Cooling Tower No. 1 2 3 4 5 6 7 Number of Cells 16 16 16 16 16 16 28 Design Flow Rate (GPM) 275,000 275,000 275,000 275,000 275,000 275,000 410,000 Cold Water Temperature (ºF) 84 84 90.8 91 90 90.8 90 Wet Bulb Temperature (ºF) 55 55 82 80 82 82 82 Range (ºF) 31.7 31.7 22.9 28.2 28.5 22.9 28.5}} | ||
}} |
Revision as of 02:36, 18 May 2018
ML18023B246 | |
Person / Time | |
---|---|
Site: | Browns Ferry ![]() |
Issue date: | 10/05/2017 |
From: | Tennessee Valley Authority |
To: | Office of Nuclear Reactor Regulation |
Shared Package | |
ML18018A778 | List:
|
References | |
Download: ML18023B246 (1) | |
Text
BFN-26 Table 11.6-1 Cooling Tower Mechanical Design Parameters (Helper Mode, non-EPU Conditions) Cooling Tower No. 1 2 3 4 5 6 7 Number of Cells 16 16 16 16 16 16 28 Design Flow Rate (GPM) 275,000 275,000 275,000 275,000 275,000 275,000 410,000 Cold Water Temperature (ºF) 84 84 90.8 91 90 90.8 90 Wet Bulb Temperature (ºF) 55 55 82 80 82 82 82 Range (ºF) 31.7 31.7 22.9 28.2 28.5 22.9 28.5