ML18023B246

From kanterella
Jump to navigation Jump to search
Updated Final Safety Analysis Report (Ufsar), Amendment 27, 11.6 Table - Condenser Circulating Water
ML18023B246
Person / Time
Site: Browns Ferry  
Issue date: 10/05/2017
From:
Tennessee Valley Authority
To:
Office of Nuclear Reactor Regulation
Shared Package
ML18018A778 List: ... further results
References
Download: ML18023B246 (1)


Text

BFN-26 Table 11.6-1 Cooling Tower Mechanical Design Parameters (Helper Mode, non-EPU Conditions)

Cooling Tower No.

1 2

3 4

5 6

7 Number of Cells 16 16 16 16 16 16 28 Design Flow Rate (GPM) 275,000 275,000 275,000 275,000 275,000 275,000 410,000 Cold Water Temperature (ºF) 84 84 90.8 91 90 90.8 90 Wet Bulb Temperature (ºF) 55 55 82 80 82 82 82 Range (ºF) 31.7 31.7 22.9 28.2 28.5 22.9 28.5