BFN-17 Table 12.3-1 PLANT RADIATION ZONE CLASSIFICATIONS

  • ** Shielding Access Access Design Dose Rate Action Requirements Zone Conditions Occupancy Dose Rate Range to Enter Zone

1 Unlimited Continuous <1.0 mRem/hr

2a Regulated Continuous 1.0 mRem/hr

2b Regulated Periodic 15 mRem/hr

3 Controlled Unoccupied 50-1,000 mRem/hr 4 Prohibited Unoccupied >1,000 mRem/hr

  • Access Dose Rate Range will meet 10 CFR 20 requirements as given in plant procedures. ** Action Requirements to Enter Zone are given in plant procedures.