| title = Standby Shutdown Facility (Ssf) Not Analyzed | | title = Standby Shutdown Facility (Ssf) Not Analyzed for All Operating Conditions | ||
| event text = On 3/29/2012 Duke Energy identified that unanalyzed conditions exist for SSF mitigated events since associated thermal and hydraulic analyses do not consider all initial operating conditions, especially lower operating modes and lower decay heat. Specifically there are four (4) conditions where the SSF is not currently analyzed: | | event text = On 3/29/2012 Duke Energy identified that unanalyzed conditions exist for SSF mitigated events since associated thermal and hydraulic analyses do not consider all initial operating conditions, especially lower operating modes and lower decay heat. Specifically there are four (4) conditions where the SSF is not currently analyzed: | ||
1. SSF operating at less than 525 degrees F and less than normal operating pressure (approximately 2155 psig), | 1. SSF operating at less than 525 degrees F and less than normal operating pressure (approximately 2155 psig), | ||
Latest revision as of 21:04, 1 March 2018
| Where | |
|---|---|
| Oconee South Carolina (NRC Region 2) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition | |
| Time - Person (Reporting Time:+1.32 h0.055 days <br />0.00786 weeks <br />0.00181 months <br />) | |
| Opened: | Stephen Newman 03:57 Apr 6, 2012 |
| NRC Officer: | Pete Snyder |
| Last Updated: | Apr 13, 2012 |
| 47810 - NRC Website
| |