| event date = 04/05/2012 22:38 EDT
| event date = 04/05/2012 22:38 EDT
| last update date = 04/13/2012
| last update date = 04/13/2012
| title = Standby Shutdown Facility (Ssf) Not Analyzed For All Operating Conditions
| title = Standby Shutdown Facility (Ssf) Not Analyzed for All Operating Conditions
| event text = On 3/29/2012 Duke Energy identified that unanalyzed conditions exist for SSF mitigated events since associated thermal and hydraulic analyses do not consider all initial operating conditions, especially lower operating modes and lower decay heat.  Specifically there are four (4) conditions where the SSF is not currently analyzed:
| event text = On 3/29/2012 Duke Energy identified that unanalyzed conditions exist for SSF mitigated events since associated thermal and hydraulic analyses do not consider all initial operating conditions, especially lower operating modes and lower decay heat.  Specifically there are four (4) conditions where the SSF is not currently analyzed:
1. SSF operating at less than 525 degrees F and less than normal operating pressure (approximately 2155 psig),
1. SSF operating at less than 525 degrees F and less than normal operating pressure (approximately 2155 psig),

Latest revision as of 21:04, 1 March 2018

ENS 47810 +/-
Where
Oconee Duke Energy icon.png
South Carolina (NRC Region 2)
Reporting
10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition
Time - Person (Reporting Time:+1.32 h0.055 days <br />0.00786 weeks <br />0.00181 months <br />)
Opened: Stephen Newman
03:57 Apr 6, 2012
NRC Officer: Pete Snyder
Last Updated: Apr 13, 2012
47810 - NRC Website