ENS Event | |
|---|---|
08:00 Sep 23, 2003 | |
| Title | Unanalyzed Condition Due to Potential Rcs Leakage at Oconee 1 |
| Event Description | During a scheduled bare metal visual inspection of the Unit 1 reactor vessel head prior to RV head retirement, evidence of possible through wall leakage was observed on two control rod drive mechanism (CRDM) and one thermocouple (T/C) penetrations (nozzles 6 and 16 and T/C nozzle 7). Of these locations, only the T/C had been previously repaired (plugged) in December 2000.
Initial Safety Significance: Any RCS leakage from these penetrations would have been below the threshold of measurability by the reactor coolant system leakage measurement process. Total measured RCS leakage prior to unit shutdown was varying between 0.15 gallons per minute and .24 gallons per minute. Corrective Action: The reactor vessel head is scheduled for replacement during the present refueling outage. Therefore, there are no plans at this time to perform additional inspections or repairs on the current head. The NRC Resident Inspector was notified. |
| Where | |
|---|---|
| Oconee South Carolina (NRC Region 2) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition | |
| Time - Person (Reporting Time:+3.25 h0.135 days <br />0.0193 weeks <br />0.00445 months <br />) | |
| Opened: | Randy Todd 11:15 Sep 23, 2003 |
| NRC Officer: | Rich Laura |
| Last Updated: | Sep 23, 2003 |
| 40192 - NRC Website
Loading map... {"minzoom":false,"maxzoom":false,"mappingservice":"leaflet","width":"350px","height":"250px","centre":false,"title":"","label":"","icon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"zoom":6,"defzoom":14,"layers":["OpenStreetMap"],"image layers":[],"overlays":[],"resizable":false,"fullscreen":false,"scrollwheelzoom":true,"cluster":false,"clustermaxzoom":20,"clusterzoomonclick":true,"clustermaxradius":80,"clusterspiderfy":true,"geojson":"","clicktarget":"","imageLayers":[],"locations":[{"text":"\u003Cb\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca class=\"mw-selflink selflink\"\u003EENS 40192\u003C/a\u003E - \u003Ca href=\"/Oconee\" title=\"Oconee\"\u003EOconee\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E\u003C/b\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003EUnanalyzed Condition Due to Potential Rcs Leakage at Oconee 1\n\u003C/p\u003E\u003C/div\u003E","title":"ENS 40192 - Oconee\n","link":"","lat":34.79336388888889,"lon":-82.89360555555555,"icon":"/w/images/7/75/Duke_Energy_icon.png"}],"imageoverlays":null} | |
Unit 1 | |
|---|---|
| Reactor critical | Not Critical |
| Scram | No |
| Before | Cold Shutdown (0 %) |
| After | Cold Shutdown (0 %) |
WEEKMONTHYEARENS 506402014-11-25T17:12:00025 November 2014 17:12:00
[Table view]10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Deficiency in Methodology Used for Emergency Core Cooling System Performance Requirements ENS 499682014-03-28T17:00:00028 March 2014 17:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Keowee Emergency Power System 13.8Kv Cable May Not Comply with Licensing Basis ENS 490682013-05-24T18:00:00024 May 2013 18:00:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition, 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material Heating Ventilation and Air Condition System Inadequately Analyzed for Heat Load ENS 478102012-04-06T02:38:0006 April 2012 02:38:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Standby Shutdown Facility (Ssf) Not Analyzed for All Operating Conditions ENS 423182006-02-07T01:50:0007 February 2006 01:50:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition - Non-Conforming Fire Barriers ENS 418502005-07-18T15:30:00018 July 2005 15:30:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Electrical Alignment Results in Single Failure Vulnerability ENS 417282005-05-24T17:50:00024 May 2005 17:50:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Involving Emergency Backup Power Generators ENS 407242004-05-04T20:55:0004 May 2004 20:55:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition and Potential Loss of Containment Safety Function ENS 401922003-09-23T08:00:00023 September 2003 08:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Due to Potential Rcs Leakage at Oconee 1 2014-03-28T17:00:00 | |
Retrieved from "https://kanterella.com/w/index.php?title=ENS_40192&oldid=428952"