ML17206A971: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(Created page by program invented by StriderTol)
Line 2: Line 2:
| number = ML17206A971
| number = ML17206A971
| issue date = 07/11/1979
| issue date = 07/11/1979
| title = Responds to NRC 790620 Ltr Re Violation Noted in Ie Insp Rept 50-335/79-14.Corrective Actions:Required Valves Are Locked & Prestart Check List Will Be Revised by 790801
| title = Responds to NRC 790620 Ltr Re Violation Noted in IE Insp Rept 50-335/79-14.Corrective Actions:Required Valves Are Locked & Prestart Check List Will Be Revised by 790801
| author name = UHRIG R E
| author name = UHRIG R E
| author affiliation = FLORIDA POWER & LIGHT CO.
| author affiliation = FLORIDA POWER & LIGHT CO.

Revision as of 01:58, 27 February 2018

Responds to NRC 790620 Ltr Re Violation Noted in IE Insp Rept 50-335/79-14.Corrective Actions:Required Valves Are Locked & Prestart Check List Will Be Revised by 790801
ML17206A971
Person / Time
Site: Saint Lucie NextEra Energy icon.png
Issue date: 07/11/1979
From: UHRIG R E
FLORIDA POWER & LIGHT CO.
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML17206A970 List:
References
NUDOCS 7908200013
Download: ML17206A971 (4)


See also: IR 05000335/1979014

Text

8P.BOX013100.MIAMI.FL33101pR~3FLORIDAPOWER8cLIGHTCOMPANYJulyll,1979L-79-189Mr.JamesP.O'Reilly,Director,RegionIIOfficeofInspectionandEnforcementU.S.NuclearRegulatoryCommission101MariettaStreet,Suite3100Atlanta,Georgia30303

DearMr.O'Reilly:

Re:RII:JAD50-335/79-14FloridaPower5LightCompanyhasreviewedthesubjectinspectionreportandaresponseisattached.Thereisnoproprietaryinformationinthereport.Verytrulyyours,obertE.UhrigVicePresidentAdvancedSystems&TechnologyREU/MAS/malAttachmentcc:HaroldF.Reis,EsquireO82OOOi~PEOPLE...SERVINGPEOPLE

ATTACHMENTRe.RII:JAB50-335/79-14FindinnAsrequiredbyTechnicalSpecification6.8.l.a,writtenproceduresarerequiredtobeestablished,implementedandmaintainedcoveringtheapplicableproce-duresrecommendedinAppendix"A"ofRegulatoryGuide1.33,November,1972.Contrarytotheabove:l.PlantOperatingProcedure0410020"HPSI/LPSI-NormalOperation",Section8.1wasnotfollowedinthatsafeguardspumpsminimumflowisolationvalveNV-3660,requiredtobelockedopen,wasfoundopenbutunlockedonJune7,1979.2.PlantOperatingProcedure0420020"ContainmentSpray-InitialValveAlignment",Section8.1.9divasnotfollowedinthatBheadereductorinletvalve07261,requiredtobelockedopen,wasfoundopenbutunlockedonJune7,19/9.~ResenseThevalvesrequiredtobelockedarenowlocked.,Theindividualsresponsibleforvalvelockinghavebeenapprisedoftheimportanceofthefinding.Thepre-startchecklistprocedure(AdministrativeProcedure0030120)willberevisedbyAugust1,1979.Therevisedprocedurewillrequireverificationofthelockedvalvelistforaparticularmodeofoperationpriortoentryintothatmode.Thisrequirementwillbemandatoryafteranyoutageinvolvingsignificantvalvemanipulation.