| NRC officer = Thomas Herrity | | NRC officer = Thomas Herrity | ||
| event date = 02/09/2024 13:22 EST | | event date = 02/09/2024 13:22 EST | ||
| last update date = 03/ | | last update date = 03/21/2024 | ||
| title = Unanalyzed Condition - Inadequate Fuses for Fuel Pool Cooling | | title = Unanalyzed Condition - Inadequate Fuses for Fuel Pool Cooling | ||
| event text = The following information was provided by the licensee via email: | | event text = The following information was provided by the licensee via email: | ||
Line 35: | Line 35: | ||
The NRC Senior Resident Inspector has been notified. | The NRC Senior Resident Inspector has been notified. | ||
Notified R1DO (Jackson) | Notified R1DO (Jackson) | ||
| URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2024/ | * * * UPDATE ON 3/21/2024 AT 1525 FROM PAUL BOKUS TO IAN HOWARD * * * | ||
The following information was provided by the licensee via email: | |||
On 03/21/24 at 1211, extent of condition reviews identified an annunciator circuit for the Unit 3 emergency service water (ESW) and high pressure service water (HPSW) pump structure heating and ventilation panel that is also uncoordinated due to improper fuse sizing. This circuit is not bounded by existing design and licensing documents for 10 CFR 50 Appendix R Fire Safe Shutdown and, therefore, this event is being reported as an eight-hour, non-emergency notification per 10 CFR 50.72(b)(3)(ii)(B). This event poses no impact to the health and safety of the public or plant personnel. | |||
The postulated event affects fire area 47 (Unit 3 pump structure for `B' ESW and `3A'-`3D' HPSW pumps) and the yard fire area (Manhole 026D). In order to restore immediate compliance, the cable has been de-energized to eliminate the possibility of the event of concern. This circuit will remain de-energized or other measures will be implemented until the condition is permanently resolved. | |||
The NRC Senior Resident Inspector has been notified. | |||
Notified R1DO (Ford) | |||
| URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2024/20240322en.html#en56957 | |||
}}{{unit info | }}{{unit info | ||
| Unit = 2 | | Unit = 2 |
Latest revision as of 07:30, 22 March 2024
Where | |
---|---|
Peach Bottom Pennsylvania (NRC Region 1) | |
Reporting | |
10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition | |
Time - Person (Reporting Time:+-3.25 h-0.135 days <br />-0.0193 weeks <br />-0.00445 months <br />) | |
Opened: | Bill Linell 15:07 Feb 9, 2024 |
NRC Officer: | Thomas Herrity |
Last Updated: | Mar 21, 2024 |
56957 - NRC Website
| |