ENS 56957: Difference between revisions

From kanterella
Jump to navigation Jump to search
(StriderTol Bot change)
(StriderTol Bot change)
Line 15: Line 15:
| NRC officer = Thomas Herrity
| NRC officer = Thomas Herrity
| event date = 02/09/2024 13:22 EST
| event date = 02/09/2024 13:22 EST
| last update date = 03/08/2024
| last update date = 03/13/2024
| title = Unanalyzed Condition - Inadequate Fuses for Fuel Pool Cooling  
| title = Unanalyzed Condition - Inadequate Fuses for Fuel Pool Cooling  
| event text = The following information was provided by the licensee via email:
| event text = The following information was provided by the licensee via email:
Line 28: Line 28:
The postulated event affects the following fire areas: 32, 33, 38 and 39 (Units 2 and 3 Switchgear Rooms). In accordance with procedural requirements, compensatory actions for the affected fire areas have been implemented and will remain until the condition is resolved.   
The postulated event affects the following fire areas: 32, 33, 38 and 39 (Units 2 and 3 Switchgear Rooms). In accordance with procedural requirements, compensatory actions for the affected fire areas have been implemented and will remain until the condition is resolved.   
The NRC Senior Resident Inspector has been notified.
The NRC Senior Resident Inspector has been notified.
Notified R1DO(Arner)
Notified R1DO (Arner)
| URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2024/20240311en.html#en56957
* * * UPDATE ON 3/13/2024 AT 1538 FROM TROY RALSTON TO SAM COLVARD * * *
On March 13, 2024, at 1350 EDT, extent of condition reviews identified a circuit in the Unit 2 reactor protection system (RPS) which is also uncoordinated due to improper fuse sizing. This circuit is not bounded by existing design and licensing documents for 10 CFR 50, Appendix R, Fire Safe Shutdown, therefore, this event is being reported as an eight-hour, non-emergency notification per 10 CFR 50.72(b)(3)(ii)(B). This event poses no impact to the health and safety of the public or plant personnel.
The postulated event affects fire area 57 (Switchgear Corridor, common to Units 2 and 3). In accordance with procedural requirements, compensatory actions for the affected fire areas have been implemented and will remain until the condition is resolved.
Additionally, it was previously reported that fire area 6N contained a circuit which was not bounded by the Fire Safe Shutdown analysis; however, after further review it has been determined that compliance is maintained in this fire area and is therefore retracted from the scope of this report.
The NRC Senior Resident Inspector has been notified.
Notified R1DO (Jackson)
| URL = https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2024/20240314en.html#en56957
}}{{unit info
}}{{unit info
| Unit = 2
| Unit = 2

Revision as of 07:30, 14 March 2024

ENS 56957 +/-
Where
Peach Bottom Constellation icon.png
Pennsylvania (NRC Region 1)
Reporting
10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition
Time - Person (Reporting Time:+-3.25 h-0.135 days <br />-0.0193 weeks <br />-0.00445 months <br />)
Opened: Bill Linell
15:07 Feb 9, 2024
NRC Officer: Thomas Herrity
Last Updated: Mar 13, 2024
56957 - NRC Website
Loading map...