| Inspector = T Taylor, A Scarbeary, J Corujo | | Inspector = T Taylor, A Scarbeary, J Corujo-Sandin, J Beavers, S Shah, M Holmberg, J Cassidy, S Sheldon, J Lennartz, J Laughlin, D Betancourtc, Zoias Sheldon, M Phalen, J Lennartz, K Walton, M Jones, T Taylor, A Scarbeary, E Sanchez-Santiago, D Alley | ||
| CCA = N/A for ROP | | CCA = N/A for ROP | ||
| INPO aspect = | | INPO aspect = | ||
| description = After reviewing CR-PLP-2012-4451, the inspectors were concerned the associated aging effects of the accumulated water were not properly managed because the condition of the affected annulus region was not evaluated by the licensee. Specifically, the accumulated water beneath the floor of the SIRW tank created an environment that could promote corrosion of the tank floor, and this condition does not appear to be formally evaluated. Also, the potential for corrosion could be exacerbated by concrete-aluminum interaction. The inspectors required more information to determine whether this issue constituted a finding of significance. This issue is considered an unresolved item pending further NRC review of the licensees actions. | | description = After reviewing CR-PLP-2012-4451, the inspectors were concerned the associated aging effects of the accumulated water were not properly managed because the condition of the affected annulus region was not evaluated by the licensee. Specifically, the accumulated water beneath the floor of the SIRW tank created an environment that could promote corrosion of the tank floor, and this condition does not appear to be formally evaluated. Also, the potential for corrosion could be exacerbated by concrete-aluminum interaction. The inspectors required more information to determine whether this issue constituted a finding of significance. This issue is considered an unresolved item pending further NRC review of the licensees actions. | ||
}} | }} |
Latest revision as of 19:46, 20 February 2018
Site: | Palisades |
---|---|
Report | IR 05000255/2012005 Section 4OA2 |
Date counted | Dec 31, 2012 (2012Q4) |
Type: | URI: |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71152 |
Inspectors (proximate) | T Taylor A Scarbeary J Corujo-Sandin J Beavers S Shah M Holmberg J Cassidy S Sheldon J Lennartz J Laughlin D Betancourtc Zoias Sheldon M Phalen J Lennartz K Walton M Jones T Taylor A Scarbeary E Sanchez-Santiago D Alley |